1598024xxx XR30CX VST GB r1.0 2011.01.21.doc

XR30CX

3/4

bon

Time of buzzer restart after muting, in case of alarm duration:

(0÷30min) when 0

the buzzer is always off after muting.

AoP

Alarm  relay  polarity:

it  set  if  the alarm  relay  is  open  or  closed  when  an  alarm

happens.

CL

= terminals 1-2 closed during an alarm;

oP

= terminals 1-2 open during

an alarm

DIGITAL INPUT

i1P

Digital  input  polarity:

(oP;  CL)

oP

= the  digital  input  is activated by opening the

contact;

CL

= the digital input is activated by closing the contact.

i1F

Digital input configuration:

(EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES)

EAL

=  external  alarm:  “EA”  message  is  displayed;

bAL

=  serious  alarm  “CA”

message is displayed.

PAL

= pressure switch alarm, “CA” message is displayed;

dor

= door switch function;

dEF

= activation of a defrost cycle;

AUS

=to switch on the

second relay if oA1 = AUS;

Htr

= kind of action inversion (cooling – heating);

FAn =

not set it; ES

= Energy saving.

did

Digital input alarm delay when i1F=EAL or i1F=bAL:

(0÷255 min) delay between

the detection of the external alarm condition and its signalling.

With i1F= dor: door open signalling delay.

With  i1F=PAL:  time  for  pressure  switch  function.

It  is  the time

interval to calculate the number of the pressure switch activation.

nPS

Number of pressure switch activation:

(0

15) Number of activation, during the

did

interval, before signalling an alarm event (

i2F=PAL

).

If the

nPS

activation during

did

time is reached, switch off and on the instrument to

restart normal regulation.

odc

Compressor status when open door:

(no; FAn; CPr;F_C;)

no

= normal;

FAn

= normal;

CPr

= compressor OFF,

F_C

= compressor OFF.

rrd

Outputs restart after doA alarm:

(n; Y)

n

= outputs not affected by the

doA

alarm;

Y

= outputs restart with the

doA

alarm.

HES

Temperature increase during the Energy Saving cycle:

(-30.0

30.0°C; -54

54°F)

it  sets  the  increasing  value  of the  set  point

[SET+HES]

during  the Energy Saving

cycle.

OTHER

Adr

Serial  address:

(1÷244) identifies  the  instrument  address  when  connected  to  a

ModBUS compatible monitoring system.

PbC

Type of probe:

(ntC, CtC) it allows to set the kind of probe used by the instrument:

PtC

= PTC probe,

Pt1 =

Pt1000 probe.

onF

On/Off key enabling:

(nU; oFF; ES)

nU

= disabled;

oFF

= enabled;

ES

= not set it.

rSE

Real set point:

it shows the set point used during the energy saving cycle or during

the continuous cycle.

rEL

Software release for internal use.

Ptb

Parameter table code:

readable only.

8. DIGITAL INPUT

The free voltage digital input is programmable in different configurations by the

i1F

parameter.

8.1 DOOR SWITCH INPUT  (i1F = dor)

It signals the door status and the corresponding relay output status through the

odC

parameter:

no,

Fan

= normal (any change);

CPr, F_C

= Compressor OFF.

Since the door is opened, after the delay time set through parameter

did

, the door alarm is enabled,

the display shows the message “

dA

” and

the regulation restarts is rtr=Y.

The alarm stops as soon

as the external digital input is disabled again. With the door open, the high and low temperature alarms

are disabled.

8.2 GENERIC ALARM (i1F = EAL)

As soon as the digital input is activated the unit will wait for

did

time delay before signalling the “

EAL

alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-

activated.

8.3 SERIOUS ALARM MODE (i1F = bAL)

When the digital input is activated, the unit will wait for

did

delay before signalling the “

CA

” alarm

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated.

8.4 PRESSURE SWITCH (i1F = PAL)

If  during  the  interval  time  set  by

did

parameter  the  pressure  switch  reaches the

nPS

number  of

activation, the “

CA

” pressure alarm message will be displayed and the compressor and the regulation

will be stopped. When the digital input is ON the compressor is always OFF.

If the nPS activation in the did time is reached, switch off and on the instrument to restart

normal regulation.

8.5 START DEFROST (i1F = dFr)

A defrost will start if there are the right conditions. After the defrost is finished, the normal regulation

will restart only if the digital input is disabled otherwise the instrument will wait for

MdF

safety time to

expire.

8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)

This function allows to invert the regulation of the controller: from cooling to heating and viceversa.

8.7 ENERGY SAVING (i1F = ES)

The Energy Saving function allows to change the set point value as the result of the

[SET+ HES]

(parameter) sum. This function is enabled until the digital input is activated.

8.8 DIGITAL INPUTS POLARITY

The digital input polarity depends on the

i1P

parameter.

i1P=CL

: the input is activated by closing the contact.

i1P=OP

: the input is activated by opening the contact

9. TTL SERIAL LINE – FOR MONITORING SYSTEMS

It is possible to connect the instrument to a

ModBUS-RTU

compatible monitoring system (e.g.

X-WEB500/3000/300) by using the TTL serial line available on the HOTKEY connector. An external

adapter has to be used to connect the device to the network (e.g. a TTL/RS485 converter

XJ485-CX

).

10. INSTALLATION AND MOUNTING

Instrument

XR30CX

shall be mounted on vertical panel, in a 29x71

mm hole, and fixed using the special bracket supplied.

The temperature range allowed for correct operation is 0

60 °C.

Avoid places subject to strong vibrations, corrosive gases,

excessive dirt or humidity. The same recommendations apply to

probes. Let air circulate by the cooling holes.

11. ELECTRICAL CONNECTIONS

The instrument is provided with screw terminal block to connect cables with a cross section up to

2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and the

power connections. Do not exceed the maximum current allowed on each relay, in case of heavier

loads use a suitable external relay.

11.1 PROBE CONNECTION

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid

infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly

measure the average room temperature. Place the defrost termination probe among the evaporator

fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during

defrost, to prevent premature defrost termination.

12. HOW TO USE THE HOT KEY

12.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)

1.

Program one controller with the front keypad.

2.

When  the  controller  is ON,  insert  the “HOT-KEY” and push

UP

button; the “

uPL

” message

appears followed a by a flashing “

End

” label.

3.

Push

SET

button and the “

End

” will stop flashing.

4.

Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again.

NOTE

: the “

Err

” message appears in case of a failed programming operation. In this case push again

button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation.

12.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)

1.

Turn OFF the instrument.

2.

Insert a

pre-programmed

“Hot Key”

into the 5-PIN receptacle

and then turn the Controller

ON.

3.

The  parameter  list  of  the “Hot  Key” will  be  automatically downloaded  into  the  Controller

memory. The “

doL

” message will blink followed a by a flashing “

End

” label.

4.

After 10 seconds the instrument will restart working with the new parameters.

5.

Remove the “HOT-KEY”.

NOTE:

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then

on if you want to restart the download again or remove the “HOT-KEY” to abort the operation.

13. ALARM SIGNALS

Message

Cause

Outputs

“P1”

Room probe  failure

Compressor output acc. to par.

Con

and

CoF

.

“HA”

Maximum temperature alarm

Outputs unchanged.

“LA”

Minimum temperature alarm

Outputs unchanged.

“dA”

Door open

Compressor restart according to

rrd

.

“EA”

External alarm

Output unchanged.

“CA”

Serious external alarm (

i1F=bAL

) All outputs OFF.

“CA”

Pressure switch alarm (

i1F=PAL

) All outputs OFF

13.1 ALARM RECOVERY

Probe alarm “

P1

” starts some seconds after the fault in the related probe; they automatically stop

some  seconds  after  the  probe  restarts  normal  operation.  Check  connections  before  replacing  the

probe.

Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the temperature returns to normal

values.

Alarms “

EA

” and “

CA

” (with

i1F=bAL

) recover as soon as the digital input is disabled.

Alarm “

CA”

(with

i1F=PAL

) recovers only by

switching off and on

the instrument.

13.2 OTHER MESSAGES

Pon

Keyboard unlocked.

PoF

Keyboard locked

noP In programming mode

: none parameter is present in Pr1

On the display

or in dP2, dP3, dP4: the selected probe is nor enabled

noA No alarm recorded.

14. TECHNICAL DATA

Housing:

self extinguishing ABS.

Case: XR30CX

frontal 32x74mm; depth 60mm.

Mounting: XR30CX

panel mounting in a 71x29mm panel cut-out.

Protection:

IP20.

Frontal protection: XR30CX

IP65.

Connections:

Screw terminal block

2.5 mm

2

wiring.

Power supply:

100Vac

10%, 50/60Hz; 230Vac

10%, 50/60Hz.

Summary of Contents for Dixell XR30CX-4S1C1

Page 1: ...estriction of the use of certain hazardous substances in electrical and electronic equipment RoHS directive This drawing is the property of A S Vestfrost and must not be copied passed on to or otherwise used by any person without the express consent of A S Vestfrost Date Last modification Init Denne vare er specificeret ved nedenstående datablad Med forudgående skriftlig tilladelse fra Vestfrost k...

Page 2: ...the digital input can operate as third temperature probe The battery backup version is also provided with an input for external battery It is used to supply the controller in case of main voltage failure By using the HOT KEY input output port is possible to upload a new parameter map from program the controller or save the actual parameter map to an external memory device named HOTKEY memory Moreo...

Page 3: ...0 1 25 5 C 1 255 F intervention differential for set point Compressor Cut IN is Set Point differential HY Compressor Cut OUT is when the temperature reaches the set point LS Minimum set point 100 C SET 148 F SET it sets the minimum value for the set point US Maximum set point SET 150 C SET 302 F it sets the maximum value for set point ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to...

Page 4: ...ing function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until the digital input is activated 8 8 DIGITAL INPUTS POLARITY The digital input polarity depends on the i1P parameter i1P CL the input is activated by closing the contact i1P OP the input is activated by opening the contact 9 TTL SERIAL LINE FOR MONITORING SYSTEMS It is possible...

Page 5: ... 60 Pr2 CoF Compressor OFF time with faulty probe 0 255 min 5 5 Pr2 CH Kind of action CL cooling Ht heating CL CL Pr2 CF Temperature measurement unit C F C C Pr2 rES Resolution in integer dE dec point in in Pr2 dLY Display temperature delay 0 20min 00s res 10s 0 0 0 0 Pr2 idF Interval between defrost cycles 1 120 hours 0 0 Pr1 MdF Maximum length for defrost 0 255 min 0 0 Pr1 dFd Displaying during ...

Reviews: