1592023130 XM670K_XM679K GB r4.2 26.06.2017.docx 

XM670K - XM679K  

          1/10 

 

CONTROLLERS FOR MULTIPLEXED CABINETS 

XM670K- XM679K 

-MANUAL FOR THE SW REL. 4.2- 

 

1.

 

GENERAL WARNING 

1.1

 

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 

reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot 

be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring 

the same and unchanged functionality. 

1.2

 

 SAF

E

TY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits  avoiding 

sudden temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell 

S.r.l.

” 

(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 

each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel 

with inductive loads could be useful. 

2.

 

BEFORE PROCEEDING 

2.1

 

CHECK THE SW REL. OF THE XM679K 

1.

 

Look at the SW rel. of XM679K printed on the label of the controller. 

 

2.

 

If  the SW release is 4.2 proceed with this manual otherwise contact Dixell to get the right manual. 

3.

 

GENERAL DESCRIPTION 

The 

XM670K/XM679K

 are high level microprocessor based controllers for multiplexed cabinets suitable 

for applications on medium or low temperature. It can be inserted in a LAN of up to 8 different sections 

which can operate, depending on the programming, as stand alone controllers or following the commands 

coming from the other sections. The 

XM670K/XM679K

 are provided with 6 relay outputs to control the 

solenoid valve, defrost - which can be either electrical or hot gas  - the evaporator fans, the lights, an 

auxiliary output and an alarm output and with one output to drive 

pulsed electronic expansion valves 

(

only XM679K

). The devices are also provided with four probe inputs, one for temperature control, one 

to control the defrost end temperature of the evaporator, the third for the display and the fourth can be 

used for application with virtual probe or for inlet/outlet air temperature measurement. The model 

XM679K

 

is provided by other two probes that have to be used for superheat measurement and regulation. Finally, 

the 

XM670K/XM679K

  are  equipped  with  the  three  digital  inputs  (free  contact)  fully  configurable  by 

parameters. 

The instruments are equipped with the HOTKEY connector that permits to be programmed in a simple 

way. Direct serial output 

RS485

 

ModBUS-RTU 

compatible permits a simple XWEB interfacing. 

RTC

  are 

available as options. The HOTKEY connector can be used to connect 

X-REP

 display (Depending on the 

model). 

4.

 

INSTALLATION AND MOUNTING 

This device can operate without any user interface, but normal application is with Dixell CX660 keyboard. 

 

 

 

Figure 1a 

 

 

 

Figure 1b 

The 

CX660  keyboard 

shall  be 

mounted on vertical panel, in a 29x71 

mm  hole,  and  fixed  using  the  special 

bracket supplied as shown in fig. 1a/1b. 

The  temperature  range  allowed  for 

correct  operation  is  0  to  60°C.  Avoid 

places  subject  to  strong  vibrations, 

corrosive  gases,  excessive  dirt  or 

humidity. 

The  same  recommendations  apply  to 

probes. Let air circulate by the cooling 

holes. 

 

 

Figure 1c 

 

5.

 

WIRING DIAGRAM AND CONNECTIONS 

5.1

 

IMPORTANT NOTE 

XM

 device is provided with disconnectable terminal block to connect cables with a cross section up to 1.6 mm

for 

all the low voltage connection: the RS485, the LAN, the probes, the digital inputs and the keyboard. Other inputs, 

power supply and relay connections are provided with screw terminal block or fast-on connection (5.0 mm). Heat-

resistant cables have to be used.  

Before connecting cables make sure the power supply complies with the instrument’s requirements. Separate the 

probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the 

maximum current allowed on each relay, in case of heavier loads use a suitable external relay. 

N.B.

 Maximum 

current allowed for all the loads is 16A. The probes shall be mounted with the bulb upwards to prevent damages 

due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly 

measure the average room temperature. Place the defrost termination probe among the evaporator fins in the 

coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent 

premature defrost termination. 

 

5.2

 

XM670K 

 ALL POWER SUPPLY 

 

 

 

5.3

 

XM679K 

 230VAC VALVES 

 

5.4

 

XM679K 

 24VAC VALVES 

 

NOTE: the jumper indicated as JMP is inside the case of the controller. This jumper 

has to be closed only in case of driving 24Vac valve. 

5.5

 

KEYBOARD DISPLAY CX660 

 

 

 

The 

XM670/679K 

board can operate also without keyboard. 

Polarity:

 

Terminal [

34

] [-] 

Terminal [

35

] [+] 

 

Use twisted shielded cable 

AWG 18 or less in case of long 

distance.  

Max distance: 

30m

 

 

5.6

 

SYNCHRONIZED DEFROST 

 MAXIMUM 8 SECTIONS 

Follow next steps to create a LAN connection, which is a necessary condition to perform synchronized defrost 

(also called master-slave functioning): 

 

1)   connect a shielded cable between terminals [

38

] [-] and [

39

] [+] for a 

maximum of 8 sections

2)   the 

Adr

 parameter is the number to identify each electronic board. 

Address duplication is not permitted

in this case the synchronized defrost and the communication with monitoring system is not guaranteed (the 

Adr

 is also the ModBUS address). For example, a correct configuration is the following: 

 

 

 

If the LAN is well connected, the green LED will be ON. If the green LED blinks then the connection is 

wrongly configured.  

 

The max distance allowed is 30m 

Summary of Contents for Dixell XM670K

Page 1: ...nstruments are equipped with the HOTKEY connector that permits to be programmed in a simple way Direct serial output RS485 ModBUS RTU compatible permits a simple XWEB interfacing RTC are available as options The HOTKEY connector can be used to connect X REP display Depending on the model 4 INSTALLATION AND MOUNTING This device can operate without any user interface but normal application is with D...

Page 2: ... to 10Vdc Use CABCJ15 to perform the connections It s located near the terminal 39 on a 2 pin connector It s possible to use the output to control anti sweat heaters through a chopped phase controller XRPW500 500watt or family XV D or XV K 6 QUICK REFERENCE GUIDE HOW TO RUN THE SELF ADAPTIVE REGULATION IN 4 STEPS 1 After wiring the XM679K set the proper gas via Fty parameter Pre set gas is R404A 2...

Page 3: ...c set point if the functions are enabled Exit Pressed together or wait the timeout of about 60 sec 10 MENU FOR MULTIMASTER FUNCTION SEC The function section SEC is enabled when icon is lit It allows entering in the remote programming mode from a keyboard not physically connected to the board through the LAN functionality Action Button or display Notes Enter menu Press UP arrow for about 3 sec the ...

Page 4: ...of regulation parameter SFd percentage and SFd time Forced opening of the valve after defrost parameter oPd percentage and Pdd time 12 4 MINIMUM STABLE SUPERHEAT SEARCH AMS YES ATU YES With the parameter ATU the minimum stable superheat search function is enabled With ATU yES controllers start searching the mimimum stable value for the SH the minimum admitted value in any case is LSH 2 C 4 F Pleas...

Page 5: ...ing to LMd parameter Selecting dPA and dPb probes and by changing the dtP and ddP parameters the defrost can be started when the difference between dPA and dPb probes is lower than dtP for all ddP time This is useful to start defrost when a low thermal exchange is detected If ddP 0 this function is disabled Defrost ending When defrost is started via rtc the maximum duration of defrost is obtained ...

Page 6: ...pressure exceeds maximum operating pressure value instrument signals situation with MOP alarm related to PrM parameter LOP Lowest Operating Pressure threshold PA4 P20 bar psi kPA 10 if the suction pressure comes down to this value a low pressure alarm is signalled with LOP alarm related to PrM parameter dML delta MOP LOP 0 100 when a MOP alarm occurs valve will close of the dML percentage every cy...

Page 7: ...ion dor door open dEF defrost activation AUS auxiliary activation LiG light activation OnF switch on off the instrument Htr change type of action FHU not used ES activate energy saving Hdy activate holiday function d3d Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when i3F PAL If i3F EAL or bAL external alarms d3d para...

Page 8: ... for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 18 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KEY 1 When the XM unit is ON insert the Hot key and push UP key 2 The UPLOAD begins the uPL message is blinking 3 Remove the Hot Key At the end of the data transfer phase the instrument displays the foll...

Page 9: ...5 F Fod 0 Pr1 Fan activation time after defrost without compressor 0 255 min Fon 0 Pr1 Fan ON time 0 15 min FoF 0 Pr1 Fan OFF time 0 15 min trA UAL Pr2 Kind of regulation for modulating output UAL 0 rEG 1 AC 2 SOA 80 Pr2 Fixed speed for fan AMi AMA SdP 30 0 Pr2 Default Dew Point value 55 0 C 50 0 C 67 F 122 F ASr 1 0 Pr2 Differential for fan offset for anti sweat heater 25 5 C 25 5 C 45 F 45 F PbA...

Page 10: ...ving ESP P1 Pr1 Energy saving probe selection nP 0 P1 1 P2 2 P3 3 P4 4 P5 5 tEr 6 HES 0 0 Pr1 Temperature increasing during Energy Saving 30 0 C 30 0 C 54 F 54 F PEL n Pr1 Energy saving activation when Light switched off n 0 Y 1 L A N Management LMd y Pr2 Defrost Synchronisation n 0 Y 1 dEM y Pr2 Defrost end Synchronisation n 0 Y 1 LSP n Pr2 SET POINT Synchronisation n 0 Y 1 LdS n Pr2 Display Sync...

Reviews: