1598024xxx XR30CX VST GB r1.0 2011.01.21.doc

XR30CX

1/4

Digital controllers with off cycle defrost, AUX relay,

power supply 100 or 230VAC and battery backup.

XR30CX

CONTENTS

1.

GENERAL WARNING__________________________________________________________1

2.

GENERAL DESCRIPTION ______________________________________________________1

3.

CONTROLLING LOADS ________________________________________________________1

4.

FRONT PANEL COMMANDS____________________________________________________1

5.

MAX & MIN TEMPERATURE MEMORIZATION _____________________________________1

6.

MAIN FUNCTIONS ____________________________________________________________2

7.

PARAMETERS _______________________________________________________________2

8.

DIGITAL INPUT_______________________________________________________________3

9.

TTL SERIAL LINE – FOR MONITORING SYSTEMS _________________________________3

10. INSTALLATION AND MOUNTING ________________________________________________3

11. ELECTRICAL CONNECTIONS___________________________________________________3

12. HOW TO USE THE HOT KEY ___________________________________________________3

13. ALARM SIGNALS _____________________________________________________________3

14. TECHNICAL DATA ____________________________________________________________3

15. CONNECTIONS ______________________________________________________________4

16. DEFAULT SETTING VALUES ___________________________________________________4

1. GENERAL WARNING

1.1 PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and quick

reference.

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It

cannot be used as a safety device.

Check the application limits before proceeding.

1.2

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding

sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of

condensation

Warning:

disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”

(see address) with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from

each other, without crossing or intertwining.

In  case  of  applications  in  industrial  environments,  the  use  of mains filters (our mod. FT1) in

parallel with inductive loads could be useful.

2. GENERAL DESCRIPTION

NOTE:

This manual is related to the following model:

Model description

User code

Power Supply

Options

XR30CX -4S1C1

7020115

100VAC

-

XR30CX -5S1C1

7020110

230VAC

-

XR30CX -5S1C1

7020122

230VAC

Battery backup

Model

XR30CX

, format 32x74mm, is a digital thermostat with off cycle defrosting function designed for

refrigeration applications. It provides two relay outputs, one for the compressor and the other one for

alarm  signalling. It  is  also  provided  with a PT1000  or  PTC  probe  input for  temperature  control.

Moreover, the digital input can operate as third temperature probe.

The battery-backup version is also provided with an input for external battery. It is used to supply the

controller in case of main voltage failure.

By using the HOT-KEY input/output port is possible to upload a new parameter map from (program the

controller)  or  save  the  actual  parameter  map  to  an  external  memory  device  (named  HOTKEY

memory). Moreover, by using this port is possible to connect the device to a network line (ModBUS-

RTU compatible) such as a

dIXEL

monitoring units of X-WEB family. In this case, a special adapter

(XJ485-CX) has to be used.

3. CONTROLLING LOADS

3.1 COMPRESSOR

The regulation is performed according to

the  temperature  measured  by  the

thermostat  probe  with  a  positive

differential (HY) from the set point: if the

temperature  increases  and  reaches  set

point plus differential the compressor is

started  and  then  turned  off  when  the

temperature reaches the set point value

again.

Time

Temper.

Compr.

SET

ON

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through

parameters

Con

and

CoF

.

3.2 DEFROST

Defrost is performed through a simple stop of the compressor. Parameter

idF

controls the interval

between defrost cycles, while its length is controlled by using

MdF

parameter.

3.3 DEVICE OPERATIONS IN CASE OF POWER FAILURE, IF A BACK UP

BATTERY IS CONNECTED (ONLY FOR 7020122-01 MODEL)

3.3.1 Power failure without temperature alarm

If the controller is connected to the battery, during a power failure:

1. The alarm LED icon will be lit.

2. The alarm relay will be activated according to the

Aro

parameter.

3. Every 5s the buzzer will ring 3 times during 1s.

The buzzer will be muted after pressing any button. It will restart ringing after the

bon

time if the power

failure keeps on lasting. After pushing

SET

button, the controller will display the temperature for 5s.

3.3.2 Power failure and temperature alarms

If a temperature alarm happens during a power failure:

1.

The alarm LED icon will be lit.

2.

The buzzer will ring continuously.

3.

The displays will shows: real temperature for 1s, alarm label for 1s and remains off for 5s.

The buzzer will be muted for the

bon

time after pressing any button.

The battery can guarantee at least 50 hours of operations in this conditions.

The time for a full charge of the battery is 94 hours.

4. FRONT PANEL COMMANDS

To display target set point.

In programming mode it selects a parameter or confirm an operation.
(

DEF

) To start a manual defrost.

(

UP

) To see the max stored temperature. In programming mode it browses

parameters or increases the displayed value.

(

DOWN

)  To  see  the  min  stored  temperature.  In  programming  mode  it

browses the parameters or decreases the displayed value.
To switch the instrument on and off when

onF=oFF

.

NOT USED

KEY COMBINATIONS:

+

To lock & unlock the keyboard

.

+

To enter in programming mode.

+

To return to the room temperature display.

4.1 USE OF LEDS

Each LED function is described in the following table.

LED

MODE

FUNCTION

ON

Compressor enabled

Flashing

Anti-short cycle delay enabled

ON

Defrost enabled

ON

An alarm is occurring

ON

Continuous cycle is running

ON

Energy saving enabled

°C/°F

ON

Measurement unit

Flashing

Programming phase

5. MAX & MIN TEMPERATURE MEMORIZATION

5.1 HOW TO SEE THE MIN TEMPERATURE

1.

Press and release the

DOWN

button.

2.

The “

Lo

” message will be displayed followed by the minimum temperature recorded.

3.

By pressing the

DOWN

button again or by waiting for 5s the normal display will be restored.

Summary of Contents for Dixell XR30CX-4S1C1

Page 1: ...estriction of the use of certain hazardous substances in electrical and electronic equipment RoHS directive This drawing is the property of A S Vestfrost and must not be copied passed on to or otherwise used by any person without the express consent of A S Vestfrost Date Last modification Init Denne vare er specificeret ved nedenstående datablad Med forudgående skriftlig tilladelse fra Vestfrost k...

Page 2: ...the digital input can operate as third temperature probe The battery backup version is also provided with an input for external battery It is used to supply the controller in case of main voltage failure By using the HOT KEY input output port is possible to upload a new parameter map from program the controller or save the actual parameter map to an external memory device named HOTKEY memory Moreo...

Page 3: ...0 1 25 5 C 1 255 F intervention differential for set point Compressor Cut IN is Set Point differential HY Compressor Cut OUT is when the temperature reaches the set point LS Minimum set point 100 C SET 148 F SET it sets the minimum value for the set point US Maximum set point SET 150 C SET 302 F it sets the maximum value for set point ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to...

Page 4: ...ing function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until the digital input is activated 8 8 DIGITAL INPUTS POLARITY The digital input polarity depends on the i1P parameter i1P CL the input is activated by closing the contact i1P OP the input is activated by opening the contact 9 TTL SERIAL LINE FOR MONITORING SYSTEMS It is possible...

Page 5: ... 60 Pr2 CoF Compressor OFF time with faulty probe 0 255 min 5 5 Pr2 CH Kind of action CL cooling Ht heating CL CL Pr2 CF Temperature measurement unit C F C C Pr2 rES Resolution in integer dE dec point in in Pr2 dLY Display temperature delay 0 20min 00s res 10s 0 0 0 0 Pr2 idF Interval between defrost cycles 1 120 hours 0 0 Pr1 MdF Maximum length for defrost 0 255 min 0 0 Pr1 dFd Displaying during ...