Label  Name 

  Range 

Default  Level

 

 

FANS 

 

 

 

FnC  Fans operating mode 

C-n, C-y, O-n, O-y  

O-n 

Pr2 

Fnd 

Fans delay after defrost 

0÷255 min. 

10 

Pr2 

FSt 

Fans stop temperature 

-50,0÷110°C /  -58÷230°F 

2/35 

Pr2 

 

ALARMS 

 

 

 

ALC  Temperature alarms configuration 

rE÷Ab 

rE 

Pr2 

ALU  MAXIMUM temperature alarm 

-50,0÷110°C/-58÷230°F 

10/20 

Pr1 

ALL  minimum temperature alarm 

-50,0÷110°C/ -58÷230°F 

10/20 

Pr1 

AFH  Temperature alarm and fan differential 

0,1÷25,5 °C/ 1÷45°F 

2/4 

 

ALd  Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO  Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 

Pr2 

EdA  Alarm delay at the end of defrost  

0÷255 min. 

30 

Pr2 

dot 

Delay of temperature alarm after closing the door  

0÷255 min. 

15 

Pr2 

dOA  Open door alarm delay  

0÷254 min., nu 

15 

Pr2 

tBA 

Alarm relay silencing 

y ÷ n 

Pr2 

nPS  Pressure switch activation number 

0÷15 

Pr2 

 

ANALOGUE OUTPUT  
4÷20mA (Optional)

 

 

 

 

AOS  Analogue output start point 

-50,0÷110°C / -58÷230°F 

0/32 

Pr2 

APb  Analogue output band width 

-50,0÷110°C / -58÷230°F 

Pr2 

CAO  Input type for the analogue output 

P1÷1r2 

P1 

Pr2 

 

ANALOGUE INPUTS 

 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr1 

OE 

Evaporator probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr2 

O3 

Auxiliary probe calibration 

-12,0÷12,0°C / -21÷21°F 

Pr2 

P2P  Evaporator probe presence 

n ÷ y 

Pr2 

P3P  Auxiliary probe presence 

n ÷ y 

Pr2 

HES  Temperature increase during the Energy Saving 

cycle  

-30÷30°C / -54÷54°F 

Pr2 

 

DIGITAL INPUTS 

 

 

 

Odc  Open door control  

no, Fan, CPr, F_C 

Fan 

Pr2 

I1P 

Door switch polarity 

CL÷OP 

CL 

Pr2 

I2P 

Configurable digital input polarity 

CL÷OP 

CL 

Pr2 

i2F 

Digital input configuration 

EAL, bAL, PAL, 

dFr, AUS, ES, OnF 

EAL 

Pr2 

dId 

Digital input alarm delay 

0÷255 min. 

Pr2 

 

TIME AND WEEKLY HOLIDAYS

 

 

°C/°F 

XW570 

Hur  Current hour 

0 ÷ 23 

Pr2 

Min  Current minute 

0 ÷ 59 

Pr2 

dAY  Current day 

Sun ÷ SAt 

Sun 

Pr2 

Hd1  First weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr2 

Hd2  Second weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr2 

Hd3  Third weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr2 

 

ENERGY SAVING TIMES 

 

 

 

ILE 

Energy Saving cycle start during workdays 

0 ÷ 23h 50 min. 

Pr2 

dLE  Energy Saving cycle length during workdays 

0 ÷ 24h 00 min. 

Pr2 

ISE  Energy Saving cycle start on holidays 

0 ÷ 23h 50 min. 

Pr2 

dSE  Energy Saving cycle length on holidays 

0 ÷ 24h 00 min. 

Pr2 

HES  Temperature  increase  during  the  Energy  Saving 

cycle 

-30÷30°C / -54÷54°F 

Pr2 

 

DEFROST TIMES 

 

 

 

Ld1  1

st

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Ld2  2

nd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Ld3  3

rd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Ld4  4

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld5  5

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld6  6

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld7  7

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Ld8  8

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd1  1

st

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

6.0 

Pr2 

Sd2  2

nd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

13.0 

Pr2 

Sd3  3

rd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

21.0 

Pr2 

Sd4  4

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd5  5

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd6  6

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

Sd7  7

th

 holiday defrost start 

0 ÷ 23h 50  min. - nu 

nu 

Pr2 

Sd8  8

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Pr2 

 

OTHER 

 

 

 

Adr 

Serial address 

0÷247 

Pr1 

rEL 

Software release 

- - - 

- - - 

Pr2 

Label  Name 

  Range 

Default  Level

 

Ptb 

Map code 

- - - 

- - - 

Pr2 

Prd 

Probes display 

Pb1÷Pb3 

- - - 

Pr2 

Pr2   Access parameter list 

- - - 

- - - 

Pr2 

 
 

 

 

Summary of Contents for Dixell Wing XW570K

Page 1: ...ble through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is control by means of parameter EdF EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld8 on workdays and in Sd1 Sd8 in holidays EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only ...

Page 2: ...ll be possible 4 To exit press SET UP or wait 15s without pressing any key 5 3 TO SET THE DEFROST TIMES 1 Push the n key for more than 3 seconds 2 eLED switches ON and the current time is displayed 3 By pushing DEF key the DEF led will start flashing and setting defrost time will be possible 4 To exit press SET UP or wait 15s without pressing any key 5 4 TO SET THE ENERGY SAVING TIMES 1 Push the n...

Page 3: ...AUX actuation Es Energy Saving onF remote On OFF Hdf Holiday function did Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when I2F PAL If I2F EAL or bAL external alarms did parameter defines the time delay between the detection and the successive signalling of the alarm TO SET CURRENT TIME AND WEEKLY HOLIDAYS 3SEC afterw...

Page 4: ...he TTL connector allows by means of the external module TTL RS485 XJ485 to connect the unit to a network line ModBUS RTU compatible as the Dixell monitoring system XJ500 Version 3 0 The same TTL connector is used to upload and download the parameter list of the HOT KEY The instruments can be ordered wit the serial output RS485 Optional 12 USE OF THE PROGRAMMING HOT KEY The Wing units can UPLOAD or...

Page 5: ...ans relay SPST 8 3 A 250Vac defrost relay SPST 8 3 A 250Vac alarm SPST relay 8 3 A 250Vac auxiliary SPST relay 16 3 A 250Vac Other output Analogue output 4 20 mA optional Serial output TTL standard RS485 optional Communication protocol ModBUS RTU Data storing on the non volatile memory EEPROM Internal clock back up 24 hours Kind of action 1B Pollution grade normal Software class A Operating temper...

Page 6: ...put configuration EAL bAL PAL dFr AUS ES OnF EAL Pr2 dId Digital input alarm delay 0 255 min 5 Pr2 TIME AND WEEKLY HOLIDAYS C F XW570 Hur Current hour 0 23 0 Pr2 Min Current minute 0 59 0 Pr2 dAY Current day Sun SAt Sun Pr2 Hd1 First weekly holiday Sun SAt nu nu Pr2 Hd2 Second weekly holiday Sun SAt nu nu Pr2 Hd3 Third weekly holiday Sun SAt nu nu Pr2 ENERGY SAVING TIMES ILE Energy Saving cycle st...

Reviews: