background image

 

 

1592009130 XW570L GB r1.0 03.08.2015                      

     XW570L 

5/5 

14.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: 

facia 38x185 mm; depth 76mm 

Mounting :

  

panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

Distance between the holes 165mm 

Protection: 

IP20.

 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

 

Optional

 disconnectable terminal blocks (

max.12A

Power supply: 

230Vac or. 110Vac 

 10% 

 

Power absorption: 

7VA max.

 

Display

: 3 digits, red LED, 14,2 mm high.  

Inputs

: 3 NTC probes 

Digital inputs

: 2 free voltage 

Relay outputs: 

Total current on loads MAX. 20A

 

compressor:

 relay SPST 20(8) A, 250Vac  

light: 

relay SPST 16(3) A, 250Vac (or 

optional

 relay SPST 16(3) A, special for fluorescent lights) 

fans:

 relay SPST 8(3) A, 250Vac

 

defrost:

 relay SPST 8(3) A, 250Vac  

alarm: 

SPST relay 8(3) A, 250Vac 

auxiliary:

 SPST relay 16(3) A, 250Vac 

Other output : 

 

Alarm buzzer

 (Standard) 

 

Analogue output

 4÷20 mA (optional) 

 

Direct

 RS485 

(optional)

 

14.1.1.1

 

 

XW-REP 

output for remote display (optional)

 

Serial output :

 TTL standard  

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Internal clock back-up:

 24 hours 

Kind of action: 

1B. 

Pollution grade: 

normal 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

 
  

15.

 

CONNECTIONS 

15.1

 

XW570L 

 

 

 

 

16.

 

DEFAULT SETTING VALUES 

 

Label  Name 

  Range 

Default 

Level

 

 

REGULATION 

 

°C/°F  XW570L 

Set 

Set point 

LS÷US 

-5/23 

Pr1 

Hy 

Differential 

0,1÷25,5 °C / 1÷45°F 

2/4 

Pr1 

LS 

Minimum set point 

 -50,0°C÷SET / -58°F÷SET 

-30/-22 

Pr2 

US 

Maximum set point 

SET ÷ 110°C / SET ÷ 230°F 

20/68 

Pr2 

OdS  Outputs activation delay at start up 

0÷255 min. 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

CCt  Compressor ON time during fast freezing 

0 ÷ 23h 50 min. 

Pr2 

COn  Compressor ON time with faulty probe 

0÷255 min. 

15 

Pr2 

COF  Compressor OFF time with faulty probe 

0÷255 min. 

30 

Pr2 

 

DISPLAY 

 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C/°F 

Pr2 

rES 

Resolution (integer/decimal point) 

in ÷ de 

de 

Pr1 

Lod 

Local display  

P1 ÷ 1r2 

P1 

Pr2 

Red  Remote display  

P1 ÷ 1r2 

p1 

Pr2 

 

DEFROST 

 

 

 

tdF 

Defrost type 

rE,  rT,  in  

rE 

Pr1 

EdF  Defrost mode 

rtc, In, Sd 

In 

Pr2 

SdF  Set point for SMART DEFROST 

-30 ÷ +30°C / -22÷+86°F 

Pr2 

dtE 

Defrost 

termination 

temperature 

(1°Evaporator) 

-50,0÷110°C /-58÷230°F 

8/46 

Pr1 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF  (Maximum) length for 1° defrost 

0÷255 min. 

30 

Pr1 

dFd  Displaying during defrost 

rt, it, SEt, dEF, dEG 

it 

Pr2 

dAd  MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

Fdt 

Draining time 

0÷60 min. 

Pr2 

dPO  First defrost after start up 

n ÷ y 

Pr2 

dAF  Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

Pr2 

 

FANS 

 

 

 

FnC  Fans operating mode 

C-n, C-y, O-n, O-y  

O-n 

Pr2 

Fnd  Fans delay after defrost 

0÷255 min. 

10 

Pr2 

Label  Name 

  Range 

Default 

Level

 

FSt 

Fans stop temperature 

-50,0÷110°C /  -58÷230°F 

2/35 

Pr2 

 

ALARMS 

 

 

 

ALC  Temperature alarms configuration 

rE÷Ab 

rE 

Pr2 

ALU  MAXIMUM temperature alarm 

-50,0÷110°C/-58÷230°F 

10/20 

Pr1 

ALL  minimum temperature alarm 

-50,0÷110°C/ -58÷230°F 

10/20 

Pr1 

AFH  Temperature alarm and fan differential 

0,1÷25,5 °C/ 1÷45°F 

2/4 

 

ALd  Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO  Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 

Pr2 

EdA  Alarm delay at the end of defrost  

0÷255 min. 

30 

Pr2 

dot 

Delay  of  temperature  alarm  after  closing  the 
door  

0÷255 min. 

15 

Pr2 

dOA  Open door alarm delay  

0÷254 min.,nu 

15 

Pr2 

tBA 

Alarm relay silencing 

y ÷ n 

Pr2 

nPS  Pressure switch activation number 

0÷15 

Pr2 

 

ANALOGUE OUTPUT  
4÷20mA (Optional)

 

 

 

 

AOS  Analogue output start point 

-50,0÷110°C / -58÷230°F 

0/32 

Pr2 

APb  Analogue output band width 

-50,0÷110°C / -58÷230°F 

Pr2 

CAO  Input type for the analogue output 

P1÷1r2 

P1 

Pr2 

 

ANALOGUE INPUTS 

 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr1 

OE 

Evaporator probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr2 

O3 

Auxiliary probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr2 

P2P  Evaporator probe presence 

n ÷ y 

Pr2 

P3P  Auxiliary probe presence 

n ÷ y 

Pr2 

HES  Temperature  increase  during  the  Energy 

Saving cycle  

-30÷30°C / -54÷54°F 

Pr2 

 

DIGITAL INPUTS 

 

 

 

Odc  Open door control  

no, Fan, CPr, F_C 

Fan 

Pr2 

I1P 

Door switch polarity 

CL÷OP 

CL 

Pr2 

I2P 

Configurable digital input polarity 

CL÷OP 

CL 

Pr2 

i2F 

Digital input configuration 

EAL, bAL, PAL, 

dFr, AUS, ES, OnF 

EAL 

Pr2 

dId 

Digital input alarm delay 

0÷255 min. 

Pr2 

 

TIME AND WEEKLY HOLIDAYS

 

 

°C/°F  XW570L 

Hur 

Current hour 

0 ÷ 23 

Pr2 

Min 

Current minute 

0 ÷ 59 

Pr2 

dAY  Current day 

Sun ÷ SAt 

Sun 

Pr2 

Hd1  First weekly holiday 

Sun÷ SAt – nu 

nu 

Pr2 

Hd2  Second weekly holiday 

Sun÷ SAt – nu 

nu 

Pr2 

Hd3  Third weekly holiday 

Sun÷ SAt – nu 

nu 

Pr2 

 

ENERGY SAVING TIMES 

 

 

 

ILE 

Energy Saving cycle start during workdays 

0 ÷ 23h 50 min. 

Pr2 

dLE  Energy Saving cycle length during workdays 

0 ÷ 24h 00 min. 

Pr2 

ISE 

Energy Saving cycle start on holidays 

0 ÷ 23h 50 min. 

Pr2 

dSE  Energy Saving cycle length on holidays 

0 ÷ 24h 00 min. 

Pr2 

HES  Temperature  increase  during  the  Energy 

Saving cycle 

-30÷30°C / -54÷54°F 

Pr2 

 

DEFROST TIMES 

 

 

 

Ld1 

1

st

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Ld2 

2

nd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Ld3 

3

rd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Ld4 

4

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld5 

5

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld6 

6

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld7 

7

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld8 

8

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd1  1

st

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Sd2  2

nd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Sd3  3

rd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Sd4  4

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd5  5

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd6  6

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd7  7

th

 holiday defrost start 

0 ÷ 23h 50  min. - nu 

nu 

Pr2 

Sd8  8

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

 

OTHER 

 

 

 

Adr 

Serial address 

0÷247 

Pr1 

rEL 

Software release 

- - - 

- - - 

Pr2 

Ptb 

Map code 

- - - 

- - - 

Pr2 

Prd 

Probes display 

Pb1÷Pb3 

- - - 

Pr2 

Pr2   Access parameter list 

- - - 

- - - 

Pr2 

 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Dixell Wing XW570L

Page 1: ...is control by means of parameter EdF Edf rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld8 on workdays and in Sd1 Sd8 in holidays EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temperature is bigger than SdF parameter At the end of defrost the dr...

Page 2: ...tting the current hour minutes day and the weekly holidays up to 3 will be possible 4 To exit press SET UP or wait 15s without pressing any key 5 3 TO SET THE DEFROST TIMES 1 Push the n key for more than 3 seconds 2 eLED switches ON and the current time is displayed 3 By pushing DEF key the DEF led will start flashing and setting defrost time will be possible 4 To exit press SET UP or wait 15s wit...

Page 3: ...AL If I2F EAL or bAL external alarms did parameter defines the time delay between the detection and the successive signalling of the alarm TO SET CURRENT TIME AND WEEKLY HOLIDAYS 3SEC afterward Hur Current hour 0 23 h Min Current minute 0 59min dAY Current day Sun SAt Hd1 First weekly holiday Sun nu Set the first day of the week which follows the holiday times Hd2 Second weekly holiday Sun nu Set ...

Page 4: ...l cable then turn it ON again At the end of the data transfer phase the instrument displays the following messages end for right programming The instrument starts regularly with the new programming err for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 12 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KE...

Page 5: ...perature 50 0 110 C 58 230 F 2 35 Pr2 ALARMS ALC Temperature alarms configuration rE Ab rE Pr2 ALU MAXIMUM temperature alarm 50 0 110 C 58 230 F 10 20 Pr1 ALL minimum temperature alarm 50 0 110 C 58 230 F 10 20 Pr1 AFH Temperature alarm and fan differential 0 1 25 5 C 1 45 F 2 4 ALd Temperature alarm delay 0 255 min 15 Pr2 dAO Delay of temperature alarm at start up 0 23h 50 min 1 3 Pr2 EdA Alarm d...

Reviews: