background image

 

1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx 

XWi70K

 

8/15 

 

16.6

 

DEFROST CONTROL (dEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 
restart only if the digital input is disabled otherwise the instrument will wait until the 

MdF

 safety time is 

expired. 

16.7

 

ENERGY SAVING (ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the 

SET+HES

 

(parameter) sum. This function is enabled until the digital input is activated. 

16.8

 

HOLIDAY MODE (HdF) 

Holiday mode activation. 

16.9

 

REMOTE LIGHT CONTROL (LIG) 

To manage the light activation from remote. 

16.10

 

REMOTE ON OFF (onF) 

To issue a remote ON/OFF command. 

16.11

 

PARAMETER MAP CHANGE (Lnt) 

To change the used parameter map from 

nt

 

(first configuration or “normal temperature”) to 

Lt 

(second 

configuration or “low temperature”) and vice

-versa. 

16.12

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the 

i1P

 or

 i2P

 parameters: 

i1P or i2P=CL:

 the input is activated by closing the contact.

 

i1P or i2P=OP:

 the input is activated by opening the contact 

17

 

HOW TO INSTALL AND MOUNT 

The controller 

XWi70K

 shall be mounted in a din rail and in a horizontal position or with the relay output 

on the bottom side (IEC/60730). 
It must be connected to the keyboard by using a 2-wire cable (

 1mm). The temperature range allowed 

for correct operation is 0 to 60°C. Avoid places subject to strong vibrations, corrosive gases, excessive 

dirt or humidity. The same recommendations apply to probes. Let the air free to circulate by the aeration 
holes. 

 

17.1

 

XWi70K 

 8 DIN CASE - DIMENSIONS 

 

18

 

ELECTRICAL CONNECTIONS 

XWi70K

 is provided with screw terminal blocks to connect cables with a cross section up to 2.5 mm

for 

the RS485 (optional) and the keyboard. To connect the other inputs, power supply and relays, 

XWi70K

 

is provided with Plug-in connections (6.3mm). Heat-resistant cables must be used. Before connecting 

cables make sure the power supply complies with the instrument’s requirements. Separate the probe 

cables from the power supply cables, from the outputs and the power connections. Do not exceed the 
maximum current allowed, in case of heavier loads use a suitable external relay. 

NOTE:

  

-

 

The maximum current allowed for the common line of the relays is 14A (IEC/60730)

 

-

 

The maximum current allowed for insulated relay (oA5) is 3A (IEC/60730)

 

18.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb upwards to prevent damages due to liquid infiltration. It is 

recommended to place the thermostat probe away from air streams to correctly measure the average 
room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, 
where  most  ice  is  formed,  far  from  heaters  or  from  the  warmest  place  during  defrost,  to  prevent 
premature defrost termination. 

 

19

 

TTL/RS485 SERIAL LINE 

The TTL connector allows, by means of the external module TTL/RS485 

(XJ485CX)

, to connect the unit 

to a network line 

ModBUS-RTU

 compatible as the 

Dixell

 monitoring system. The same TTL connector 

is used to upload and download the parameter list of the “

HOT-KEY

”. 

 

20

 

HOW TO 

USE OF THE “HOT KEY”

 

NOTE: the XWi controllers need a 64KB HOT KEY (Dixell code: 

DK00000300

). Standard Hot Key is not 

supported. 

20.1

 

PROGRAM A HOT-KEY FROM AN INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON

,  insert  the  “

HOT-KEY

”  and  push 

UP 

button;  t

he  “

uPL

 

message 

appears followed a by a flashing “

End

” label.

 

3.

 

Push 

SET 

button and the “

End

” will stop flashing.

 

4.

 

Turn OFF 

the instrument, remove the “

HOT-KEY

” and

 

then turn it ON again. 

 

NOTE

: the “

Err

” message appears in case of a failed programming opera

tion. In this case push again 

button if you want to restart the upload again or remove the “

HOT-KEY

” to abort the operation.

 

20.2

 

HOT TO CHANGE PARAMETER MAP BY USING AN HOT-KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a 

pre-programmed 

HOT-KEY

 into the 5-PIN port 

and then turn the Controller ON. 

3.

 

The  parameter  list  of  the  “

HOT-KEY

”  will  be  automatically  downloaded  into  the  Controller 

memory. The “

doL

” message will blink followed a by a flashing “

End

” label.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “

HOT-KEY

”.

 

 

NOTE: 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then on 

if you want to restart the download again or remov

e the “

HOT-KEY

” to abort the operation.

 

21

 

INTERNAL MEMORY 

The controller has an internal memory where are stored: 
-

 

Parameter maps 

nt

 and 

Lt

 

-

 

Factory default configurations for both 

nt

 and 

Lt

 parameters map 

 
The controller is always shipped with: 
-

 

Parameter map 

nt

 

= factory default configuration “

nt

 

-

 

Parameter map 

Lt

 

= factory default configuration “

Lt

 

Any modification to parameter map 

nt

 or 

Lt

 does not change factory values. 

It  will be  possible to restore factory  defaults values for 

nt

  or 

Lt

 parameters map  by  using 

UP2=CC

 

function.  

 
NOTES:  

-

 

If  controller  is  using 

nt

  parameter  map,  the  factory  default  configuration 

nt

  will  be  reloaded 

overwriting 

nt

 parameter map. The same for parameter map 

Lt

-

 

The factory default configurations are read only (it is not possible to modify them on the field). 

22

 

ALARM SIGNALS 

Message  Cause 

Outputs 

P1 

Thermostat probe failure 

Alarm  output  ON;  Compressor  output  according  to 
parameters 

Con

 and 

CoF

 

P2 

Second probe failure 

Alarm output ON; Other outputs unchanged 

P3 

Third probe failure 

Alarm output ON; Other outputs unchanged 

P4 

Fourth probe failure 

Alarm output ON; Other outputs unchanged 

HA 

Maximum temperature alarm 

Alarm output ON; Other outputs unchanged 

LA 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged 

HA2 

Condenser high temperature 

It depends on the 

AC2

 parameter 

LA2 

Condenser low temperature 

It depends on the 

bLL

 parameter 

dA 

Door open 

Compressor and fans restarts  

EA 

Warning 

Output unchanged 

CA 

Lock alarm (i1F=bAL) 

All outputs OFF 

CA 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

EE 

Data or memory failure 

Alarm output ON; Other outputs unchanged 

noL 

No communication between base 
and keyboard 

Unchanged 

EC1 

VSC communication error 

Unchanged 

 
The alarm message is displayed until the alarm condition is recovery. 

All the alarm messages are showed alternating with the room temperature except for the “P1” which is 

flashing. 

To reset the “EE” alarm and restart the normal functioning press any key, the “

rSt

” message is displayed 

for about 3 sec. 

22.1

 

SERIAL COMPRESSOR AND MODBUS FAN MANAGEMENT 

The following table shows the managed alarms and errors when the serial compressor or the serial fan 
control is used. 
-

 

EMB1 or 2:

 indication valid for Embraco compressor 1 or 2 

-

 

SCP1 or 2:

 indication valid for SECOP compressor 1 or 2 

 

Message 

Cause 

Outputs 

EC1 

EMB1 or 2: communication error 

Regulation stopped, retry function active 

CP1, CP2 

EMB1 or 2: compressor stopped 

Regulation stopped, retry function active 

HP1, HP2 

EMB1 or 2: start fail 

Regulation stopped, retry function active 

E11, E21 

EMB1 or 2: overload 

Regulation stopped, retry function active 

E12, E22 

EMB1 or 2: under speed 

Regulation stopped, retry function active 

E13, E23 

EMB1 or 2: wrong rotor position 

Regulation stopped, power off required 

E14, E24 

EMB1 or 2: short circuit 

Regulation stopped, power off required 

HT1, HT2 

EMB1 or 2: high temperature 

Regulation stopped, retry function active 

EC2 

SCP1 or 2: communication error 

Regulation stopped, retry function active 

EV1, EV2 

SCP1 or 2: voltage error 

Regulation stopped, retry function active 

EM1, EM2 

SCP1 or 2: motor error 

Regulation stopped, retry function active 

ET1, ET2 

SCP1 or 2: internal temperature error  Regulation stopped, retry function active 

CSr 

Condenser fan maintenance 

Unchanged, warning reset required 

22.2

 

BUZZER MUTING 

Once the alarm signal is detected the buzzer can be silenced by pressing any key. Buzzer is mounted 
in the keyboard and it is an option. 

22.3

 

“EE” ALARM

 

The 

Dixell

 

instruments are provided with an internal check for the data integrity. The “EE” alarm flashes 

when a failure in the memory data occurs. In such cases the alarm output is enabled. 

22.4

 

ALARM RECOVERY 

Probe 

alarms: “

P1

” (probe1 faulty), “

P2

”, “

P3

” and “

P4

”; they automatically stop 10 sec after the probe 

restarts normal operation. Check connections before replacing the probe. 

Summary of Contents for Dixell XWi70K

Page 1: ... delay AC1 is always respected The second compressor is deactivated when T SET HY With parameter rCC it is possible to enable the compressor rotation function the activation of the first and the second compressor will be alternated to equalize the number of working hours of both of them In case of hot gas defrost operation it is possible to select if one or both compressors will be used 3 2 PULL D...

Page 2: ... for auxiliary regulator 2 Sd2 Auxiliary regulator 2 disabled during any defrost 9 ANALOGUE OUTPUTS The controller is equipped with 2 configurable analogue outputs type 4 20mA or 0 10Vdc both selectable It is possible to use them for proportional regulation of Evaporator fan speed Condenser fan speed Or as proportional output linked to the Auxiliary regulator 1 linked only to analogue output 1 Aux...

Page 3: ... manually by the user 11 7 DEAD BAND oAx db By setting oAx db the controller will perform a dead band regulation The heating element has to be connected to the correspondent relay If the temperature increases and reaches set point plus differential HY the compressor is started and then turned off when the temperature reaches the set point value again If the temperature decreases and reaches the se...

Page 4: ...accessible parameters under a specific menu operate as follows 1 Enter the Programming mode by pressing the SET DOWN key for 3 seconds 2 The display will show the first menu available under Pr1 level 14 4 HOW TO ENTER PARAMETER PROGRAMMING MENU PR2 In the PR2 level there are all the parameters of the instrument 14 4 1 ENTERING THE PARAMETER PROGRAMMING MENU PR2 1 Enter the Programming mode by pres...

Page 5: ... control ON in normal mode n Y Y VSC is never stopped during regulation CME Continuous control ON in energy saving mode n Y Y VSC is never stopped during regulation MnP Compressor speed threshold to activate lubrication valid for variable speed compressors only 0 disabled nu 1 to 100 OFF nu not used 1 to 100 select the percentage to activate function OFF compressor is stopped when the condition is...

Page 6: ...tput value at the end of the scale 2At Interval of time with analogue output 2 maximum value 0 to 255 sec analogue output is forced at 100 after any activation for 2At seconds ALARM MENU ALr ALP Probe selection for temperature alarms nP P1 P2 P3 P4 nP no probe Px probe x Note P4 Probe on Hot Key plug ALC Temperature alarm configuration Ab rE Ab absolute rE relative ALU High temperature alarm when ...

Page 7: ...mable defrost cycles during any ddx day Example when Ld2 12 4 the second defrost starts at 12 40 am during working days N B To disable a defrost cycle set it to nu not used Ex if Ld6 nu the sixth defrost cycle will be disabled SERIAL COMMUNICATION CoM Adr Serial address 1 to 247 device address for Modbus communication bAU Baudrate 9 6 19 2 select the correct baudrate for serial communication USER ...

Page 8: ...automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation...

Page 9: ...t Maximum duration for Pull Down 04 00 Pr1 hour CCS Pull Down phase differential SET CCS or SET HES CCS 1 Pr1 F oHt Threshold for automatic activation of Pull Down in normal mode SET HY oHt 10 Pr1 F Con Compressor ON time with faulty probe 30 Pr1 min CoF Compressor OFF time with faulty probe 10 Pr1 min PbC Probe selection ntC Pr2 ot Probe P1 calibration 0 Pr1 F P2P Probe P2 presence yes Pr1 oE Pro...

Page 10: ...r2 C ndE Number of connected controllers for random refrost Syd rnd 1 Pr2 FAP Probe selection for evaporator fan P3 Pr1 FSt Evaporator fan stop temperature 50 Pr1 F HyF Evaporator fan regulator differential 2 Pr1 F FnC Evaporator fan operating mode O_n Pr1 Fnd Evaporator fan delay after defrost cycle 4 Pr1 min FCt Differential temperature for cyclic activation of evaporator fans 0 disabled 0 Pr1 F...

Page 11: ...ential in energy saving 1 Pr1 F ESt Energy saving timeout 24 Pr1 hour LdE Energy saving controls the lights lights OFF when energy saving goes active no Pr1 LHt Maximum duration for light output on 0 Pr1 min HUr Hours Pr1 Min Minutes Pr1 dAy Day of the week Pr1 dyM Day of the month Pr1 Mon Month Pr1 yAr Year Pr1 Hd1 First day of weekend nu Pr1 Hd2 2nd day of weekend nu Pr1 iLE Energy saving cycle ...

Page 12: ...r max interval for output variation 30 Pr2 sec tLv_nt PI regulator min interval for output variation 10 Pr2 sec rSr_nt PI regulator range for output value calculation RPM 10 90 Pr2 RPM 10 Str_nt PI regulator delay before range drift 60 Pr2 sec dPt_nt PI regulator divisor for PI response time reduction acts on both par tSt and iSt 1 Pr2 CMn_nt Continuous control ON in normal mode yes Pr2 CME_nt Con...

Page 13: ...Interval of time with analogue output 1 maximum value 5 Pr1 sec 2An_nt Type of analogue output 2 Vlt Pr1 2oL_nt Minimum value for analogue output 2 5 Pr1 2oH_nt Maximum value for analogue output 2 100 Pr1 2At_nt Interval of time with analogue output 2 maximum value 5 Pr1 sec ALP_nt Probe selection for temperature alarms nP Pr1 ALC_nt Temperature alarms configuration relative absolute Ab Pr1 ALU_nt...

Page 14: ...no Pr1 dd7_nt Saturday defrost no Pr1 Ld1_nt 1st defrost starting time nu Pr1 hour Ld2_nt 2nd defrost starting time nu Pr1 hour Ld3_nt 3rd defrost starting time nu Pr1 hour Ld4_nt 4th defrost starting time nu Pr1 hour Ld5_nt 5th defrost starting time nu Pr1 hour Ld6_nt 6th defrost starting time 12 00 Pr1 hour Adr_nt Serial address 1 Pr1 bAU_nt Baudrate 9 6 Pr1 brd_nt Type of keyboard lock UnL Pr2 ...

Page 15: ...ac 30K cycles Motor load 2HP 12FLA 72LRA 230Vac 30K cycles Motor load 1HP 16FLA 96LRA 110Vac 30K cycles Motor load 4 9FLA 29 4LRA 110 230Vac 30K cycles 14 8 A 230Vac 30K cycles oA2 SPST 16A 250VAC Resistive load 10A 230 Vac 30K cycles 14A NO 230Vac 50K cycles oA3 SPST 8A 250VAC Resistive load 10A 110 230Vac 30K cycles Motor load 1 2HP 230Vac 30K cycles Motor load 4 9FLA 29 4LRA NO 110 230Vac 30K c...

Reviews: