1598024001 XR44CX ISA GB r2.0 21.06.2012.doc 

XR44CX 

3/4 

ALL 

Minimum temperature alarm:  

 

If ALC=Ab: [-55°C to ALU; -67 to ALU] 

 

If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] 

when this temperature is reached the alarm is enabled, after the ALd delay time. 

AFH 

Differential  for  temperature  alarm  recovery:  (0.1  to  25.5°C;  1  to 45°F) intervention 
differential for recovery of temperature alarm. 

ALd    Temperature  alarm  delay:  (0  to  255  min)  time  interval  between  the  detection  of  an 

alarm condition and alarm signalling. 

dAo 

Exclusion  of  temperature  alarm  at  start-up:  (0.0  to  24h00min,  res.  10min)  time 
interval between the detection of the temperature alarm condition after instrument power 
on and alarm signalling. 

OUTPUT RELAYS 

oA1 

First relay configuration AUX1: (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2) dEF 
= defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; onF = 
always on when instrument on; CP2 = second compressor; dEF2 = second defrost. 

oA2 

Second relay configuration AUX2: (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2) 
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; 
onF  =  always  on  when  instrument  on;  CP2  =  second  compressor;  dEF2  =  second 
defrost. 

oA3 

Third  relay  configuration  AUX3:  (dEF;  FAn;  ALr;  LiG;  AUS;  onF;  db;  CP2;  dEF2) 
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; 
onF  =  always  on  when  instrument  on;  CP2  =  second  compressor;  dEF2  =  second 
defrost. 

DIGITAL INPUTS 

i1P 

Second digital input polarity: (oP; CL) oP = the digital input is activated by opening 
the contact; CL = the digital input is activated by closing the contact. 

i1F   

Second digital input configuration: (EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES) 
EAL = external alarm: “EA” message is displayed; bAL = serious alarm “CA” message 
is  displayed;  PAL  =  pressure  switch  alarm,  “CA”  message  is  displayed;  dor  =  door 
switch function; dEF = activation of a defrost cycle; AUS = auxiliary relay activation with 
oAx=AUSHtr = type of inverting action (cooling or heating); FAn = fan; ES = energy 
saving. 

did 

Digital input 1 alarm delay:  (0 to 255 min) delay between the detection of the external 
alarm condition and its signalling. 
When  i1F=  PAL,  it  is  the  interval  of  time  to  calculate  the  number  of  pressure  switch 
activation. 

nPS 

Number of pressure switch activation: (0 to 15) Number of activation, during the did 
or d2d interval, before signalling an alarm event (i1F, i2F=PAL).  
If  the  nPS  activation  during  did  or  d2d  time  is  reached,  switch  off  and  on  the 
instrument to restart normal regulation. 

odC 

Compressor status when open door: (no; FAn; CPr;F_C;)  no = normal;  
FAn = normal; CPr = compressor OFF, F_C = compressor OFF. 

rrd 

Outputs restart after door open alarm: (n; Y) n = outputs follow the odC parameter.  
Y = outputs restart with a door open alarm.  

HES 

Delta temperature during an Energy Saving cycle: (-30.0 to 30.0°C; -54 to 54°F) it 
sets the increasing value of the set point [SET+HES] during the Energy Saving cycle. 

OTHER 

Adr 

Serial  address:  (1  to  247)  identifies  the  instrument  address  when  connected  to  a 
ModBUS compatible monitoring system. 

PbC 

Type of probe: (PtC; ntC) it allows to set the kind of probe used by the instrument:  
PtC = PTC probe, ntC = NTC probe. 

onF 

On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it. 

dP1 

Thermostat probe display. 

dP2 

Evaporator probe display. 

dP3 

Third probe display- optional. 

rEL 

Software release for internal use. 

Ptb 

Parameter table code: readable only. 

8.

 

DIGITAL INPUTS  

The free voltage digital input is programmable by the i1F parameter. 

8.1

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL 
alarm message. The outputs statuses don’t change. The alarm stops just after the digital input is de-
activated. 

8.2

 

SERIOUS ALARM MODE (I1F = BAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  did  delay  before  signalling  the  CA  alarm 
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.3

 

PRESSURE SWITCH (I1F = PAL) 

If  during  the  interval  time  set  by  did  parameter,  the  pressure  switch  has  reached  the  number  of 
activation of the nPS parameter; the CA pressure alarm message will be displayed. The compressor 
and  the  regulation  are  stopped.  When the digital input is ON the compressor is always OFF. If the 
nPS activation in the did time is reached, switch off and on the instrument to restart normal 
regulation. 

8.4

 

DOOR SWITCH INPUT (I1F = DOR) 

It signals the door status and the corresponding relay output status through the odC parameter:  
no  =  normal  (any  change);  FAn = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan 
OFF.  Since  the  door  is  opened,  after  the delay time set through parameter doA, the door alarm is 
enabled,  the  display  shows  the  message  dA  and  the  regulation  restarts  is  rtr=YES.  The  alarm 
stops  as  soon  as  the  external  digital  input  is  disabled  again.  With  the  door open, the high and low 
temperature alarms are disabled. 

8.5

 

START DEFROST (I1F = DEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation 
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety 
time is expired. 

8.6

 

SWITCH THE AUXILIARY RELAY (I1F = AUS) 

With oA3 = AUS the digital input switched the status of the auxiliary relay 

8.7

 

ENERGY SAVING (I1F = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+  HES 
(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

ON OFF FUNCTION (I1F = ONF)  

To switch the controller on and off. 

8.9

 

DIGITAL INPUT POLARITY  

The digital input polarity depends on the i1P parameter. 
i1P = CL: the input is activated by closing the contact. 
i1P = oP
: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows to connect the instrument to a 
monitoring system ModBUS-RTU compatible such as the XWEB500. The connection needs a special 
TTL/RS485 adapter: the XJ485CX

10.

 

INSTALLATION AND MOUNTING 

 

Instrument XR70CX shall be mounted on vertical panel, in a 29x71 
mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0 to 60°C. 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to 
probes. Let air circulate by the cooling holes. 
 

 

11.

 

ELECTRICAL CONNECTIONS 

The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to 
2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of heavier 
loads use a suitable external relay. 

11.1

 

PROBE CONNECTION 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room  temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

12.

 

USE THE HOT KEY  

12.1

 

HOW TO: PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON,  insert  the  “HOT-KEY”  and  push  UP  button;  the  “uPL  message 
appears followed a by a flashing “End” label. 

3.

 

Push SET button and the “End” will stop flashing. 

4.

 

Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again. 

 
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again 
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation. 

12.2

 

HOW TO: PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a pre-programmed HOT-KEY into the 5-PIN receptacle and then turn the Controller 
ON. 

3.

 

The  parameter  list  of  the  “HOT-KEY”  will  be  automatically  downloaded  into  the  Controller 
memory. The “doL” message will blink followed a by a flashing “End” label. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “HOT-KEY”. 
 

NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then 
on if you want to restart the download again or remove the “HOT-KEY” to abort the operation. 

13.

 

ALARM SIGNALS 

Message 

Cause 

Outputs 

P1 

Room probe  failure 

Compressor output acc. to par. Con and CoF 

P2 

Evaporator probe  failure 

Defrost end is timed 

P3 

Third probe  failure 

Outputs unchanged 

HA 

Maximum temperature alarm 

Outputs unchanged. 

LA 

Minimum temperature alarm 

Outputs unchanged. 

dA 

Door open 

Compressor and fans restarts  

EA 

External alarm 

Output unchanged. 

CA 

Serious external alarm (i2F=bAL)  All outputs OFF. 

CA 

Pressure switch alarm (i2F=PAL)  All outputs OFF 

Summary of Contents for Dixell XR44CX

Page 1: ...heater tdF EL and hot gas defrost tdF in Other parameters are used to control the interval between defrost cycles idF its maximum length MdF and two defrost modes timed or controlled by the evaporator s probe P2P At the end of defrost dripping time is started its length is set in the Fdt parameter With Fdt 0 the dripping time is disabled 3 4 CONTROL OF EVAPORATOR FANS The fan control mode is selec...

Page 2: ...Y n not present the terminals operate as digital input Y present the terminals operate as third probe o3 Second evaporator probe calibration P3 12 0 to 12 0 C 21 to 21 F allows to adjust possible offset of the third probe odS Outputs activation delay at start up 0 to 255min this function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time ...

Page 3: ... DOR It signals the door status and the corresponding relay output status through the odC parameter no normal any change FAn Fan OFF CPr Compressor OFF F_C Compressor and fan OFF Since the door is opened after the delay time set through parameter doA the door alarm is enabled the display shows the message dA and the regulation restarts is rtr YES The alarm stops as soon as the external digital inp...

Page 4: ...min 15 Pr2 CoF Compressor OFF time with faulty probe 0 to 255 min 15 Pr2 CF Temperature measurement unit C F C Pr2 rES Resolution dE in dE Pr1 Lod Probe displayed P1 P2 P3 P4 SEt dtr P1 Pr2 tdF Defrost type EL in EL Pr2 Label Name Range Value Level dtE First defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 dtS Second defrost termination temperature 55 to 50 0 C 67 to 122 F 8 Pr1 idF ...

Reviews: