13.1

 

ALARM RECOVERY  

Probe  alarms  “P1”,  “P2”  and  “P3”  start  some  seconds  after  the  fault  in  the  related  probe;  they 
automatically stop some seconds after the probe restarts normal operation. Check connections before 
replacing the probe. 
Temperature alarms “HA” and “LA2” automatically stop as soon as the temperature returns to normal 
values. 
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled. 
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument. 

13.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode: none parameter is present in Pr1 
On the display or in dP2, dP3, dP4: the selected probe is nor enabled 

14.

 

TECHNICAL DATA 

Housing: self extinguishing ABS. 
Case: 
frontal 32x74 mm; depth 60mm; 
Mounting: panel mounting in a 71x29mm panel cut-out 
Protection: IP20; Frontal protection: IP65 
Connections: Screw terminal block 

 2.5 mm

2

 wiring 

Power supply: 12VAC/DC, ±10% 
Power absorption: 3VA max 
Display
: 3 digits, red LED, 14.2 mm high  
Inputs: Up to 3 NTC or PTC probes 
Digital inputs: 
 free voltage contact 
Relay outputs:  

Compressor SPST 16(6) A 250VAC 

 

Defrost: SPST 16(6) A, 250VAC 

Buzzer: optional 
Data storing: on the non-volatile memory (EEPROM) 
Kind of action: 1B  
Pollution degree: 
Software class: A  
Rated impulsive voltage: 2500V  
Overvoltage Category: II 
Operating temperature: 
0 to 55°C 
Storage temperature: -25 to 60°C  
Relative humidity: 20 to 85% (no condensing) 
Measuring and regulation range:  

NTC probe: -40 to 110°C (-40 to 230°F)  
PTC probe: -55 to 150°C (-67 to 302°F) 

Resolution: 0.1°C or 1°C or 1°F (selectable)  
Accuracy (ambient temp. 25°C):  ±0.7°C ±1 digit 

15.

 

CONNECTIONS 

 

16.

 

DEFAULT SETTING VALUES 

Label 

Name 

Range 

Value  Level 

SEt  Set point 

LS; US 

-5.0 

- - - 

HY  Differential 

[0.1 to 25.5°C] 

[1 to 45°F] 

2.0 

Pr1 

LS  Minimum set point 

[-55°C to SET] 
[-67°F to SET] 

-40.0 

Pr2 

US  Maximum set point 

[SET to 150°C] 
[SET to 302°F] 

110 

Pr2 

ot  Thermostat probe calibration 

[-12.0 to 12.0°C] 

[-21 to 21°F] 

0.0 

Pr1 

P2P  Evaporator probe presence 

n; Y 

Pr2 

oE  Evaporator probe calibration 

[-12.0 to 12.0°C] 

[-21 to 21°F] 

0.0 

Pr2 

P3P  Third probe presence 

n; Y 

Pr2 

o3  Third probe calibration 

[-12.0 to 12.0°C] 

[-21 to 21°F] 

Pr2 

odS  Outputs delay at start up 

0 to 255 min 

Pr2 

AC 

Anti-short cycle delay for first 
compressor 

0 to 50 min 

Pr1 

AC1 

Anti-short cycle delay for second 
compresor 

0 to 50 min 

Pr1 

CCt  Continuous cycle duration 

0.0 to 24h00min, res. 10 min 

0.0 

Pr2 

CCS  Set point for continuous cycle 

[-55 to 150.0°C] 

[-67 to 302°F] 

0.0 

Pr2 

Con  Compressor ON time with faulty probe 

0 to 255 min 

15 

Pr2 

CoF  Compressor OFF time with faulty probe 

0 to 255 min 

15 

Pr2 

CF  Temperature measurement unit 

°C; °F 

°C 

Pr2 

rES  Resolution 

dE; in 

dE 

Pr1 

Lod  Probe displayed 

P1; P2; P3; P4; SEt; dtr 

P1 

Pr2 

tdF  Defrost type 

EL; in 

EL 

Pr2 

Label 

Name 

Range 

Value  Level 

dtE  First defrost termination temperature 

[-55 to 50.0°C] 

[-67 to 122°F] 

Pr1 

dtS  Second defrost termination temperature 

[-55 to 50.0°C] 

[-67 to 122°F] 

Pr1 

idF  Interval between defrost cycles 

0 to 120 hours 

Pr1 

MdF  (Maximum) length for first defrost 

0 to 255 min 

30 

Pr1 

MdS  (Maximum) length for second defrost 

0 to 255 min 

30 

Pr1 

dSd  Start defrost delay 

0 to 255 min 

Pr2 

dFd  Displaying during defrost 

rt; it; SEt; dEF 

it 

Pr2 

dAd  MAX display delay after defrost 

0 to 255 min 

30 

Pr2 

Fdt  Draining time 

0 to 255 min 

Pr2 

dPo  First defrost after start-up 

n; Y 

Pr2 

dAF  Defrost delay after fast freezing 

0.0 to 24h00min, res. 10 min 

0.0 

Pr2 

FnC  Fan operating mode 

C-n; o-n; C-Y; o-Y 

o-n 

Pr2 

Fnd  Fan delay after defrost 

0 to 255 min 

Pr2 

FCt 

Differential of temperature for forced 
activation of fans 

[0 to 50°C] 
[0 to 90°F] 

Pr2 

FSt  Fan stop temperature 

[-55 to 50.0°C] 

[-67 to 122°F] 

50 

Pr2 

ALC  Temperat. alarms configuration 

rE; Ab 

Ab 

Pr2 

ALU  MAXIMUM temperature alarm 

Rel: [0.0 to 50.0°C] [0 to 90°F] 

AbS: [ALL to 150°C] [ALL to 302°F] 

110.0 

Pr1 

ALL  Minimum temperature alarm 

Rel: [0.0 to 50.0°C] [0 to 90°F] 

AbS: [-55°C to ALU] [-67°F to ALU] 

-50.0 

Pr1 

AFH  Differential for temperat. alarm recovery 

[0.1 to 25.5°C] 

[1 to 45°F] 

1.0 

Pr2 

ALd  Temperature alarm delay 

0 to 255 min 

10 

Pr2 

dAo  Delay of temperature alarm at start up 

0.0 to 24h00min, res. 10 min 

1.3 

Pr2 

oA1  AUX1 relay configuration 

dEF = defrost; FAn= do not select it; 
ALr = alarm; LiG =Light; AUS =AUX; 

onF=always on; db = neutral zone; 

CP2 = second compressor; 

dF2 = second defrost. 

CP2 

Pr2 

oA2   AUX2 configuration 

dEF = defrost; FAn= do not select it; 
ALr = alarm; LiG =Light; AUS =AUX; 

onF=always on; db = neutral zone; 

CP2 = second compressor; 

dF2 = second defrost. 

dEF 

Pr2 

oA3  AUX3 relay configuration 

dEF = defrost; FAn= do not select it; 
ALr = alarm; LiG =Light; AUS =AUX; 

onF=always on; db = neutral zone; 

CP2 = second compressor; 

dF2 = second defrost. 

DF2 

Pr2 

i1P  Digital input polarity  

oP; CL 

oP 

Pr1 

i1F  Digital input configuration  

EAL; bAL; PAL; dor; dEF; AUS; Htr; 

FAn; ES. 

bAL 

Pr1 

did  Digital input alarm delay  

0 to 255 min 

Pr1 

nPS  Number of activation of pressure switch 

0 to 15 

15 

Pr2 

odC 

Compress and fan status when open 
door 

no; FAn; CPr; F-C 

no 

Pr2 

rrd  Regulation restart with door open alarm 

n; Y 

Pr2 

HES  Differential for Energy Saving 

[-30 to 30°C] 
[-54 to 54°F] 

Pr2 

Adr  Serial address 

0 to 247 

Pr2 

PbC  Kind of probe 

PtC; ntC 

ntC 

Pr2 

dP1  Room probe display 

probe value 

Pr1 

dP2  Evaporator probe display 

probe value 

Pr1 

dP3  Third probe display 

probe value 

Pr1 

rEL  Software release 

read only 

Pr2 

Ptb  Map code 

read only 

Pr2 

 

 

Summary of Contents for Dixell XR44CX

Page 1: ...heater tdF EL and hot gas defrost tdF in Other parameters are used to control the interval between defrost cycles idF its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selec...

Page 2: ...Y n not present the terminals operate as digital input Y present the terminals operate as third probe o3 Second evaporator probe calibration P3 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the third probe odS Outputs activation delay at start up 0 to 255min this function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time ...

Page 3: ... DOR It signals the door status and the corresponding relay output status through the odC parameter no normal any change FAn Fan OFF CPr Compressor OFF F_C Compressor and fan OFF Since the door is opened after the delay time set through parameter doA the door alarm is enabled the display shows the message dA and the regulation restarts is rtr YES The alarm stops as soon as the external digital inp...

Page 4: ...min 15 Pr2 CoF Compressor OFF time with faulty probe 0 to 255 min 15 Pr2 CF Temperature measurement unit C F C Pr2 rES Resolution dE in dE Pr1 Lod Probe displayed P1 P2 P3 P4 SEt dtr P1 Pr2 tdF Defrost type EL in EL Pr2 Label Name Range Value Level dtE First defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 dtS Second defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 idF ...

Reviews: