background image

1598024xxx XR30CX VST GB r1.0 2011.01.21.doc

XR30CX

2/4

5.2 HOW TO SEE THE MAX TEMPERATURE

1.

Press and release the

UP

button.

2.

The “

Hi

” message will be displayed, followed by the maximum recorded temperature.

3.

By pressing the

UP

button again or by waiting for 5s, the normal display will be restored.

5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED

1.

Keep

SET

button pressed more than 3s while the max or min temperature is displayed

(“

rSt

” message will be displayed).

2.

To confirm the operation the “

rSt

” message starts blinking and the normal temperature will be

displayed.

6. MAIN FUNCTIONS

6.1 HOW TO SEE THE SETPOINT

1.

Push and immediately release the

SET

button: the display will show the

Set point value;

2.

Push and immediately release the

SET

button or wait for 5 seconds to

display the probe value again.

6.2 HOW TO CHANGE THE SETPOINT

1.

Keep

SET

button pressed more than 2 seconds to change the Set point value.

2.

The value of the set point will be displayed and the “

°C

” or “

°F

” LED icon will start blinking.

3.

To change the Set-point value, push the

UP

or

DONW

buttons within 10s.

4.

To memorise the new set point value, push the

SET

button again or wait for 10s.

6.3 HOW TO START A MANUAL DEFROST

Push the

DEF

key for more than 2 seconds and a manual defrost will start.

6.4 HOW TO CHANGE A PARAMETER VALUE

To change any parameter value, operate as follows:

1. Enter the Programming mode by pressing

SET + DOWN

for 3s (the “

°C

” or “

°F

” LED icons will

start blinking).

2. Select the required parameter. Press

SET

to display its value.

3. Use

UP

or

DOWN

to change its value.

4. Press

SET

to store the new value and move to the following parameter.

To exit

: Press

SET + UP

or wait for 15s without pressing any key.

NOTE

: the set value is stored even when the procedure is exited by waiting for the time-out to expire.

6.5 THE HIDDEN MENU

The hidden menu includes all the parameters of the instrument.

6.5.1 HOW TO ENTER THE HIDDEN MENU

1. Enter the Programming mode by pressing

SET + DOWN

for 3s (the “

°C

” or “

°F

” LED icons will

start blinking).

2. Released the buttons and then push again them (

SET + DOWN

) for more than 7s. The Pr2 label

will be displayed immediately, followed from the

HY

parameter.

Now it is possible to browse the hidden menu.

3. Select the required parameter.

4. Press

SET

to display its value

5. Use

UP

or

DOWN

to change its value.

6. Press

SET

to store the new value and move to the following parameter.

To exit

: Press

SET + UP

or wait for 15s without pressing any key.

NOTE1:

if no parameter is present in Pr1, after 3s the “

noP

” message will be displayed. Keep the

buttons pushed till the Pr2 message will be displayed.

NOTE2

: the set value is stored even when the procedure is exited by waiting for the time-out to expire.

6.5.2 HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE

FIRST LEVEL AND VICEVERSA.

Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing

SET + DOWN

buttons. If a parameter is part of the user level, when showed in the hidden menu the

decimal point will be lit.

6.6 HOW TO LOCK THE KEYBOARD

1.

Keep pressed for more than 3 s the

UP

+

DOWN

buttons.

2.

The “

PoF

” message will be displayed and the keyboard will be locked. At this point it will be

possible only to see the set point or the MAX o Min temperature stored

3.

If a button is pressed more than 3s the “

PoF

” message will be displayed.

6.7 TO UNLOCK THE KEYBOARD

Keep pressed both

UP

and

DOWN

for more than 3s till the

“Pon”

message will be displayed.

6.8 THE CONTINUOUS CYCLE

When defrost is not in progress, it can be activated by keeping the

UP

button pressed for about 3

seconds. The compressor operates to maintain the

CCS

set point for the time set through the

CCt

parameter.  The  cycle  can  be  terminated  before  the  end  of the set time using the same activation

button (

UP

for 3 seconds).

6.9 THE ON/OFF FUNCTION

When “

onF=oFF

”, pushing the

ON/OFF

key, the instrument is switched off. The “

OFF

message is displayed. In this configuration, the regulation is disabled.

To switch the instrument on, push again the

ON/OFF

key.

WARNING: Loads connected to the normally closed contacts of the relays are always supplied

and under voltage, even if the instrument is in stand by mode.

7. PARAMETERS

REGULATION

HY

Differential:

(0.1÷25.5°C; 1÷255°F) intervention differential for set point. Compressor

Cut IN is Set Point + differential (

HY

). Compressor Cut OUT is when the temperature

reaches the set point.

LS

Minimum set point:

(-100°C÷SET; -148°F÷SET) it sets the minimum value for the

set point.

US

Maximum set point:

(SET÷150°C; SET÷302°F) it sets the maximum value for set

point.

ot

Thermostat  probe  calibration:

(-12.0÷12.0°C; -120÷120°F)  allows  to  adjust

possible offset of the thermostat probe.

odS

Outputs  activation  delay  at  start  up:

(0÷255min) this  function  is  enabled  at  the

initial start up of the instrument and inhibits any output activation for the period of time

set in the parameter.

AC

Anti-short cycle delay:

(0÷50min) minimum interval between the compressor stop

and the following restart.

rtr

Percentage of the second and first probe for regulation:

(0÷100; 100=P1, 0=P2)

it  allows  to  set  the  regulation  according  to  the  percentage  of  the  first  and  second

probe, as for the following formula (

rtr

(P1-P2)/100 + P2).

CCt

Compressor ON time during continuous cycle:

(0.0÷24h00min, res. 10min) allows

to set the length of the continuous cycle. Compressor stays on without interruption

during

CCt

time. This  is  useful,  for  instance,  when  the  room  is  filled  with  new

products.

CCS

Set  point  for  continuous  cycle:

(-100÷150°C; -148÷302°C)  it  sets  the  set  point

used during the continuous cycle.

Con

Compressor  ON  time  with  faulty  probe:

(0÷255min)  time  during  which  the

compressor is active in case of faulty thermostat probe. With

Con=0

compressor is

always OFF.

CoF

Compressor  OFF  time  with  faulty  probe:

(0÷255min)  time  during  which  the

compressor  is OFF in case of faulty thermostat probe. With

CoF=0

compressor is

always active.

CH

Type of action:

(CL, Ht)

CL

= cooling;

Ht

= heating.

DISPLAY

CF

Temperature measurement unit:

(°C; °F)

°C

= Celsius;

°F

= Fahrenheit.

WARNING:

When the measurement unit is changed the SET point and the values of

the parameters

HY

,

LS

,

US

,

ot

,

ALU

and

ALL

have to be checked and modified (if

necessary).

rES

Resolution (for °C):

(in=1°C; dE=0.1°C) allows decimal point display.

dLY

Display delay:

(0.0÷20min00s; res. 10s) when the temperature increases, the display

is updated of 1°C or 1°F after this time.

DEFROST

idF

Interval  between  defrost  cycles:

(0÷120hours) determines  the  interval  of  time

between two defrost cycles.

MdF

(Maximum) length for defrost:

(0÷255min)

When

P2P=n

, (not evaporator probe: timed defrost) it sets the defrost duration.

When

P2P=Y

(defrost  end  based  on  temperature)  it  sets  the  maximum  length  for

defrost.

dFd

Temperature displayed during defrost:

(rt; it; SEt; dEF)

rt

= real temperature;

it

= temperature at defrost start;

SEt

= set point;

dEF

= “

dEF

” label.

dAd

MAX display delay after defrost:

(0÷255min) sets the maximum time between the

end of defrost and the restarting of the real room temperature display.

ALARMS

ALC

Temperature  alarms  configuration:

(Ab;  rE)

Ab

=  absolute  temperature, alarm

temperature is given by the ALL or ALU values.

rE

= temperature alarms are referred

to  the  set  point. Temperature alarm is enabled when the temperature exceeds the

[

SET+ALU

] or [

SET-ALL

] values.

ALU

MAXIMUM temperature alarm:

ALC=Ab:

(SET÷150°C; SET÷302°F)

ALC=rE:

(0.1÷50°C; 1÷90°F)

When this temperature is reached, the alarm is enabled, possibly the

ALd

delay time.

ALL

Minimum temperature alarm:

ALC=Ab:

(-100.0 ÷ SET°C; -148÷302°F)

ALC=rE:

(0.1÷50°C; 1÷90°F)

When this temperature is reached, the alarm is enabled, possibly the

ALd

delay time.

AFH

Differential  for  temperature  alarm  recovery:

(0.1÷25.5°C;  1÷45°F) intervention

differential for recovery of temperature alarm.

ALd

Temperature  alarm  delay:

(0÷255  min)  time  interval  between  the detection of an

alarm condition and alarm signalling.

dAo

Exclusion  of  temperature  alarm  at  start-up:

(0.0÷23h 50min,  res.  10min)  time

interval  between  the  detection  of  the  temperature  alarm  condition  after  instrument

power on and alarm signalling.

ALARM RELAY MANAGEMENT – ONLY FOR BATTERY-BACKUP MODELS (7020122-01)

tbA

Alarm relay silencing (with oA1=ALr):

(n, Y)

n

= silencing disabled; alarm relay stays on till alarm condition lasts.

Y

= silencing enabled; alarm relay is switched OFF by pressing a key during an alarm.

Aro

Alarm relay activation with power failure:

(n, Y)

n

= the alarm relay is never activated during a power failure.

Y

= the alarm relay is activated during a power failure.

ALF

Alarm relay activation for all the alarms:

(n, Y)

n

=  the  alarm  relay is activated only in case of a temperature alarm or regulation

probe failure.

Y

= the alarm relay is activated for all the alarms.

Summary of Contents for Dixell XR30CX-4S1C1

Page 1: ...estriction of the use of certain hazardous substances in electrical and electronic equipment RoHS directive This drawing is the property of A S Vestfrost and must not be copied passed on to or otherwise used by any person without the express consent of A S Vestfrost Date Last modification Init Denne vare er specificeret ved nedenstående datablad Med forudgående skriftlig tilladelse fra Vestfrost k...

Page 2: ...the digital input can operate as third temperature probe The battery backup version is also provided with an input for external battery It is used to supply the controller in case of main voltage failure By using the HOT KEY input output port is possible to upload a new parameter map from program the controller or save the actual parameter map to an external memory device named HOTKEY memory Moreo...

Page 3: ...0 1 25 5 C 1 255 F intervention differential for set point Compressor Cut IN is Set Point differential HY Compressor Cut OUT is when the temperature reaches the set point LS Minimum set point 100 C SET 148 F SET it sets the minimum value for the set point US Maximum set point SET 150 C SET 302 F it sets the maximum value for set point ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to...

Page 4: ...ing function allows to change the set point value as the result of the SET HES parameter sum This function is enabled until the digital input is activated 8 8 DIGITAL INPUTS POLARITY The digital input polarity depends on the i1P parameter i1P CL the input is activated by closing the contact i1P OP the input is activated by opening the contact 9 TTL SERIAL LINE FOR MONITORING SYSTEMS It is possible...

Page 5: ... 60 Pr2 CoF Compressor OFF time with faulty probe 0 255 min 5 5 Pr2 CH Kind of action CL cooling Ht heating CL CL Pr2 CF Temperature measurement unit C F C C Pr2 rES Resolution in integer dE dec point in in Pr2 dLY Display temperature delay 0 20min 00s res 10s 0 0 0 0 Pr2 idF Interval between defrost cycles 1 120 hours 0 0 Pr1 MdF Maximum length for defrost 0 255 min 0 0 Pr1 dFd Displaying during ...

Reviews: