1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx 

XWi70K

 

4/15 

 

12.6

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor is running 

FLASHING  - Programming menu 

- Anti-short cycle delay enabled 

 

ON 

The fan is running 

FLASHING  Programming menu 

 

ON 

The defrost is enabled 

FLASHING  Drip time in progress 

 

ON 

- ALARM signal 

In “Pr2” indicates that the parameter is also present in “Pr1”

 

 

ON 

Pull down is running 

 
 

ON 

Energy saving enabled 

 

ON 

Light on 

 

ON 

Auxiliary output on 

,   

ON 

Measurement unit 

13

 

CONTROLLER INTERFACE 

13.1

 

HOW TO SET THE CURRENT TIME AND DAY (ONLY WITH RTC) 

When the instrument is switched on, it could be necessary to program the real-time clock. This operation 
requires to enter the rtC menu (depending on the visibility level) and set the following parameters: 

HUr

 

(hours),

 Min

 (minutes), 

dAy

 (day of the week), 

dYM

 (day of the month) 

Mon (month

) and 

YAr

 (year). 

13.2

 

HOW TO SEE THE MIN TEMPERATURE 

1.

 

Press and release the 

DOWN

 key. 

2.

 

The “Lo” message will be displayed followed by the minimum 

temperature recorded. 

3.

 

By pressing the 

DOWN

 key or waiting for 5 sec the normal display will be restored. 

13.3

 

HOW TO SEE THE MAX TEMPERATURE 

1.

 

Press and release the 

UP

 key. 

2.

 

The “Hi” message will be displayed followed by the maximum temperature recorded. 

 

3.

 

By pressing the 

UP

 key or waiting for 5 sec the normal display will be restored. 

13.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed, press 

SET

 

key until “rSt”

 

label starts blinking. 
 

Note: after the installation remember to RESET the temperature stored.

 

13.5

 

HOW TO SEE AND MODIFY THE SET POINT 

1.

 

Push and immediately release the 

SET 

key: the display will show the Set point value; 

2.

 

To change the 

SEt

 value, push the 

UP

 or 

DOWN

 arrows within 10 sec. 

3.

 

To save the new set point value push the 

SET

 key again or wait for 10 sec. 

13.6

 

TO START A MANUAL DEFROST  

 

Push the 

DEF 

key for more than 2 sec and a manual defrost will start. 

13.7

 

ON/OFF FUNCTION (STAND BY) 

 

By pushing the 

ON/OFF

 

key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED 

is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a 
monitoring system is connected, it does not record the instrument data and alarms. 

When the instrument is in stand by the keyboard displays “oFF”.

 

 

N.B. During the OFF status the Light and AUX buttons are active. 

 

13.8

 

HOW TO SEE THE PROBE VALUES 

1.

 

Enter “

Pr1

” programming menu.

 

2.

 

Parameters “dP1”, “dP2”, “dP3” and “dP4” displ

ay the value of probes P1, P2, P3 and P4. 

14

 

PROGRAMMING MODE 

14.1

 

KEYBOARD LOCK 

 + 

 

1. 

Keep both 

UP

 and 

DOWN

 buttons pressed for 3 sec. 

2. 

The “PoF” message will be displayed and the keyboard is locked. At this point 

it is only possible the viewing of the set point or the MAX o Min temperature 
stored and to switch ON and OFF the light, the auxiliary output and the 
instrument. 

 

TO UNLOCK THE KEYBOARD 

Keep both 

UP

 and 

DOWN

 buttons pressed for 3 sec. 

 
NOTE: if keyboard lock is enabled (see par. 

brd

), then keyboard control function is disabled. 

14.2

 

PARAMETER MENUS 

The configuration  parameters are divided in  groups (named menu). After  entering the  programming 
mode,  the  first  label  corresponding  to  the  first  available  group  (menu)  will  appear  on  the  display 
depending on the visibility level. Every parameter belonging to a specific menu has its own visibility rules 
for placement in PR1 (user accessible parameters) or PR2 (hidden parameters). Any menu can have 
parameters placed both in PR1 and/or PR2. 

 

 

14.3

 

HOW TO 

ENTER PARAMETER PROGRAMMING MENU “PR1”

  

To enter a parameter list under 

“Pr1”

 level (user accessible parameters), under a specific menu, operate 

as follows: 

 

 

1.

 

Enter  the  Programming  mode  by  pressing  the 

SET+DOWN

  key  for  3 

seconds. 

2.

 

The display will show the first menu available under 

“Pr1”

 level 

14.4

 

HOW TO ENTER PARAMETER 

PROGRAMMING MENU “PR2”

 

In the PR2 level there are all the parameters of the instrument. 

14.4.1

 

ENTERING THE PARAMETER 

PROGRAMMING MENU “PR2”

 

1.

 

Enter the Programming mode by pressing both 

SET+DOWN

 buttons for 3 sec: the label of the first 

menu available in Pr1 will be displayed (for example: rEG) 

2.

 

Release  the 

SET+DOWN

  buttons  and  then  push  them  again  for  7  sec:  during  this  time  both 

compressor and fan icon will blink. After 7 sec t

he “

Pr2

” label will

 be displayed immediately, and, 

after releasing the 

SET+DOWN

 buttons, the first parameter menu available will be displayed (for 

example: rEG) 

NOW 

THE PARAMETER MENU “PR2” IS AVAILABLE FOR ANY MODIFICATION

 

 

If no parameter is present in the “

Pr1

” level, after the first 3 sec the “

noP

” message will be displayed. 

Keep 

SET+DOWN

 

buttons pushed till the “

Pr2

” message will be displayed. 

 

14.4.2

 

HOW TO MOVE A PARAMETER FROM 

“PR2”

 MENU TO 

“PR1” MENU

 AND VICE-

VERSA 

Each parameter present in the PR2 level can be moved or put into PR1 level (user level) by pressing 

SET+DOWN

 buttons. When in PR2 menu, if a parameter is present also in the First Level (Pr1), the 

decimal point will be lit. 

14.4.3

 

HOW TO CHANGE A PARAMETER VALUE 

1.

 

Enter the programming mode (both in PR1 or PR2 level) 

2.

 

Select the required menu with 

UP 

or 

DOWN

 

3.

 

Press the SET button to enter the parameter list belonging to the selected menu 

4.

 

The  first  available  parameter  label  (depending  on  the  visibility  level)  will  be  displayed.  The 
compressor icon will blink to indicate the position in the selected menu 

5.

 

Select the required parameter by using 

UP 

or 

DOWN

 buttons. 

6.

 

Press the 

SET

 key to display the current value (compressor and fan icon starts blinking to indicate 

this condition) 

7.

 

Use 

UP 

or 

DOWN

 to change its value. 

8.

 

Press 

SET

 to store the new value and move to the following parameter (belonging to the same menu) 

 

To exit

: Press 

SET+UP 

or wait for 30 sec without pressing any button. 

 
NOTE

:  

-

 

The new programming is stored even when the procedure ends by waiting the time-out 

-

 

The LIGHT button is used as BACK function when into PROGRAMMING MODE: press it to exit 
from a parameter list and return to the upper menu or to discard a parameter value modification 
and return to the same parameter label (without changing the previous parameter value) 

15

 

PARAMETER LIST 

The configuration parameters are divided in groups (named menu) to speed up the browsing operations. 
Here below the list of all Menu with their meaning: 
 

rEG 

Regulation menu: 

to set regulation band 

Prb 

Temperature probe menu

 

vSC 

Variable Speed Drive menu: 

to set the VS functional parameters 

vSF 

Modbus Variable Speed Fan menu:

 to set Modbus VSF functional parameters 

diS 

Display menu: 

to set the visualization rules 

dEF 

Defrost menu: 

to set the defrost operational mode 

FAn 

Fan menu: 

to set the evaporator and condenser fan control mode 

AUS 

Auxiliary menu: 

 to set the auxiliary output mode 

ALr 

Alarm menu: 

to set the alarm thresholds 

oUt 

Output menu:

 to set the function linked to any configurable output 

inP 

Input menu: 

to set the function linked to any configurable input 

ES 

Energy saving menu:

 to set the energy saving mode 

rtC 

Real Time Clock menu:

 to set the internal clock 

CoM 

Serial communication menu:

 to set serial port speed and baudrate 

Ui 

User Interface:

 to set keyboard related functions 

inF 

Info menu: 

to read probe values and FW information 

REGULATION MENU - rEG 

SEt 

Setpoint:

 (LS to US) temperature regulation setpoint. 

SET

DOWN

UP

DOWN

UP

...

LIGHT

LIGHT

LIGHT

DOWN

SET

SET

SET

SET

UP

SET

DOWN

UP

DOWN

UP

...

LIGHT

LIGHT

LIGHT

DOWN

SET

SET

SET

SET

...

UP

...

...

...

...

...

...

...

...

...

...

PARAMETER LIST

MENU

Prb

ot

P2P

rEG

LS

US

1

5.0

2.0

1.0

5.0

Y

Summary of Contents for Dixell XWi70K

Page 1: ... delay AC1 is always respected The second compressor is deactivated when T SET HY With parameter rCC it is possible to enable the compressor rotation function the activation of the first and the second compressor will be alternated to equalize the number of working hours of both of them In case of hot gas defrost operation it is possible to select if one or both compressors will be used 3 2 PULL D...

Page 2: ... for auxiliary regulator 2 Sd2 Auxiliary regulator 2 disabled during any defrost 9 ANALOGUE OUTPUTS The controller is equipped with 2 configurable analogue outputs type 4 20mA or 0 10Vdc both selectable It is possible to use them for proportional regulation of Evaporator fan speed Condenser fan speed Or as proportional output linked to the Auxiliary regulator 1 linked only to analogue output 1 Aux...

Page 3: ... manually by the user 11 7 DEAD BAND oAx db By setting oAx db the controller will perform a dead band regulation The heating element has to be connected to the correspondent relay If the temperature increases and reaches set point plus differential HY the compressor is started and then turned off when the temperature reaches the set point value again If the temperature decreases and reaches the se...

Page 4: ...accessible parameters under a specific menu operate as follows 1 Enter the Programming mode by pressing the SET DOWN key for 3 seconds 2 The display will show the first menu available under Pr1 level 14 4 HOW TO ENTER PARAMETER PROGRAMMING MENU PR2 In the PR2 level there are all the parameters of the instrument 14 4 1 ENTERING THE PARAMETER PROGRAMMING MENU PR2 1 Enter the Programming mode by pres...

Page 5: ... control ON in normal mode n Y Y VSC is never stopped during regulation CME Continuous control ON in energy saving mode n Y Y VSC is never stopped during regulation MnP Compressor speed threshold to activate lubrication valid for variable speed compressors only 0 disabled nu 1 to 100 OFF nu not used 1 to 100 select the percentage to activate function OFF compressor is stopped when the condition is...

Page 6: ...tput value at the end of the scale 2At Interval of time with analogue output 2 maximum value 0 to 255 sec analogue output is forced at 100 after any activation for 2At seconds ALARM MENU ALr ALP Probe selection for temperature alarms nP P1 P2 P3 P4 nP no probe Px probe x Note P4 Probe on Hot Key plug ALC Temperature alarm configuration Ab rE Ab absolute rE relative ALU High temperature alarm when ...

Page 7: ...mable defrost cycles during any ddx day Example when Ld2 12 4 the second defrost starts at 12 40 am during working days N B To disable a defrost cycle set it to nu not used Ex if Ld6 nu the sixth defrost cycle will be disabled SERIAL COMMUNICATION CoM Adr Serial address 1 to 247 device address for Modbus communication bAU Baudrate 9 6 19 2 select the correct baudrate for serial communication USER ...

Page 8: ...automatically downloaded into the Controller memory The doL message will blink followed a by a flashing End label 4 After 10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation...

Page 9: ...t Maximum duration for Pull Down 04 00 Pr1 hour CCS Pull Down phase differential SET CCS or SET HES CCS 1 Pr1 F oHt Threshold for automatic activation of Pull Down in normal mode SET HY oHt 10 Pr1 F Con Compressor ON time with faulty probe 30 Pr1 min CoF Compressor OFF time with faulty probe 10 Pr1 min PbC Probe selection ntC Pr2 ot Probe P1 calibration 0 Pr1 F P2P Probe P2 presence yes Pr1 oE Pro...

Page 10: ...r2 C ndE Number of connected controllers for random refrost Syd rnd 1 Pr2 FAP Probe selection for evaporator fan P3 Pr1 FSt Evaporator fan stop temperature 50 Pr1 F HyF Evaporator fan regulator differential 2 Pr1 F FnC Evaporator fan operating mode O_n Pr1 Fnd Evaporator fan delay after defrost cycle 4 Pr1 min FCt Differential temperature for cyclic activation of evaporator fans 0 disabled 0 Pr1 F...

Page 11: ...ential in energy saving 1 Pr1 F ESt Energy saving timeout 24 Pr1 hour LdE Energy saving controls the lights lights OFF when energy saving goes active no Pr1 LHt Maximum duration for light output on 0 Pr1 min HUr Hours Pr1 Min Minutes Pr1 dAy Day of the week Pr1 dyM Day of the month Pr1 Mon Month Pr1 yAr Year Pr1 Hd1 First day of weekend nu Pr1 Hd2 2nd day of weekend nu Pr1 iLE Energy saving cycle ...

Page 12: ...r max interval for output variation 30 Pr2 sec tLv_nt PI regulator min interval for output variation 10 Pr2 sec rSr_nt PI regulator range for output value calculation RPM 10 90 Pr2 RPM 10 Str_nt PI regulator delay before range drift 60 Pr2 sec dPt_nt PI regulator divisor for PI response time reduction acts on both par tSt and iSt 1 Pr2 CMn_nt Continuous control ON in normal mode yes Pr2 CME_nt Con...

Page 13: ...Interval of time with analogue output 1 maximum value 5 Pr1 sec 2An_nt Type of analogue output 2 Vlt Pr1 2oL_nt Minimum value for analogue output 2 5 Pr1 2oH_nt Maximum value for analogue output 2 100 Pr1 2At_nt Interval of time with analogue output 2 maximum value 5 Pr1 sec ALP_nt Probe selection for temperature alarms nP Pr1 ALC_nt Temperature alarms configuration relative absolute Ab Pr1 ALU_nt...

Page 14: ...no Pr1 dd7_nt Saturday defrost no Pr1 Ld1_nt 1st defrost starting time nu Pr1 hour Ld2_nt 2nd defrost starting time nu Pr1 hour Ld3_nt 3rd defrost starting time nu Pr1 hour Ld4_nt 4th defrost starting time nu Pr1 hour Ld5_nt 5th defrost starting time nu Pr1 hour Ld6_nt 6th defrost starting time 12 00 Pr1 hour Adr_nt Serial address 1 Pr1 bAU_nt Baudrate 9 6 Pr1 brd_nt Type of keyboard lock UnL Pr2 ...

Page 15: ...ac 30K cycles Motor load 2HP 12FLA 72LRA 230Vac 30K cycles Motor load 1HP 16FLA 96LRA 110Vac 30K cycles Motor load 4 9FLA 29 4LRA 110 230Vac 30K cycles 14 8 A 230Vac 30K cycles oA2 SPST 16A 250VAC Resistive load 10A 230 Vac 30K cycles 14A NO 230Vac 50K cycles oA3 SPST 8A 250VAC Resistive load 10A 110 230Vac 30K cycles Motor load 1 2HP 230Vac 30K cycles Motor load 4 9FLA 29 4LRA NO 110 230Vac 30K c...