1592009130 XW570L GB r1.0 03.08.2015
XW570L
5/5
14.
TECHNICAL DATA
Housing:
self extinguishing ABS.
Case:
facia 38x185 mm; depth 76mm
Mounting :
panel mounting in a 150x31 mm panel cut-out with two screws.
3 x 2mm.
Distance between the holes 165mm
Protection:
IP20.
Frontal protection:
IP65 with frontal gasket mod RG-L. (optional)
Connections:
Screw terminal block
2,5 mm
2
heat-resistant wiring and 6,3mm Faston
Optional
disconnectable terminal blocks (
max.12A
)
Power supply:
230Vac or. 110Vac
10%
Power absorption:
7VA max.
Display
: 3 digits, red LED, 14,2 mm high.
Inputs
: 3 NTC probes
Digital inputs
: 2 free voltage
Relay outputs:
Total current on loads MAX. 20A
compressor:
relay SPST 20(8) A, 250Vac
light:
relay SPST 16(3) A, 250Vac (or
optional
relay SPST 16(3) A, special for fluorescent lights)
fans:
relay SPST 8(3) A, 250Vac
defrost:
relay SPST 8(3) A, 250Vac
alarm:
SPST relay 8(3) A, 250Vac
auxiliary:
SPST relay 16(3) A, 250Vac
Other output :
Alarm buzzer
(Standard)
Analogue output
4÷20 mA (optional)
Direct
RS485
(optional)
14.1.1.1
XW-REP
output for remote display (optional)
Serial output :
TTL standard
Communication protocol:
Modbus - RTU
Data storing
: on the non-volatile memory (EEPROM).
Internal clock back-up:
24 hours
Kind of action:
1B.
Pollution grade:
normal
Software class:
A.
Operating temperature:
0÷60 °C.
Storage temperature:
-25÷60 °C.
Relative humidity:
20
85% (no condensing)
Measuring and regulation range: NTC probe:
-40÷110°C (-58÷230°F)
Resolution:
0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C)
: ±0,5 °C ±1 digit
15.
CONNECTIONS
15.1
XW570L
16.
DEFAULT SETTING VALUES
Label Name
Range
Default
Level
REGULATION
°C/°F XW570L
Set
Set point
LS÷US
-5/23
Pr1
Hy
Differential
0,1÷25,5 °C / 1÷45°F
2/4
Pr1
LS
Minimum set point
-50,0°C÷SET / -58°F÷SET
-30/-22
Pr2
US
Maximum set point
SET ÷ 110°C / SET ÷ 230°F
20/68
Pr2
OdS Outputs activation delay at start up
0÷255 min.
1
Pr2
AC
Anti-short cycle delay
0÷30 min.
1
Pr1
CCt Compressor ON time during fast freezing
0 ÷ 23h 50 min.
0
Pr2
COn Compressor ON time with faulty probe
0÷255 min.
15
Pr2
COF Compressor OFF time with faulty probe
0÷255 min.
30
Pr2
DISPLAY
CF
Temperature measurement unit
°C ÷ °F
°C/°F
Pr2
rES
Resolution (integer/decimal point)
in ÷ de
de
Pr1
Lod
Local display
P1 ÷ 1r2
P1
Pr2
Red Remote display
P1 ÷ 1r2
p1
Pr2
DEFROST
tdF
Defrost type
rE, rT, in
rE
Pr1
EdF Defrost mode
rtc, In, Sd
In
Pr2
SdF Set point for SMART DEFROST
-30 ÷ +30°C / -22÷+86°F
0
Pr2
dtE
Defrost
termination
temperature
(1°Evaporator)
-50,0÷110°C /-58÷230°F
8/46
Pr1
IdF
Interval between defrost cycles
1÷120h
6
Pr1
MdF (Maximum) length for 1° defrost
0÷255 min.
30
Pr1
dFd Displaying during defrost
rt, it, SEt, dEF, dEG
it
Pr2
dAd MAX display delay after defrost
0÷255 min.
30
Pr2
Fdt
Draining time
0÷60 min.
0
Pr2
dPO First defrost after start up
n ÷ y
n
Pr2
dAF Defrost delay after fast freezing
0 ÷ 23h 50 min.
2
Pr2
FANS
FnC Fans operating mode
C-n, C-y, O-n, O-y
O-n
Pr2
Fnd Fans delay after defrost
0÷255 min.
10
Pr2
Label Name
Range
Default
Level
FSt
Fans stop temperature
-50,0÷110°C / -58÷230°F
2/35
Pr2
ALARMS
ALC Temperature alarms configuration
rE÷Ab
rE
Pr2
ALU MAXIMUM temperature alarm
-50,0÷110°C/-58÷230°F
10/20
Pr1
ALL minimum temperature alarm
-50,0÷110°C/ -58÷230°F
10/20
Pr1
AFH Temperature alarm and fan differential
0,1÷25,5 °C/ 1÷45°F
2/4
ALd Temperature alarm delay
0÷255 min.
15
Pr2
dAO Delay of temperature alarm at start up
0 ÷ 23h 50 min.
1,3
Pr2
EdA Alarm delay at the end of defrost
0÷255 min.
30
Pr2
dot
Delay of temperature alarm after closing the
door
0÷255 min.
15
Pr2
dOA Open door alarm delay
0÷254 min.,nu
15
Pr2
tBA
Alarm relay silencing
y ÷ n
y
Pr2
nPS Pressure switch activation number
0÷15
0
Pr2
ANALOGUE OUTPUT
4÷20mA (Optional)
AOS Analogue output start point
-50,0÷110°C / -58÷230°F
0/32
Pr2
APb Analogue output band width
-50,0÷110°C / -58÷230°F
0
Pr2
CAO Input type for the analogue output
P1÷1r2
P1
Pr2
ANALOGUE INPUTS
Ot
Thermostat probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr1
OE
Evaporator probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
O3
Auxiliary probe calibration
-12,0÷12,0°C / -21÷21°F
0
Pr2
P2P Evaporator probe presence
n ÷ y
y
Pr2
P3P Auxiliary probe presence
n ÷ y
n
Pr2
HES Temperature increase during the Energy
Saving cycle
-30÷30°C / -54÷54°F
0
Pr2
DIGITAL INPUTS
Odc Open door control
no, Fan, CPr, F_C
Fan
Pr2
I1P
Door switch polarity
CL÷OP
CL
Pr2
I2P
Configurable digital input polarity
CL÷OP
CL
Pr2
i2F
Digital input configuration
EAL, bAL, PAL,
dFr, AUS, ES, OnF
EAL
Pr2
dId
Digital input alarm delay
0÷255 min.
5
Pr2
TIME AND WEEKLY HOLIDAYS
°C/°F XW570L
Hur
Current hour
0 ÷ 23
0
Pr2
Min
Current minute
0 ÷ 59
0
Pr2
dAY Current day
Sun ÷ SAt
Sun
Pr2
Hd1 First weekly holiday
Sun÷ SAt – nu
nu
Pr2
Hd2 Second weekly holiday
Sun÷ SAt – nu
nu
Pr2
Hd3 Third weekly holiday
Sun÷ SAt – nu
nu
Pr2
ENERGY SAVING TIMES
ILE
Energy Saving cycle start during workdays
0 ÷ 23h 50 min.
0
Pr2
dLE Energy Saving cycle length during workdays
0 ÷ 24h 00 min.
0
Pr2
ISE
Energy Saving cycle start on holidays
0 ÷ 23h 50 min.
0
Pr2
dSE Energy Saving cycle length on holidays
0 ÷ 24h 00 min.
0
Pr2
HES Temperature increase during the Energy
Saving cycle
-30÷30°C / -54÷54°F
0
Pr2
DEFROST TIMES
Ld1
1
st
workdays defrost start
0 ÷ 23h 50 min. - nu
6.0
Pr2
Ld2
2
nd
workdays defrost start
0 ÷ 23h 50 min. - nu
13.0
Pr2
Ld3
3
rd
workdays defrost start
0 ÷ 23h 50 min. - nu
21.0
Pr2
Ld4
4
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld5
5
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld6
6
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld7
7
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Ld8
8
th
workdays defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd1 1
st
holiday defrost start
0 ÷ 23h 50 min. - nu
6.0
Pr2
Sd2 2
nd
holiday defrost start
0 ÷ 23h 50 min. - nu
13.0
Pr2
Sd3 3
rd
holiday defrost start
0 ÷ 23h 50 min. - nu
21.0
Pr2
Sd4 4
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd5 5
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd6 6
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd7 7
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
Sd8 8
th
holiday defrost start
0 ÷ 23h 50 min. - nu
nu
Pr2
OTHER
Adr
Serial address
0÷247
1
Pr1
rEL
Software release
- - -
- - -
Pr2
Ptb
Map code
- - -
- - -
Pr2
Prd
Probes display
Pb1÷Pb3
- - -
Pr2
Pr2 Access parameter list
- - -
- - -
Pr2