Emerson Fisher 63EG-98HM Instruction Manual Download Page 2

Specifications

This section lists the specifications for Type 63EG-98HM relief valves or backpressure regulators. Factory 

specifications are stamped on the main valve and pilot nameplates. The main valve nameplate is located on the 

main valve body. The pilot relief pressure range appears on the pilot nameplate. 

Main Valve Body Sizes and End Connection Styles

(1)

See Table 1

Maximum Design Pressure

(2)(3)

600 psig / 41.4 bar or body rating limit, whichever  

is lower

Maximum Operating Relief (Inlet) Pressure 

Including Build-up

(2)(3)

450 psig / 31.0 bar or body rating limit, whichever 

is lower

Maximum Outlet Pressure

(2)(3)

450 psig / 31.0 bar

Maximum Differential Pressure

(2)

400 psig / 27.6 bar

Relief Set Pressure/Backpressure Control Ranges

(4)

See Table 3

Port Diameter and Valve Plug Travels

See Table 2

Differential and Build-up Pressure Requirements

(2)

See Table 4

Temperature Capabilities

(2)(5)

Fluorocarbon (FKM): 

0 to 300°F / -18 to 149°C 

Not acceptable in water in excess of 180°F / 82°C

Ethylenepropylene (EPR):

Steel:

 -20 to 350°F / -29 to 177°C

Stainless steel: 

-40 to 350°F / -40 to 177°C

Perfluoroelastomer (FFKM): 

0 to 450°F /

-18 to 232°C

Main Valve Flow Characteristics

Linear 

(standard)

 or Whisper Trim™ III Cage (optional)

Pilot Control Line Connection

1/4 NPT

Pilot Spring Case Connection

1/4 NPT

Approximate Weights (Including pilot)

NPS 2 / DN 50 body: 

65 lbs / 29 kg

NPS 3 / DN 80 body: 

105 lbs / 48 kg 

NPS 4 / DN 100 body: 

155 lbs / 70 kg 

NPS 6 / DN 150 body: 

340 lbs / 154 kg

NPS 8 x 6 / DN 200 x 150 body: 

630 lbs / 286 kg

  1. Other ratings and end connections can usually be supplied; consult the local Sales Office. 

  2. The pressure/temperature limits in this Instruction Manual and any applicable standard limitation should not be exceeded. 

  3. Fluorocarbon (FKM) diaphragm is limited to 300 psig / 20.7 bar.

  4. Set pressure is defined as the pressure at which the pilot starts-to-discharge. 

  5.  Special low temperature constructions for process temperatures between -76 to 104°F / -60 to 40°C are available by request. The low temperature construction passed Emerson 

laboratory testing for lockup and external leakage down to -76°F / -60°C.

Table 1. 

Body Sizes and End Connection Styles

Table 2. 

Port Diameters and Valve Plug Travels

Table 3. 

Relief Set Pressure or Backpressure Control Ranges

MAIN VALVE BODY SIZE

END CONNECTION STYLE

NPS

DN

2

50

NPT, ASME CL150 RF, CL300 RF, 

CL600 RF or PN 16/25/40 flanged

3, 4, 6

80, 100, 150

ASME CL150 RF, CL300 RF, 

CL600 RF or PN 16/25/40 flanged

 8 x 6 

200 x 150

ASME CL150 RF, CL300 RF 

and CL600 RF flanged

BODY SIZE

PORT DIAMETER

VALVE PLUG TRAVEL

NPS

DN

In.

mm

In.

mm

2

50

2-3/8

60

1-1/8

29

3

80

3-3/8

86

1-1/2

38

4

100

4-3/8

111

2

51

6

150

7-3/16

183

2

51

8 x 6

200 x 150

7-3/16

183

2

51

CONTROL PRESSURE RANGE

(1)

PART NUMBER

COLOR

SPRING FREE LENGTH

SPRING WIRE DIAMETER

psig

bar

In.

mm

In.

mm

15 to 35

1.0 to 2.4

ERCA04288A0

Yellow

2.50

63.5

0.207

5.26

25 to 75

1.7 to 5.2

ERAA01910A0

Green

2.595

65.9

0.234

5.94

70 to 140

4.8 to 9.7

ERAA01911A0

Red

2.44

62.0

0.283

7.19

130 to 200

9.0 to 13.8

ERAA02889A0

Blue

2.250

57.2

0.331

8.41

100 to 375

6.9 to 25.9

ERCA04293A0

Unpainted

2.60

66.0

0.375

9.53

150 to 375

(2)

10.3 to 25.9

(2)

1N943427142

Unpainted

5.063

129

0.394

10.0

1. All springs may be backed off to 0 psig / 0 bar. However, highest capacities and best performances are obtained by using these springs in their recommended ranges.

2. 150 to 375 psig / 10.3 to 25.9 bar spring range is only for the Type MR98HH pilot construction; consult the local Sales Office for this option..

2

Type 63EG-98HM

Summary of Contents for Fisher 63EG-98HM

Page 1: ...condition may result in equipment damage or personal injury Use qualified personnel when installing operating and maintaining the Type 63EG 98HM Pilot Operated Relief Valve or Backpressure Regulator Figure 1 Type 63EG 98HM Pilot Operated Relief Valve or Backpressure Regulator Introduction Scope of the Manual This manual describes and provides instructions and a parts list for the Type 63EG 98HM re...

Page 2: ...and any applicable standard limitation should not be exceeded 3 Fluorocarbon FKM diaphragm is limited to 300 psig 20 7 bar 4 Set pressure is defined as the pressure at which the pilot starts to discharge 5 Special low temperature constructions for process temperatures between 76 to 104 F 60 to 40 C are available by request The low temperature construction passed Emerson laboratory testing for lock...

Page 3: ...e pilot exhaust faster than it can be replaced through the pilot restriction This permits inlet pressure to unbalance the main valve plug and open the main valve As inlet pressure drops below set pressure the pilot control spring closes the pilot valve plug Loading pressure again builds up to close the main valve plug WARNING Installation Personal injury equipment damage or leakage due to escaping...

Page 4: ... Call a qualified personnel when installing operating and maintaining relief valves and backpressure regulators Before installing inspect the main valve pilot and tubing for any shipment damage or foreign material that may have collected during crating and shipment Make certain the body interior is clean and the pipelines are free of foreign material Apply pipe compound only to the external pipe t...

Page 5: ... the main valve and pilot WARNING Maintenance Relief valve and backpressure regulator parts are subject to normal wear and must be inspected and replaced as necessary The frequency of inspection and replacement of parts depends upon the severity of service conditions or the requirements of local state and federal regulations Due to the care Emerson takes in meeting all manufacturing requirements h...

Page 6: ...nge and valve body side tappings 4 Remove the upside down body flange key 2 if it was anchored on the body Lightly lubricate the cage seating surfaces of the valve body web and the body flange Install the body flange on the body key 1 and secure it evenly with the cap WARNING 1 Screws or stud bolts key 3 Install the pilot and its pipe nipple and connect the pilot tubing 2 Install the spring key 9 ...

Page 7: ... 11 and onto the body key 1 Tighten the cap screws key 16 finger tight only 12 To ensure proper slack in the diaphragm key 12 apply some spring compression by turning the adjusting screw key 15 clockwise Finish tightening the cap screws key 16 with 10 to 13 ft lbs 13 56 to 17 63 N m of torque Table 5 Type 63EG Main Valve Body Part Numbers Key 1 BODY MATERIAL END CONNECTION STYLE PART NUMBER NPS 2 ...

Page 8: ...able 6 11 Cage NPS 2 DN 50 body 316 Stainless steel Linear Cage 34B5838X012 416 Stainless steel Whisper Trim Cage 24A5707X012 316 Stainless steel Whisper Trim Cage 24A5707X022 NPS 3 DN 80 body 316 Stainless steel Linear Cage 34B5839X012 416 Stainless steel Whisper Trim Cage 24A5708X012 316 Stainless steel Whisper Trim Cage 24A5708X042 NPS 4 DN 100 body 316 Stainless steel Linear Cage 34B5840X012 4...

Page 9: ...012 Perfluoroelastomer FFKM 1F2629X0042 Ethylenepropylene EPR 1F2629X0032 24 Drive Screw 4 required 1A368228982 25 Flow Arrow Key Description Part Number 26 Nameplate 27 Travel Indicator Plug Steel NPS 2 3 and 4 DN 50 80 and 100 bodies 17B4894X012 NPS 6 DN 150 17B4893X032 Stainless steel NPS 2 3 and 4 DN 50 80 and 100 bodies 17B4894X022 NPS 6 DN 150 body 17B4893X032 29 Hex Nut for stainless steel ...

Page 10: ...2 302 Stainless steel ERCA00496A0 13 Nameplate 14 Diaphragm Protector PTFE if required 11A5136X012 Key Description Part Number 15 Adjusting Screw Use with all other springs GF05553X012 Use with 150 to 375 psig 10 3 to 25 9 bar spring ERAA02340A0 16 Cap Screw 8 required Steel ERCA00100A0 Stainless steel ERCA00100A1 17 Jam Nut Steel ERCA00380A0 18 Drive Screw 4 required ERAA01884A0 24 Machine Screw ...

Page 11: ... 27 36 34 35 37 35A3174 A A2812 4 24 15 26 11 2 12 21 1 27 16 9 31 20 13 14 17 3 24 25 Figure 4 Type 63EG Main Valve FIXED RESTRICTION CONTROL LINE CONNECTION EXHAUST Figure 5 Type 63EG Main Valve Trim Package Figure 6 Type 63EG 98HM Mounting Parts 11 Type 63EG 98HM ...

Page 12: ...gement Regulator Technologies Inc does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Process Management Regulator Technologies Inc product remains solely with the purchaser APPLY 1 T THREAD LOCKER L1 GENERAL PURPOSE PTFE OR LITHIUM GREASE FOR O RINGS L2 ANTI SEIZE COMPOUND L4 GRAPHITE SEALANT FOR...

Reviews: