1598024xxx XR30CX VST GB r1.0 2011.01.21.doc
XR30CX
3/4
bon
Time of buzzer restart after muting, in case of alarm duration:
(0÷30min) when 0
the buzzer is always off after muting.
AoP
Alarm relay polarity:
it set if the alarm relay is open or closed when an alarm
happens.
CL
= terminals 1-2 closed during an alarm;
oP
= terminals 1-2 open during
an alarm
DIGITAL INPUT
i1P
Digital input polarity:
(oP; CL)
oP
= the digital input is activated by opening the
contact;
CL
= the digital input is activated by closing the contact.
i1F
Digital input configuration:
(EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES)
EAL
= external alarm: “EA” message is displayed;
bAL
= serious alarm “CA”
message is displayed.
PAL
= pressure switch alarm, “CA” message is displayed;
dor
= door switch function;
dEF
= activation of a defrost cycle;
AUS
=to switch on the
second relay if oA1 = AUS;
Htr
= kind of action inversion (cooling – heating);
FAn =
not set it; ES
= Energy saving.
did
Digital input alarm delay when i1F=EAL or i1F=bAL:
(0÷255 min) delay between
the detection of the external alarm condition and its signalling.
With i1F= dor: door open signalling delay.
With i1F=PAL: time for pressure switch function.
It is the time
interval to calculate the number of the pressure switch activation.
nPS
Number of pressure switch activation:
(0
15) Number of activation, during the
did
interval, before signalling an alarm event (
i2F=PAL
).
If the
nPS
activation during
did
time is reached, switch off and on the instrument to
restart normal regulation.
odc
Compressor status when open door:
(no; FAn; CPr;F_C;)
no
= normal;
FAn
= normal;
CPr
= compressor OFF,
F_C
= compressor OFF.
rrd
Outputs restart after doA alarm:
(n; Y)
n
= outputs not affected by the
doA
alarm;
Y
= outputs restart with the
doA
alarm.
HES
Temperature increase during the Energy Saving cycle:
(-30.0
30.0°C; -54
54°F)
it sets the increasing value of the set point
[SET+HES]
during the Energy Saving
cycle.
OTHER
Adr
Serial address:
(1÷244) identifies the instrument address when connected to a
ModBUS compatible monitoring system.
PbC
Type of probe:
(ntC, CtC) it allows to set the kind of probe used by the instrument:
PtC
= PTC probe,
Pt1 =
Pt1000 probe.
onF
On/Off key enabling:
(nU; oFF; ES)
nU
= disabled;
oFF
= enabled;
ES
= not set it.
rSE
Real set point:
it shows the set point used during the energy saving cycle or during
the continuous cycle.
rEL
Software release for internal use.
Ptb
Parameter table code:
readable only.
8. DIGITAL INPUT
The free voltage digital input is programmable in different configurations by the
i1F
parameter.
8.1 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the
odC
parameter:
no,
Fan
= normal (any change);
CPr, F_C
= Compressor OFF.
Since the door is opened, after the delay time set through parameter
did
, the door alarm is enabled,
the display shows the message “
dA
” and
the regulation restarts is rtr=Y.
The alarm stops as soon
as the external digital input is disabled again. With the door open, the high and low temperature alarms
are disabled.
8.2 GENERIC ALARM (i1F = EAL)
As soon as the digital input is activated the unit will wait for
did
time delay before signalling the “
EAL
”
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-
activated.
8.3 SERIOUS ALARM MODE (i1F = bAL)
When the digital input is activated, the unit will wait for
did
delay before signalling the “
CA
” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
8.4 PRESSURE SWITCH (i1F = PAL)
If during the interval time set by
did
parameter the pressure switch reaches the
nPS
number of
activation, the “
CA
” pressure alarm message will be displayed and the compressor and the regulation
will be stopped. When the digital input is ON the compressor is always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument to restart
normal regulation.
8.5 START DEFROST (i1F = dFr)
A defrost will start if there are the right conditions. After the defrost is finished, the normal regulation
will restart only if the digital input is disabled otherwise the instrument will wait for
MdF
safety time to
expire.
8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
8.7 ENERGY SAVING (i1F = ES)
The Energy Saving function allows to change the set point value as the result of the
[SET+ HES]
(parameter) sum. This function is enabled until the digital input is activated.
8.8 DIGITAL INPUTS POLARITY
The digital input polarity depends on the
i1P
parameter.
i1P=CL
: the input is activated by closing the contact.
i1P=OP
: the input is activated by opening the contact
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS
It is possible to connect the instrument to a
ModBUS-RTU
compatible monitoring system (e.g.
X-WEB500/3000/300) by using the TTL serial line available on the HOTKEY connector. An external
adapter has to be used to connect the device to the network (e.g. a TTL/RS485 converter
XJ485-CX
).
10. INSTALLATION AND MOUNTING
Instrument
XR30CX
shall be mounted on vertical panel, in a 29x71
mm hole, and fixed using the special bracket supplied.
The temperature range allowed for correct operation is 0
60 °C.
Avoid places subject to strong vibrations, corrosive gases,
excessive dirt or humidity. The same recommendations apply to
probes. Let air circulate by the cooling holes.
11. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to
2.5mm
2
. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
loads use a suitable external relay.
11.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the evaporator
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
12. HOW TO USE THE HOT KEY
12.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
2.
When the controller is ON, insert the “HOT-KEY” and push
UP
button; the “
uPL
” message
appears followed a by a flashing “
End
” label.
3.
Push
SET
button and the “
End
” will stop flashing.
4.
Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again.
NOTE
: the “
Err
” message appears in case of a failed programming operation. In this case push again
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation.
12.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a
pre-programmed
“Hot Key”
into the 5-PIN receptacle
and then turn the Controller
ON.
3.
The parameter list of the “Hot Key” will be automatically downloaded into the Controller
memory. The “
doL
” message will blink followed a by a flashing “
End
” label.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the “HOT-KEY”.
NOTE:
the message “
Err
” is displayed for failed programming. In this case turn the unit off and then
on if you want to restart the download again or remove the “HOT-KEY” to abort the operation.
13. ALARM SIGNALS
Message
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par.
Con
and
CoF
.
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA”
Minimum temperature alarm
Outputs unchanged.
“dA”
Door open
Compressor restart according to
rrd
.
“EA”
External alarm
Output unchanged.
“CA”
Serious external alarm (
i1F=bAL
) All outputs OFF.
“CA”
Pressure switch alarm (
i1F=PAL
) All outputs OFF
13.1 ALARM RECOVERY
Probe alarm “
P1
” starts some seconds after the fault in the related probe; they automatically stop
some seconds after the probe restarts normal operation. Check connections before replacing the
probe.
Temperature alarms “
HA
” and “
LA
” automatically stop as soon as the temperature returns to normal
values.
Alarms “
EA
” and “
CA
” (with
i1F=bAL
) recover as soon as the digital input is disabled.
Alarm “
CA”
(with
i1F=PAL
) recovers only by
switching off and on
the instrument.
13.2 OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP In programming mode
: none parameter is present in Pr1
On the display
or in dP2, dP3, dP4: the selected probe is nor enabled
noA No alarm recorded.
14. TECHNICAL DATA
Housing:
self extinguishing ABS.
Case: XR30CX
frontal 32x74mm; depth 60mm.
Mounting: XR30CX
panel mounting in a 71x29mm panel cut-out.
Protection:
IP20.
Frontal protection: XR30CX
IP65.
Connections:
Screw terminal block
2.5 mm
2
wiring.
Power supply:
100Vac
10%, 50/60Hz; 230Vac
10%, 50/60Hz.