background image

 

1592009630 XW570K GB  r1.0 04.08.2015 

XW570K 

2/6 

4.3

 

HOW TO SEE THE MAX TEMPERATURE 

 

1.  

Press and release the 

o

 key. 

2.  

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

By pressing the 

o

 key or waiting for 5s the normal display will be restored. 

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 
1.

 

Press SET key until “rST” label starts blinking. 

 

N.B. After the installation RESET the temperature stored .

 

4.5

 

HOW TO SEE AND MODIFY THE SET POINT 

 

 

1. 

Push and immediately release the 

SET 

key: the display will show the Set point value; 

2. 

The SET LED start blinking; 

3. 

To change the Set value push the 

or

 n

 arrows within 10s. 

4. 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

4.6

 

TO START A MANUAL DEFROST  

 

 
1. 

Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

4.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 
 

 

 
1.  Enter  the  Programming  mode  by  pressing  the  Set  and  DOWN  key  for  few  seconds 

(

 and 

 start blinking). 

 
2. 

The instrument will show the first parameter present in “Pr1” 

 
 
 
 

4.8

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “

Pr2

”: 

1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the “

SET

” key.  

3.

 

The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero. 

4.

 

Use 

or

 n

 to input the security code in the flashing digit; confirm the figure by pressing “

SET

”. The 

security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing “

SET

” on the last digit. 

 
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys 
within 30 seconds. 
 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

“SET”

 + 

n

. When a 

parameter is present in “Pr1” LED 

 is on. 

4.9

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

or

 n

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

or

 n

 to change its value.  

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

4.10

 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

and

 n

 keys pressed together for more than 3 s the 

and

 

n

 keys. 

2.  

The  “POF”  message  will  be  displayed  and  the  keyboard  is  locked.  At  this  point  it  is  only 
possible the viewing of the set point or the MAX o Min temperature stored and to switch ON 
and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

and

 n

 keys pressed together for more than 3s. 

 

4.11

 

ON/OFF FUNCTION 

 

 

By  pushing  the 

ON/OFF

  key,  the  instrument  shows  “OFF”  for  5  sec.  and  the  ON/OFF  LED  is 

switched ON. 
During  the  OFF  status,  all  the  relays  are  switched  OFF  and  the  regulations  are  stopped;  if  a 
monitoring system is connected, it does not record the instrument data and alarms. 

N.B. During the OFF status the Light and AUX buttons are active. 

 

4.12

 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr2

” level. 

2. 

Select “

Prd

” parameter with 

o

 

or

 

n

3. 

Press the “

SET

” key to display “

Pb1” 

label alternate with Pb1 value. 

4. 

Use 

o

 

and

 

n

 keys to display the other probe values.  

5. 

Press “

SET

” to move to the following parameter. 

 

5.

 

REAL TIME CLOCK FUNCTIONS 

5.1

 

TO SEE THE CURRENT TIME AND DAY 

 

 

 

1.

 

Push the 

n

 

key for more than 3 seconds  

2.

 

e

 LED switches ON and the following messages are displayed: 

 

    

Hur

 (hour); 

Min

 (Minute); 

dAY

 (day = giorno)  

3.

 

To exit push 

o

 key or wait 5 seconds 

 

5.2

 

TO SET THE TIME AND THE WEEKLY HOLIDAYS 

 

 

1.

 

Push the 

n

 

key for more than 3 seconds  

2.

 

e

 LED switches ON and the current time is displayed. 

3.

 

By pushing the SET key, the 

e

 LED will start flashing and setting the current hour, 

minutes, day and the weekly holidays (up to 3) will be possible.   

4.

 

To exit, press 

SET + UP 

or wait 15s without pressing any key. 

 

5.3

 

TO SET THE DEFROST TIMES  

 

 

1.

 

Push the 

n

 

key for more than 3 seconds  

2.

 

e

 LED switches ON and the current time is displayed. 

3.

 

By  pushing  DEF  key,  the  DEF  led  will  start  flashing  and  setting  defrost  time  will  be 
possible.   

4.

 

To exit, press 

SET + UP 

or wait 15s without pressing any key. 

 

5.4

 

TO SET THE ENERGY SAVING TIMES  

 

 

1.

 

Push the 

n

 

key for more than 3 seconds  

2.

 

e

 LED switches ON and the current time is displayed. 

3.

 

By pushing the ES key, the ES led will start flashing and setting Energy Saving time will be 
possible.   

4.

 

To exit, press 

SET + UP 

or wait 15s without pressing any key. 

 

5.5

 

TO START HOLIDAY FUNCTION BY USING THE KEYBOARD 

 

 

1.

 

Push the ES key for more than 6 seconds until the label “Hd” is shown. 

2.

 

e

 LED will start to blink slower than during time programming and the regulators will 

follow holiday times. 

3.

 

Push the ES key for more than 6 seconds to start normal functioning again. 

 

6.

 

PARAMETER LIST 

REGULATION 
Hy  Differential: 

(0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor Cut 

IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. 

LS  Minimum  set  point  limit: 

(-50,0°C

SET;  -58°F÷SET)  Sets  the  minimum  acceptable  value  for  the  set 

point. 

US  Maximum set point limit: 

(SET

110°C; SET÷230°F) Set the maximum acceptable value for set point. 

OdS  Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up of the 

instrument and inhibits any output activation for the period of time set in the parameter. (AUX and Light 
can work) 

AC  Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following restart. 

CCt  Thermostat override:

 (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used, 

for instance, when the room is filled with new products.

 

Con Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is active in case 

of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is off in case of 

faulty thermostat probe. With COF=0 compressor is always active. 

 
DISPLAY 
CF  Temperature  measurement  unit:

  °C  =  Celsius;  °F  =  Fahrenheit  .  When  the  measurement  unit  is 

changed the SET point and the values  of the regulation parameters have to be modified

 

rES  Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

de

 = 0,1°C 

in

 = 1 °C  

Red  Remote display : 

select which probe is displayed by the remote display (

T850

)

  

P1

 = Thermostat probe 

P2

 = Evaporator probe 

P3

 = auxiliary probe 

1r2

 = difference between P1 and P2 (P1-P2) 

 

DEFROST 
tdF   Defrost type:  

rE

 = electrical heater (Compressor OFF) 

rT

 = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on the 

evaporator temperature and “dtE” value. 

in

 = hot gas (Compressor and defrost relays ON) 

EdF  Defrost mode:

  

 

 

rtc 

Real Time Clock mode

. Defrost time follows 

Ld1÷Ld8

 parameters on workdays and 

Sd1÷Sd8

 on 

holidays.  

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

Sd

  = 

Smart  Defrost  mode

.  The  time  IdF  (interval  between  defrosts)  is  increased  only  when  the 

compressor is running (even non consecutively) and only if the evaporator temperature is less than the 
value in "

SdF

” (set point for SMARTFROST).  

SdF  Set  point  for  SMARTFROST

:  (-30

30  °C/  -22

86  °F)  evaporator  temperature  which  allows  the  IdF 

counting (interval between defrosts) in SMARTFROST mode. 

 dtE   Defrost  termination  temperature:

  (-50,0÷110,0°C;  -58÷230°F)  (Enabled  only  when  the  evaporator 

probe  is  present)  sets  the  temperature  measured  by  the  evaporator  probe  which  causes  the  end  of 
defrost. 

IdF  Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two defrost 

cycles. 

MdF  (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the defrost 

duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length for defrost. 

dFd   Display during defrost:  
 

rt

 = real temperature;  

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

Summary of Contents for Dixell Wing XW570K

Page 1: ...ble through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is control by means of parameter EdF EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld8 on workdays and in Sd1 Sd8 in holidays EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only ...

Page 2: ...ll be possible 4 To exit press SET UP or wait 15s without pressing any key 5 3 TO SET THE DEFROST TIMES 1 Push the n key for more than 3 seconds 2 eLED switches ON and the current time is displayed 3 By pushing DEF key the DEF led will start flashing and setting defrost time will be possible 4 To exit press SET UP or wait 15s without pressing any key 5 4 TO SET THE ENERGY SAVING TIMES 1 Push the n...

Page 3: ...AUX actuation Es Energy Saving onF remote On OFF Hdf Holiday function did Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when I2F PAL If I2F EAL or bAL external alarms did parameter defines the time delay between the detection and the successive signalling of the alarm TO SET CURRENT TIME AND WEEKLY HOLIDAYS 3SEC afterw...

Page 4: ...he TTL connector allows by means of the external module TTL RS485 XJ485 to connect the unit to a network line ModBUS RTU compatible as the Dixell monitoring system XJ500 Version 3 0 The same TTL connector is used to upload and download the parameter list of the HOT KEY The instruments can be ordered wit the serial output RS485 Optional 12 USE OF THE PROGRAMMING HOT KEY The Wing units can UPLOAD or...

Page 5: ...ans relay SPST 8 3 A 250Vac defrost relay SPST 8 3 A 250Vac alarm SPST relay 8 3 A 250Vac auxiliary SPST relay 16 3 A 250Vac Other output Analogue output 4 20 mA optional Serial output TTL standard RS485 optional Communication protocol ModBUS RTU Data storing on the non volatile memory EEPROM Internal clock back up 24 hours Kind of action 1B Pollution grade normal Software class A Operating temper...

Page 6: ...put configuration EAL bAL PAL dFr AUS ES OnF EAL Pr2 dId Digital input alarm delay 0 255 min 5 Pr2 TIME AND WEEKLY HOLIDAYS C F XW570 Hur Current hour 0 23 0 Pr2 Min Current minute 0 59 0 Pr2 dAY Current day Sun SAt Sun Pr2 Hd1 First weekly holiday Sun SAt nu nu Pr2 Hd2 Second weekly holiday Sun SAt nu nu Pr2 Hd3 Third weekly holiday Sun SAt nu nu Pr2 ENERGY SAVING TIMES ILE Energy Saving cycle st...

Reviews: