background image

 

1598024001 XR44CX ISA GB r2.0 21.06.2012.doc 

XR44CX 

2/4 

6.

 

MAIN FUNCTIONS 

6.1

 

HOW TO: SEE THE SET POINT 

 

1.

 

Push and immediately release the SET key: the display will show the Set 
point value. 

2.

 

Push  and  immediately  release  the  SET  key  or wait for 5 sec to display 
the probe value again. 

6.2

 

HOW TO CHANGE THE SET POINT 

1.

 

Push the SET key more than 2 sec to change the Set point value. 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED will start blinking. 

3.

 

To change the Set value push the UP

 

or DOWN arrows within 10 sec. 

4.

 

To save the new set point value, push the SET key again or wait for 10 sec. 

6.3

 

HOW TO START A MANUAL DEFROST 

 

Push the DEF key for more than 2 sec and a manual defrost will start. 

6.4

 

HOW TO: CHANGE A PARAMETER VALUE 

To change a parameter value, operate as follows:  
1.

 

Enter the Programming mode by pressing the SET+DOWN buttons for 3s (the °C or °F LED will 

start blinking). 

2.

 

Select the required parameter. Press the SET button to display its actual   value. 

3.

 

Use UP or DOWN buttons to change its value. 

4.

 

Press SET button to store the new value and move to the following parameter. 

 

To exit: Press SET + UP buttons or waiting for 15s without pressing any key. 
 
NOTE
: the set value is stored even when the procedure is exited by waiting for the time-out to expire. 

6.5

 

THE HIDDEN MENU 

The hidden menu includes all the parameters of the instrument. 

6.5.1  HOW TO: ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the SET+DOWN buttons for 3 sec (the °C or °F LED 

will start blinking). 

2.

 

Released  the  buttons  and  then  push  again  the  SET+DOWN  buttons  for  more than 7s. The Pr2 
label will be displayed immediately followed from the HY parameter.  
Now it is possible to browse the hidden menu. 

3.

 

Select the required parameter. 

4.

 

Press the SET button to display its value. 

5.

 

Use UP or DOWN to change its value. 

6.

 

Press SET to store the new value and move to the following parameter. 

 
To exit: Press SET+DOWN or wait 15 sec without pressing a key. 
 
NOTE1:  
if  no  parameter  is  present  in  Pr1  menu,  after  3  sec  the  “noP”  message  will  be  displayed. 
Keep the buttons pushed till the Pr2 message will be displayed.  
 
NOTE2:  the  set  value  is  stored  even  when  the  procedure  is  exited  by  waiting  for  the  time-out  to 
expire 
 

6.5.2  HOW  TO:  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing 
SET+DOWN  buttons. If a parameter is part of the user level, when showed in the hidden menu the 
decimal point will be lit. 

6.6

 

HOW TO: LOCK THE KEYBOARD 

1. 

 

Keep both UP and DOWN buttons pressed for more than 3 sec. 

2. 

 

The  “PoF”  message  will  be  displayed  and  the  keyboard  will  be  locked.  At  this  point  it  will  be 
possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a button is pressed more than 3 sec the “PoF” message will be displayed 

6.7

 

HOW TO: UNLOCK THE KEYBOARD 

Keep pressed together for more than 3 sec the UP

 

and DOWN keys till the “Pon” message will be 

displayed. 

6.8

 

THE CONTINUOUS CYCLE 

When defrost is not in progress, it can be activated by holding the UP key pressed for about 3 sec. 
The compressor operates to maintain the CCS set point for the time set through the CCt parameter. 
The  cycle  can  be terminated before the end of the set time using the same activation key UP for 3 
sec. 

6.9

 

THE ON/OFF FUNCTION 

 

With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF” 
message is displayed. In this configuration, the regulation is disabled. 
To switch the instrument on, push again the ON/OFF key. 

WARNING:  Loads  connected  to  the  normally  closed  contacts  of  the  relays  are  always 
supplied and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

REGULATION 

HY 

Differential:  (0.1  to  25.5°C;  1  to  45°F)  intervention  differential  for  set  point. 
Compressor Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the 
temperature reaches the set point. 

LS   

Minimum set point: (-55°C to SET; -67°F to SET) sets the minimum value for the set 
point. 

US 

Maximum  set  point:  (SET  to  150°C;  SET  to  302°F)  set  the  maximum  value for set 
point. 

ot   

Thermostat probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible 
offset of the thermostat probe. 

P2P 

First evaporator probe presence: (n; Y) n = not present, the defrost stops by time;  
Y = present, the defrost stops by temperature. 

oE 

First  evaporator  probe  calibration:  (-12.0  to  12.0°C;  -21  to  21°F)  allows  to  adjust 
possible offset of the evaporator probe. 

P3P 

Second  evaporator  probe  presence  (P3):  (n;  Y)  n  =  not  present,  the  terminals 
operate as digital input; Y = present, the terminals operate as third probe. 

o3 

Second  evaporator probe calibration (P3): (-12.0 to 12.0°C; -21 to 21°F) allows to 
adjust possible offset of the third probe. 

odS 

Outputs  activation  delay  at  start  up: (0  to  255min)  this  function  is  enabled  at  the 
initial start up of the instrument and inhibits any output activation for the period of time 
set in the parameter.  

AC   

Anti-short cycle delay for first compressor: (0 to 50 min) minimum interval between 
the compressor stop and the following restart. 

AC1   

Anti-short  cycle  delay  for  second  compressor:  (0  to  50  min)  minimum  interval 
between the compressor stop and the following restart. 

CCt 

Compressor  ON  time  during  continuous  cycle:  (0.0  to  24h00min,  res.  10  min) 
allows  to  set  the  length  of  the  continuous  cycle.  Compressor  stays  on  without 
interruption  during  CCt  time.  This  is  useful,  for  instance,  when  the  room  is  filled  with 
new products. 

CCS 

Set  point  for  continuous  cycle:  (-55  to  150°C;  -67  to  302°F)  it  sets  the  set  point 
used during the continuous cycle. 

Con 

Compressor  ON  time  with  faulty  probe:  (0  to  255min)  time  during  which  the 
compressor  is  active  in  case  of  faulty  thermostat  probe.  With  Con=0  compressor  is 
always OFF. 

CoF 

Compressor  OFF  time  with  faulty  probe:  (0  to  255min)  time  during  which  the 
compressor  is  OFF  in  case  of  faulty  thermostat  probe.  With  CoF=0  compressor  is 
always active. 

DISPLAY 

CF 

Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.  
WARNING:  When  the  measurement  unit  is  changed  the  SET  point  and  the  values of 
the  parameters  HY,  LS,  US,  ot,  ALU  and  ALL  have  to  be  checked  and  modified  (if 
necessary). 

rES 

Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display. 

Lod 

Instrument display: (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by 
the instrument. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe (only 
for  model  with  this  option  enabled);  P4  =  Fourth  probe,  SET  =  set  point;  dtr  = 
percentage of visualization. 

DEFROST 

tdF 

Defrost type: (EL; in) EL = electrical heater; in = hot gas. 

dtE 

First  defrost  termination  temperature:  (-55  to  50°C;  -67  to  122°F)  (enabled  only 
when EdF=Pb) sets the temperature measured by the evaporator probe, which causes 
the end of defrost. 

dtS 

Second  defrost  termination temperature: (-55 to 50°C; -67 to 122°F) (enabled only 
when EdF=Pb) sets the temperature measured by the evaporator probe, which causes 
the end of defrost. 

idF 

Interval  between  defrost  cycles:  (0  to  120  hours)  determines  the  interval  of  time 
between two defrost cycles. 

MdF    (Maximum)  length  for  first  defrost:  (0  to  255  min)  when  P2P=n,  (not  evaporator 

probe: timed defrost) it sets the defrost duration. When P2P=Y (defrost end based on 
temperature) it sets the maximum length for defrost. 

MdS    (Maximum)  length for second defrost: (0 to 255 min) when P2P=n, (not evaporator 

probe: timed defrost) it sets the defrost duration. When P2P=Y (defrost end based on 
temperature) it sets the maximum length for defrost. 

dSd 

Start  defrost  delay:  (0  to  99  min) this is useful when different defrost start times are 
necessary to avoid overloading the plant.  

dFd   

Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;  
it = temperature at defrost start; SEt = set point; dEF = “dEF” label. 

dAd 

MAX display delay after defrost: (0 to 255 min) sets the maximum time between the 
end of defrost and the restarting of the real room temperature display. 

Fdt 

Drip  time:  (0  to  120  min)  time  interval  between  reaching  defrost  termination 
temperature  and  the  restoring  of  the  control’s  normal  operation.  This  time  allows  the 
evaporator to eliminate water drops that might have formed due to defrost. 

dPo 

First defrost after start-up: (n; Y)  

 

n = after the idF time,  

 

Y = immediately. 

dAF 

Defrost  delay  after  continuous  cycle:  (0.0  to  24h00min,  res.  10min)  time  interval 
between the end of the fast freezing cycle and the following defrost related to it. 

FANS 

FnC 

Fans  operating  mode:  (C-n;  o-n;  C-Y;  o-Y)  C-n  =  runs  with  the  compressor,  OFF 
during  defrost;  o-n  =  continuous  mode,  OFF  during  defrost;  C-Y  =  runs  with  the 
compressor, ON during defrost; o-Y = continuous mode, ON during defrost. 

Fnd 

Fans delay after defrost: (0 to 255min) interval between end of defrost and evaporator 
fans start. 

FCt 

Temperature  differential  to  avoid fan short cycles: (0 to 59°C; 0 to 90°F) (N.B.: if 
FCt=0  function  disabled)  if  the  difference  of  temperature  between  the  evaporator  and 
the room probes is higher than FCt value, the fans will be switched on. 

FSt 

Fans stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature, detected 
by evaporator probe, above which fans are always OFF. 

ALARMS 

ALU 

MAXIMUM temperature alarm:  

 

If ALC=Ab: [ALL to 150.0°C or ALL to 302°F] 

 

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the ALd delay time. 

Summary of Contents for Dixell XR44CX

Page 1: ...heater tdF EL and hot gas defrost tdF in Other parameters are used to control the interval between defrost cycles idF its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selec...

Page 2: ...Y n not present the terminals operate as digital input Y present the terminals operate as third probe o3 Second evaporator probe calibration P3 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the third probe odS Outputs activation delay at start up 0 to 255min this function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time ...

Page 3: ... DOR It signals the door status and the corresponding relay output status through the odC parameter no normal any change FAn Fan OFF CPr Compressor OFF F_C Compressor and fan OFF Since the door is opened after the delay time set through parameter doA the door alarm is enabled the display shows the message dA and the regulation restarts is rtr YES The alarm stops as soon as the external digital inp...

Page 4: ...min 15 Pr2 CoF Compressor OFF time with faulty probe 0 to 255 min 15 Pr2 CF Temperature measurement unit C F C Pr2 rES Resolution dE in dE Pr1 Lod Probe displayed P1 P2 P3 P4 SEt dtr P1 Pr2 tdF Defrost type EL in EL Pr2 Label Name Range Value Level dtE First defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 dtS Second defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 idF ...

Reviews: