1592009630 XW570K GB  r1.0 04.08.2015 

XW570K 

5/6 

13.1

 

SILENCING BUZZER / ALARM RELAY OUTPUT 

If “

tbA = y

”, once the alarm signal is detected the buzzer and the relay are is silenced by pressing any key.  

If “

tbA 

n

”, only the buzzer is silenced while the alarm relay is on until the alarm condition recovers. 

Buzzer is mounted in the 

T850

 keyboards and it is an option. 

13.2

 

“EE” ALARM 

The  Dixell  instruments  are  provided  with  an  internal  check  for  the  data  integrity.  Alarm  “EE”  flashes  when  a 
failure in the memory data occurs. In such cases the alarm output is enabled. 

13.3

 

ALARM RECOVERY 

Probe alarms : “

P1

” (probe1 faulty), “

P2

” and “

P3

”; they automatically stop 10s after the probe restarts normal 

operation. Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to normal 

values or when the defrost starts. 
Door switch alarm “

dA

”  stop as soon as the door is closed. 

External alarms “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled “

PAL

” alarm is recovered by 

switching OFF the instrument. 

14.

 

TECHNICAL DATA 

T850 keyboards 
Housing: 

self extinguishing ABS.

 

Case: 

facia 38x185 mm; depth 23mm 

Mounting :

  

 

panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 

Distance between the holes 165mm 

Protection: 

IP20.

 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm  

Power supply: 

from

 

power module

 

Display

: 3 digits, red LED, 14,2 mm high.  

Optional output: 

buzzer

 

 
Power modules XW570K  
Case: 
“OS”

: open board 132x 94 mm; height: 40mm. 

“OA”

: open board with aluminium protection 176x 123mm; height: 52mm. 

“GS”

: case 155x114; height 70mm. Self extinguishing ABS. IP55 

“PS”

:  case 147x110; height 47mm. Self extinguishing ABS. IP55. UL approved 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm Faston 

Power supply: 

230Vac or. 110Vac 

 10% 

 

Power absorption: 

10VA max.

 

Inputs

: 3 NTC probes 

Digital inputs

: 2 free voltage 

Relay outputs: 

Total current on loads MAX. 20A

 

compressor:

 relay SPST 20(8) A, 250Vac  

light: 

relay SPST 16(3) A, 250Vac (or 

optional

 relay SPST 16(3) A, special for fluorescent lights) 

fans:

 relay SPST 8(3) A, 250Vac

 

defrost:

 relay SPST 8(3) A, 250Vac  

alarm: 

SPST relay 8(3) A, 250Vac 

auxiliary:

 SPST relay 16(3) A, 250Vac 

Other output : 

 

Analogue output

 4÷20 mA (optional) 

Serial output :

 TTL standard. RS485 optional 

Communication protocol:

 ModBUS - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Internal clock back-up:

 24 hours 

Kind of action: 

1B. 

Pollution grade: 

normal 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range:  
NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

15.

 

CONNECTIONS 

15.1

 

XW570K  

 

 

 

 

Connector 
 number 

Description 

Connector 
 number 

Description 

HOT KEY 

Hot key for programming 

9 - 10 

Door switch 

RS485 (Optional) 

RS485 direct output 

11 - 12 

Alarm relay  

An.Out (Optional)  4÷20 mA analogue output 

13 - 14 

Compressor relay 

KEY (+) 

+ :connection for keyboard 

15 

Phase 

KEY (-) 

- : connection for keyboard 

16 

Neutral 

1 – 2 

Display probe 

17 - 18 

Light relay 

3 - 4 

Defrost probe 

19 - 20 

Defrost relay 

5 - 6 

Room probe 

21 - 22 

Fan relay  

7 - 8 

Configurable digital input  

18 -19 

Auxiliary relay 

 

 

16.

 

DEFAULT SETTING VALUES 

 

Label  Name 

  Range 

Default  Level

 

 

REGULATION 

 

°C/°F 

XW570 

Set 

Set point 

LS÷US 

-5/23 

Pr1 

Hy 

Differential 

0,1÷25,5 °C / 1÷45°F 

2/4 

Pr1 

LS 

Minimum set point 

 -50,0°C÷SET / -58°F÷SET 

-30/-22 

Pr2 

US 

Maximum set point 

SET ÷ 110°C / SET ÷ 230°F 

20/68 

Pr2 

OdS  Outputs activation delay at start up 

0÷255 min. 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

CCt 

Compressor ON time during fast freezing 

0 ÷ 23h 50 min. 

Pr2 

COn  Compressor ON time with faulty probe 

0÷255 min. 

15 

Pr2 

COF  Compressor OFF time with faulty probe 

0÷255 min. 

30 

Pr2 

 

DISPLAY 

 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C/°F 

Pr2 

rES 

Resolution (integer/decimal point) 

in ÷ de 

de 

Pr1 

Red  Remote display  

P1 ÷ 1r2 

p1 

Pr2 

 

DEFROST 

 

 

 

tdF 

Defrost type 

rE,  rT,  in  

rE 

Pr1 

EdF  Defrost mode 

rtc, In, Sd 

In 

Pr2 

SdF  Set point for SMART DEFROST 

-30 ÷ +30°C / -22÷+86°F 

Pr2 

dtE 

Defrost termination temperature (1°Evaporator) 

-50,0÷110°C /-58÷230°F 

8/46 

Pr1 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF  (Maximum) length for 1° defrost 

0÷255 min. 

30 

Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, dEF, dEG 

it 

Pr2 

dAd  MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

Fdt 

Draining time 

0÷60 min. 

Pr2 

dPO  First defrost after start up 

n ÷ y 

Pr2 

dAF  Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

Pr2 

Summary of Contents for Dixell Wing XW570K

Page 1: ...ble through the tdF parameter defrost with electrical heater hot gas or thermostatic defrost The defrost interval is control by means of parameter EdF EdF rtc the defrost is made in real time depending on the hours set in the parameters Ld1 Ld8 on workdays and in Sd1 Sd8 in holidays EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only ...

Page 2: ...ll be possible 4 To exit press SET UP or wait 15s without pressing any key 5 3 TO SET THE DEFROST TIMES 1 Push the n key for more than 3 seconds 2 eLED switches ON and the current time is displayed 3 By pushing DEF key the DEF led will start flashing and setting defrost time will be possible 4 To exit press SET UP or wait 15s without pressing any key 5 4 TO SET THE ENERGY SAVING TIMES 1 Push the n...

Page 3: ...AUX actuation Es Energy Saving onF remote On OFF Hdf Holiday function did Time interval delay for digital input alarm 0 255 min Time interval to calculate the number of the pressure switch activation when I2F PAL If I2F EAL or bAL external alarms did parameter defines the time delay between the detection and the successive signalling of the alarm TO SET CURRENT TIME AND WEEKLY HOLIDAYS 3SEC afterw...

Page 4: ...he TTL connector allows by means of the external module TTL RS485 XJ485 to connect the unit to a network line ModBUS RTU compatible as the Dixell monitoring system XJ500 Version 3 0 The same TTL connector is used to upload and download the parameter list of the HOT KEY The instruments can be ordered wit the serial output RS485 Optional 12 USE OF THE PROGRAMMING HOT KEY The Wing units can UPLOAD or...

Page 5: ...ans relay SPST 8 3 A 250Vac defrost relay SPST 8 3 A 250Vac alarm SPST relay 8 3 A 250Vac auxiliary SPST relay 16 3 A 250Vac Other output Analogue output 4 20 mA optional Serial output TTL standard RS485 optional Communication protocol ModBUS RTU Data storing on the non volatile memory EEPROM Internal clock back up 24 hours Kind of action 1B Pollution grade normal Software class A Operating temper...

Page 6: ...put configuration EAL bAL PAL dFr AUS ES OnF EAL Pr2 dId Digital input alarm delay 0 255 min 5 Pr2 TIME AND WEEKLY HOLIDAYS C F XW570 Hur Current hour 0 23 0 Pr2 Min Current minute 0 59 0 Pr2 dAY Current day Sun SAt Sun Pr2 Hd1 First weekly holiday Sun SAt nu nu Pr2 Hd2 Second weekly holiday Sun SAt nu nu Pr2 Hd3 Third weekly holiday Sun SAt nu nu Pr2 ENERGY SAVING TIMES ILE Energy Saving cycle st...