1592034020 XR77CHC EN r1.0 2019.01.31 

                           XR77CHC 

4/7 

 

StC 

Compressor stop time before starting any defrost: 

(0 to 900 sec) interval with compressor 

stopped before activating hot gas cycle 

dFd 

Display during defrost:

 (rt; it; SP; dF) 

rt

 = real temperature; 

it

 = start defrost temperature;  

SP

 = SET-POINT; 

dF

 = lab

el “

dF

”.

 

dAd 

Max delay for updating display after any defrost: 

(0 to 255 min) delay before updating the 

temperature on the display after finishing any defrost. 

Fdt 

Draining time: 

(0 to 255 min) 

 

Hon 

Drain heater enabled after draining time (Fdt):

 (0 to 255 min) the relative output will stay on 

after draining time. 

dPo 

First defrost after start-up: 

(n; Y) to enable defrost at power on.

 

Pd1 

Differential during any pre-defrost phase: 

(-12.0 to 12.0°C; -21 to 21°F) the regulation Set 

Point is changed to a temporary different value before any defrost 

Pd2 

Pre-defrost time: 

(0 to 120 min) interval with temporary Set Point before any defrost. 

dAF 

Defrost delay after freezing: 

(0.0 to 24h00min, res. 10 min) delay before activating a defrost. 

od1 

Automatic  defrost  (at  the  beginning  of  any  energy  saving  mode): 

(n;  Y) 

n

=function 

disabled; 

Y

=function enabled 

SYn 

Tipe of synchronized defrost:

 (nu; SYn; rnd) 

nu

=not used; 

SYn

=synchronized; 

rnd

=random 

defrost 

ndE 

Number  of  devices  connected  to  the  virtual  network  for  random  defrost  (valid  if 
Syd=rnd):

 (1 to 20) used to define how many devices will use the Random Defrost Function 

FAN - FAn 

FAP 

Probe  selection  for  evaporator  fan  management:  nP

=no  probe; 

P1

=thermostat  probe; 

P2

=evaporator probe; 

P3

=do not use it; 

P4

=Probe on Hot Key plug.

 

FSt

 

Evaporator  fan  stop  temperature: 

(-55  to  50°C;  -67  to  122°F)  setting  of  temperature, 

detected by evaporator probe. Over this value of temperature fans are always OFF. 

NOTE: it 

works only for the evaporator fan, NOT for the condenser fan.

 

HYF 

Differential for evaporator fan:

 (0.1 to 25.5°C; 1 to 45°F) differential for evaporator ventilator 

regulator 

FnC

 

Evaporator fan mode operation: 

(Cn; on; CY; oY)  

 

Cn 

= runs with the compressor, duty-cycle when  compressor is OFF (see 

FoF

,

  Fon

FF1 

and 

Fo1 

parameters) and OFF during defrost  

 

on 

= continuous mode, OFF during defrost 

 

CY 

= runs with the compressor, duty-cycle when  compressor is OFF (see 

FoF

,

  Fon

FF1 

and 

Fo1 

parameters) and ON during defrost 

 

oY 

= continuous mode, ON during defrost 

Fnd 

Fan delay after defrost: 

(0 to 255 min) delay before fan activation after any defrosts. 

FCt 

Differential of temperature for forced activation of fans 

Fon

 

Fan on time when the compressor is off: 

(0 to 255 min) used when energy saving status is 

not active. 

FoF

 

Fan off time when the compressor is off: 

(0 to 255 min) used when energy saving status is 

not active. 

Fo1

 

Fan on time with compressor off in Energy Saving mode: 

(0 to 255 min) used when energy 

saving status is active. 

FF1

 

Fan off time with compressor off in Energy Saving mode: 

(0 to 255 min) used when energy 

saving status is active. 

FAC 

Probe selection for  condenser fan management:  nP

=no probe; 

P1

=probe Pb1; 

P2

=probe 

Pb2; 

P3

=probe Pb3; 

P4

=probe Pb4 on Hot Key plug.

 

St2

 

Condenser  fan  stop  temperature: 

(-55  to  50°C;  -67  to  122°F)  setting  of  temperature, 

detected by evaporator probe. Over this value of temperature fans are always OFF. 

HY2 

Differential for condenser fan:

 (0.1 to 25.5°C; 1 to 45°F) differential for evaporator ventilator 

regulator 

FCC

 

Condenser fan mode operation: 

(Cn; on; CY; oY)  

 

Cn 

= runs with the compressor and OFF during defrost  

 

on 

= continuous mode, OFF during defrost 

 

CY 

= runs with the compressor and ON during defrost 

 

oY 

= continuous mode, ON during defrost 

AUXILIARY OUTPUT MANAGEMENT - AUS

 

ACH 

Kind of regulation for auxiliary relay:

 (Ht; CL) 

Ht

 = heating; 

CL

 = cooling. 

SAA 

Set Point for auxiliary relay:

 (-55.0 to 150.0°C; -67 to 302°F) it defines the room temperature 

set point to switch auxiliary relay. 

SHY 

Differential for auxiliary relay:

 (0.1 to 25.5°C; 1 to 45°F) differential for auxiliary output set 

point. 

 

ACH=CL

, AUX Cut in is [

SAA+SHY

]; AUX Cut out is 

SAA

 

ACH=Ht

, AUX Cut in is [

SAA

SHY]

; AUX Cut out is 

SAA

ArP 

Probe selection for auxiliary relay:

 (nP; P1; P2; P3; P4) 

nP

 = no probe, the auxiliary relay is 

switched only by the digital input; 

P1

 = Probe 1 (Thermostat probe); 

P2

 = Probe 2 (evaporator 

probe); 

P3

 = do not use it; 

P4

 = Probe 4. 

Sdd 

Auxiliary  relay  switched  off  during  defrost:

  (n;  Y) 

n

  =  the  auxiliary  relay  operates  during 

defrost. 

Y

 = the auxiliary relay is switched off during defrost. 

btA 

Base Time for timed activation of auxiliary output:

 (SEC; Min) SEC=base time is in second

 

Ato 

AUX output in ON state:

 0 to 255 (base time defined in par. 

btA

AtF 

AUX output in OFF state:

 0 to 255 (base time defined in par. 

btA

ALARMS - ALr

 

ALP 

Temperature alarms probe selection: 

(P1, P2, P3, P4) 

ALC 

Temperature alarms configuration: 

(Ab, rE) 

Ab

 = absolute; 

rE

 = relative. 

ALU

 

Maximum temperature alarm:

 when this temperature is reached, the alarm is enabled after 

the 

Ad

 delay time. 

 

If 

ALC=Ab

 

 ALL to 150.0°C or ALL to 302°F. 

 

If 

ALC=rE

 

 0.0 to 50.0°C or 0 to 90°F. 

ALL

 

Minimum temperature alarm:

 when this temperature is reached, the alarm is enabled after the 

Ad

 delay time. 

 

If 

ALC=Ab

 

 -55.0°C to ALU or -67°F to ALU. 

 

If 

ALC=rE

 

 0.0 to 50.0°C or 0 to 90°F. 

AFH 

Differential for temperature alarm recovery:

 (0.1 to 25.0°C; 1 to 45°F) differential for alarms.

 

ALd

 

Temperature  alarm  delay:

  (0  to  255  min)  delay  time  between  the  detection  of  an  alarm 

condition and the relative alarm signalling. 

Dot

 

Delay  of  temperature  alarm  with  door  open: 

(0.0  to  24h00min,  res.  10  min)  delay  time 

between the detection of a temperature alarm condition and the relative alarm signalling, after 
powering on the instrument. 

dAo

 

Delay of temperature alarm at start up: 

(0.0 to 24h00min, res. 10 min) delay time between 

the detection of a temperature alarm condition and the relative alarm signalling, after powering 
on the instrument. 

CONDENSER TEMPERATURE ALARM - ALr 

AP2 

Probe  selection  for  second  temperature  alarms: 

(nP;  P1;  P2;  P3;  P4) 

nP

=no  probe; 

P1

=thermostat probe; 

P2

=evaporator probe; 

P3

=do not use it; 

P4

=Probe on Hot Key plug 

AU1 

Second high temperature pre-alarm:

 (-55.0 to 150.0°C; -67 to 302°F)

 

AH1 

Differential for second temperature pre-alarm recovery: 

(0.1 to 25.0°C; 1 to 45°F)

 

Ad1 

Second temperature pre-alarm delay: 

(0 to 255 min; 255 = not used) delay time between the 

detection of a condenser pre-alarm condition and the relative alarm signaling.

 

AL2 

Second low temperature alarm:

 (-55.0 to 150.0°C; -67 to 302°F)

 

AU2 

Second high temperature alarm: 

(-55.0 to 150.0°C; -67 to 302°F)

 

AH2 

Differential for second temperature alarm recovery: 

(0.1 to 25.0°C; 1 to 45°F)

 

Ad2 

Second  temperature  alarm  delay: 

(0  to  255  min;  255  =  not  used)  delay  time  between  the 

detection of a condenser alarm condition and the relative alarm signaling.

 

dA2 

Delay for second temperature alarm at start up: 

(0.0 to 24h00min, res. 10 min)

 

bLL 

Compressor  off  because  of  second  low  temperature  alarm: 

(n;  Y)

  n 

=  no,

 

compressor 

keeps on working

; Y 

= yes,

 

compressor is  switched off  till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

AC2 

Compressor  off  because  of  second  high  temperature  alarm: 

(n;  Y)

  n 

=  no,

 

compressor 

keeps on working

; Y 

= yes,

 

compressor is  switched off  till the alarm is present, in any case 

regulation restarts after 

AC

 time at minimum. 

SAF 

Differential for anti freezing control: 

(-12.0 to 12.0°C; -21.0 to 21.0°F) regulation sopped if 

T<SET+SAF

 

DIGITAL OUTPUT MANAGEMENT - oUt 

tbA 

Alarm muting: 

(n; Y) to disable the (optional) buzzer and the output configured as alarm. 

oAx 

(x=1,2,3,4) 

Output configuration: 

(nu; CP1; dEF; FAn; ALr; LiG; AUS; db; onF; HES; Cnd) 

nu

=not 

used; 

CP1

=compressor; 

dEF

=defrost; 

FAn

=ventilators; 

ALr

=alarm; 

LiG

=light; 

AUS

=Auxiliary  relay; 

onF

=always  on  with  instrument  on; 

db

=neutral  zone; 

HES

=night 

blinds; 

Cnd

=Condenser fan; 

CP2

=second compressor; 

dF2

=second defrost; 

HEt

=heater 

control; 

inV

=do not use it. 

AoP 

Alarm relay polarity: 

(oP; CL) 

oP 

= alarm activated by closing the contact; 

CL 

= alarm 

activated by opening the contact

 

DIGITAL INPUTS - inP 

ibt

 

Base time for digital inputs:

 (SEC; Min) 

SEC 

= seconds; 

Min 

= minutes. Delay for activating 

the function linked to the digital inputs. 

i1P

 

Digital  input  1  polarity:

  (oP;  CL) 

oP 

=  activated  by  closing  the  contact; 

CL 

=  activated  by 

opening the contact. 

i1F

 

Digital input 1 configuration:

 (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; 

CC; EMt)  

 

nu

=not used 

 

dor

 = door switch function 

 

dEF

 = defrost activation  

 

AUS

 = auxiliary output 

 

ES 

= energy saving mode activation 

 

EAL

 = external warning alarm 

 

bAL 

= external lock alarm 

 

PAL 

= external pressure alarm 

 

FAn 

= evaporator fan control 

 

HdF

 = holiday defrost 

 

onF 

= ON/OFF status change 

 

LiG 

= light output control 

 

CC

 = change configuration (between C1 and C2) 

 

EMt

 = do not use it  

did

 

Digital inputs 1 alarm delay:

 (0 to 255) it is the delay between the detection of an  external 

event and the activation of the relative function. 

i2P

 

Digital input 2 polarity (if d.i.2 present):

 (oP; CL) 

oP 

= activated by closing the contact; 

CL 

activated by opening the contact. 

i2F

 

Digital input 2 configuration:

 (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF; LiG; 

CC; EMt)  

 

nu

=not used 

 

dor

 = door switch function 

 

dEF

 = defrost activation  

 

AUS

 = auxiliary output 

 

ES 

= energy saving mode activation 

 

EAL

 = external warning alarm 

 

bAL 

= external lock alarm 

 

PAL 

= external pressure alarm 

 

FAn 

= evaporator fan control 

 

HdF

 = holiday defrost 

 

onF 

= ON/OFF status change 

 

LiG 

= light output control 

 

CC

 = change configuration (between C1 and C2) 

 

EMt

 = Motion detector 

d2d 

Digital inputs 2 alarm delay:

 (0 to 255) it is the delay between the detection of an  external 

event and the activation of the relative function. 

nPS 

Number  of  external  pressure  alarms  before  stopping  the  regulation: 

(0  to  15)  after 

reaching 

nPS

 events in the digital input alarm delay (par. 

dxd

) the regulation will be stopped 

and a manual restart (ON/OFF, power OFF and power ON) will be required 

odC

 

Compressor and fan status after door opening:

 (no; FAn; CPr; F-C): 

no

 = normal;  

FAn

 = Fans OFF; 

CPr

 = Compressor OFF; 

F-C

 = Compressor and fans OFF. 

rrd

 

Regulation restart after door open alarm:

 (n; Y) 

n

 = no regulation if door is opened; 

Y

 = when 

did

 is elapsed, regulation restarts even if a door open alarm is present. 

LCi 

Light output controlled by digital input: 

(0 to 255 min) a digital input event will activate the 

light output and the output will stay ON for this interval 

ENERGY SAVING - ES 

HES

 

Differential  for  energy  saving  mode:

  (-30.0  to  30.0°C;  -54  to  54°F)  it  sets  the  increasing 

value of the set point during the Energy Saving cycle. 

LdE 

Energy saving mode controls the lights: 

(n; Y) lights off when energy saving mode is active

 

Summary of Contents for DIXELL XR77CHC

Page 1: ... is possible to enable the compressor rotation function the activation of the first and the second compressor will be alternated to equalize the number of working hours of both In case of hot gas defrost operation it is possible to select if one or both compressors will be used 5 ENERGY SAVING ALGORITHM 5 1 DESCRIPTION The device permits to set different temperature to be used during normal and re...

Page 2: ... CONFIGURABLE OUTPUT 10 1 1 LIGHT OUTPUT With oAx LiG the relay operates as light output 10 1 2 DIGITAL OUTPUT ACTIVATION The auxiliary output can be managed by digital inputs oAx AUS i1F or i2F AUS with oAx AUS and i1F i2F AUS the output is switched on and off following the linked digital input status 10 1 3 AUXILIARY THERMOSTAT The auxiliary regulator can be used to manage the auxiliary output H...

Page 3: ... to set up the internal clock bLE Bluetooth it includes all parameters to set up the Bluetooth communication E2 EEPROM it includes all parameters to set up the datalogger oth Other it includes all parameters to set up the serial communication and the keyboard viS Visualization it includes the read only parameters probe values and FW info REGULATION rEG SEt Regulation Set Point range from LS to US ...

Page 4: ...temperature alarm recovery 0 1 to 25 0 C 1 to 45 F differential for alarms ALd Temperature alarm delay 0 to 255 min delay time between the detection of an alarm condition and the relative alarm signalling Dot Delay of temperature alarm with door open 0 0 to 24h00min res 10 min delay time between the detection of a temperature alarm condition and the relative alarm signalling after powering on the ...

Page 5: ...audrate for serial communication brd Keyboard lock type nu SEL ALL UnL keyboard unlocked SEL only SET and DEF AUX button enabled when locked ALL keyboard unlocked after tLC tLC Keyboard lock timeout 0 to 255 sec timeout after power on and before activating the keyboard lock LGC Light button configuration left upper side nu not used LiG light output control AUS auxiliary output control dEF defrost ...

Page 6: ...e alarms EA CA and dA will automatically stop as soon as the digital input is disabled The internal buzzer can be muted by pressing any key if parameter tbA Y 21 TECHNICAL DATA Housing self extinguishing ABS Case frontal 32x74 mm depth 60mm Mounting panel mounting in a 71x29mm panel cut out Body Protection IP20 Frontal protection IP65 Terminal blocks plug in terminal blocks 2 5 mm2 wiring Power su...

Page 7: ...roller via Bluetooth Extend rights of access to a specific appliance also to other users A Cloud portal will be used for Extend rights of access to a specific appliance also to other users Select the permission level for any new user The link for opening the Cloud webpage is on the left side menu of the mobile APP slide right the screen of the APP when on the Device List page and follow the Cloud ...

Reviews: