background image

 

 

1592009130 XW570L GB r1.0 03.08.2015                      

     XW570L 

3/5 

MdF  (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the defrost 

duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length for defrost. 

dFd   Display during defrost:  
 

rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 

dEG

 = “dEG” label;

 

dAd   Defrost  display  time  out:

  (0

255  min)  Sets  the  maximum  time  between  the  end  of  defrost  and  the 

restarting of the real room temperature display. 

Fdt  Drain  down  time:

  (0÷60  min.)  time  interval  between  reaching  defrost  termination  temperature  and  the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that 
might have formed due to defrost.

 

dPO First defrost after start-up:   
 

= Immediately; 

n

 = after the IdF time 

dAF   Defrost delay after fast freezing: 

(0min÷23h 50min)  after a Fast Freezing cycle, the first defrost will be 

delayed for this time. 

FANS 
FnC  Fan operating mode: 

C-n

 = running with the compressor, OFF during the defrost;  

C-y

 = running with the compressor, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd Fan delay after defrost:

 (0÷255 min)

 

The time interval between the defrost end and evaporator fans start.

 

FSt  Fan stop temperature:

 (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe, 

above which the fan is always OFF. 

ALARMS 
ALC  Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU  High temperature alarm setting:

 ( ALC= rE, 0 

 

50°C or 90°F;   ALC= Ab, ALL 

 110°C or 230°F) 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting: (

  ALC = rE , 0 

 50 °C or 90°F; ALC = Ab , - 50°C or -58°F 

 ALU) 

 

when this temperature is reached and after the ALd delay time, the LA alarm is enabled,. 

AFH  Temperature alarm and fan differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for temperature 

alarm set point and fan regulation set point, always positive.

 

ALd  Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and the 

corresponding alarm signalling. 

dAO Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection of the 

temperature alarm condition after the instrument power on and the alarm signalling.

 

EdA  Alarm delay at the end of defrost: 

(0

255 min) Time interval between the detection of the temperature 

alarm condition at the end of defrost and the alarm signalling. 

dot   Delay of temperature alarm after closing the door : 

(0

255 min) Time delay to signal the temperature 

alarm condition after closing the door. 

doA   Open door alarm delay:

(0÷254min,nu) delay between the detection of the open door condition and its 

alarm signalling: the flashing message “

dA

” is displayed. If 

doA=nu

 the door alarm will be not signalled. 

tbA   Buzzer and alarm relay silencing: 

by pushing one of the keypad buttons.

 

 

n

= Only the Buzzer is silenced; 

y

=

 

Buzzer and relay are silenced.

 

nPS   Pressure switch number:

 (0 

15) Number of activation of the pressure switch, during the “

did

” interval, 

before signalling the alarm event (I2F= PAL). 

ANALOGUE OUTPUT 4÷20 mA (OPTIONAL) 
AOS  Analogue output start point: 

(-50÷110°C or -58°÷230°F). Sets the temperature at which the analogue 

output begins. 

APB  Analogue output band width

:

 

(-50÷110°C or -58°÷230°F) sets the width of the regulation band for the 

analogue  output.  If  APb  is 

positive

  then  it  is  above  the  start  point  and  the  kind  of  action  is  direct 

(condenser application). If APb is 

negative

 then it is below the start point and the kind of action is inverse 

(evaporator application).  

CAO  Input type for the analogue output: 

four input types can be selected: 

P1

 = room probe temperature; 

P2

 = evaporator probe temperature; 

P3

 = temperature of the third probe 

1r2

= temperature difference between the room probe and the evaporator probe 

 

PROBE INPUTS 
Ot  Thermostat  probe  calibration: 

(-12.0

12.0°C/  -21

21°F)  allows  to  adjust  possible  offset  of  the 

thermostat probe. 

OE    Evaporator  probe  calibration: 

(-12.0

12.0°C/  -21

21°F)  allows  to  adjust  possible  offsets  of  the 

evaporator probe. 

O3  Auxiliary probe calibration: 

(-12.0

12.0°C/ -21

21°F) allows to adjust possible offsets of the evaporator 

probe. 

P2P  Evaporator probe presence:  

n

= not present: the defrost stops only by time; 

y=

 present: the defrost stops by temperature and time. 

P3P  Auxiliary probe presence: n

= not present; 

y=

 present. 

HES  Temperature increase during the Energy Saving cycle :

 (-30÷30°C / -54÷54°F) sets the increasing 

value of the set point during the Energy Saving cycle.  

 

 

 

DIGITAL INPUTS 
odc  Compressor and fan status when open door:

  

no

 = normal; 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF.  

I1P  Door switch input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact. 

I2P  Configurable digital input polarity:

 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact 

I2F  Digital input operating mode:

 configure the digital input function: 

 

EAL 

= generic alarm; 

bAL 

= serious alarm mode; 

PAL 

= Pressure switch; 

dFr 

= Start defrost; 

 

AUS 

= Relay AUX actuation; 

Es 

= Energy Saving; 

onF 

= remote On/OFF; 

Hdf 

= Holiday function.

 

did   Time  interval/delay  for  digital  input  alarm:

(0

255  min.) Time interval to calculate the number of  the 

pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines 
the time delay between the detection and the successive signalling of the alarm. 

TO SET CURRENT TIME AND WEEKLY HOLIDAYS (3SEC.

 

 

afterward

 

 )

 

Hur 

Current hour 

(0 ÷ 23 h) 

Min 

Current minute

 (0 ÷ 59min) 

dAY 

Current day

 (Sun ÷ SAt) 

Hd1 

First weekly holiday 

(Sun ÷ nu) Set the first day of the week which follows the holiday times. 

Hd2 

Second weekly holiday 

(Sun ÷ nu) Set the second day of the week which follows the holiday times. 

Hd3 

Third weekly holiday 

(Sun ÷ nu) Set the third day of the week which follows the holiday times. 

 
N.B.  

Hd1,Hd2,Hd3 

can be set also as

 “nu” 

value (Not Used).

  

 

TO SET ENERGY SAVING TIMES (3SEC.

 

 

afterward

 

 )

 

ILE 

Energy Saving cycle start during workdays

: (0 ÷ 23h 50 min.) During the Energy Saving cycle the 

set point is increased by the value in HES so that the operation set point is SET + HES.  

dLe 

Energy Saving cycle length during workdays

: (0 ÷ 24h 00 min.) Sets the duration of the Energy 

Saving cycle on workdays.  

ISE 

Energy Saving cycle start on holidays

. (0 ÷ 23h 50 min.) 

dSE 

Energy Saving cycle length on holidays

 (0 ÷ 24h 00 min.) 

HES  Temperature  increase  during  the  Energy  Saving  cycle 

(-30÷30°C  /  -54÷54°F)  sets  the  increasing 

value of the set point during the Energy Saving cycle.  

TO SET DEFROST TIMES (3SEC.

 

 

afterward

 

 )

 

Ld1÷Ld8  Workday  defrost  start

  (0  ÷  23h  50  min.)  These  parameters  set  the  beginning  of  the  eight 

programmable defrost cycles during workdays. Ex. When 

Ld2

 = 12.4 the second defrost starts at 12.40 

during workdays.  

Sd1÷Sd8  Holiday  defrost  start

  (0  ÷  23h  50  min.)  These  parameters  set  the  beginning  of  the  eight 

programmable  defrost  cycles  on  holidays.  Ex.  When 

Sd2

  =  3.4  the  second  defrost  starts  at  3.40  on 

holidays.  

N.B. : 

To disable a defrost cycle set it to “nu”(not used).  

Ex. 

 If

 Ld6

=nu

 ; 

 the sixth defrost cycle is disabled 

OTHER 
Adr   RS485  serial  address 

(1÷247)

Identifies  the  instrument  address  when  connected  to  a  ModBUS 

compatible monitoring system. 

Rel   Release software:

 (read only) Software version of the microprocessor. 

Ptb   Parameter table:

 (read only) it shows the original code of the Dixell parameter map. 

Prd    Probes display: 

(read only) display the temperature values of the evaporator probe Pb2 and the auxiliary 

probe Pb3. 

Pr2   Access to the protected parameter list 

(read only). 

7.

 

DIGITAL INPUTS 

The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the 
second is programmable in seven different configurations by the “

I2F

” parameter. 

7.1

 

DOOR SWITCH INPUT  

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

dOA

”, the alarm output is enabled and the 

display shows the message “

dA

”. The alarm stops as soon as the external digital input is disabled again. During 

this time and then for the delay “

dot

” after closing the door, the high and low temperature alarms are disabled. 

7.2

 

CONFIGURABLE INPUT - GENERIC ALARM (EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the “

EAL

” alarm 

message. The outputs status don’t change. The alarm stops just after the digital input is de-activated. 

7.3

 

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

BAL

” alarm message. 

The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. 

7.4

 

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of activation of  

the “

nPS

” parameter, the “

PAL

” pressure alarm message will be displayed. The compressor and the regulation 

are stopped. When the digital input is ON the compressor is always OFF. 

7.5

 

CONFIGURABLE INPUT - START DEFROST (DFR) 

It  executes  a  defrost  if  there  are  the  right  conditions.  After  the  defrost  is  finished,  the  normal  regulation  will 
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired. 

7.6

 

CONFIGURABLE INPUT - RELAY AUX ACTUATION (AUS) 

This function allows to turn ON and OFF the auxiliary relay by using the digital input as external switch. 

7.7

 

CONFIGURABLE INPUT - ENERGY SAVING (ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES (parameter) 
sum. This function is enabled until the digital input is activated. 

7.8

 

CONFIGURABLE INPUT -  REMOTE ON/OFF (ONF) 

This function allows to switch ON and OFF the instrument. 

7.9

 

CONFIGURABLE INPUT -  HOLIDAY FUNCTION (HDF) 

In Holiday function Energy saving and defrost cycles follow holiday times. 

(Sd1…Sd8)

 

7.10

 

DIGITAL INPUTS POLARITY  

The digital inputs polarity depends on “

I1P

” and “

I2P

” parameters. 

 

CL

 : the digital input is activated by closing the contact.

 

 

OP

 : the digital input is activated by opening the contact 

8.

 

ANALOGUE OUTPUT 4÷20 MA (OPTIONAL) 

The  analogue  output  is  obtained  through  a  4

20mA  signal  proportional  to  the  input  selected  in  parameter 

CAO

”. Through the analogue output the speed of fans can be regulated according to the input variable. 

The following input types can be selected through the “

CAO

” parameter: 

 

CAO

” = 

P1

  

room temperature 

 

CAO

” = 

P2

  

evaporator temperature 

 

CAO

” = 

P3

  

third probe temperature 

 

CAO

” = 

1r2

 

room temperature - evaporator temperature 

 
To adjust the analogue output the following parameters are available: 
 

AOS

” = Start point for analogue output  

APb

” = Band width for analogue output can be either positive (direct action) and negative  

(inverse action). 

 
Named T the input, the relationship input-output is given by the following charts  
 

Summary of Contents for Dixell Wing XW570L

Page 1: ...is control by means of parameter EdF Edf rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld8 on workdays and in Sd1 Sd8 in holidays EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temperature is bigger than SdF parameter At the end of defrost the dr...

Page 2: ...tting the current hour minutes day and the weekly holidays up to 3 will be possible 4 To exit press SET UP or wait 15s without pressing any key 5 3 TO SET THE DEFROST TIMES 1 Push the n key for more than 3 seconds 2 eLED switches ON and the current time is displayed 3 By pushing DEF key the DEF led will start flashing and setting defrost time will be possible 4 To exit press SET UP or wait 15s wit...

Page 3: ...AL If I2F EAL or bAL external alarms did parameter defines the time delay between the detection and the successive signalling of the alarm TO SET CURRENT TIME AND WEEKLY HOLIDAYS 3SEC afterward Hur Current hour 0 23 h Min Current minute 0 59min dAY Current day Sun SAt Hd1 First weekly holiday Sun nu Set the first day of the week which follows the holiday times Hd2 Second weekly holiday Sun nu Set ...

Page 4: ...l cable then turn it ON again At the end of the data transfer phase the instrument displays the following messages end for right programming The instrument starts regularly with the new programming err for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation 12 2 UPLOAD FROM THE INSTRUMENT TO THE HOT KE...

Page 5: ...perature 50 0 110 C 58 230 F 2 35 Pr2 ALARMS ALC Temperature alarms configuration rE Ab rE Pr2 ALU MAXIMUM temperature alarm 50 0 110 C 58 230 F 10 20 Pr1 ALL minimum temperature alarm 50 0 110 C 58 230 F 10 20 Pr1 AFH Temperature alarm and fan differential 0 1 25 5 C 1 45 F 2 4 ALd Temperature alarm delay 0 255 min 15 Pr2 dAO Delay of temperature alarm at start up 0 23h 50 min 1 3 Pr2 EdA Alarm d...

Reviews: