background image

 

1592009550 XW264K GB r1.0 04.08.2015 

                     XW264K 

4/4 

                          XW264K   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4/4/ 

err

” for failed programming. In this case turn the unit off and then on if you want to restart the download again 

or remove the “

Hot key

” to abort the operation. 

10.2

 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1.

 

Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then 
turn it ON again. 

2.

 

When the Wing unit  is ON, insert the “

Hot key

” and push 

o

 

key; the  

"uPL" 

message appears. 

3.

 

Push “

SET”

 key to start the UPLOAD; the “

uPL

” message is blinking. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. 

err

”  for  failed  programming.  In  this  case  push  “SET”  key  if  you  want  to  restart  the  programming  again  or 

remove the not programmed “

Hot key

”. 

11.

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure 

Alarm  output  ON;  Compressor  output  according  to 
parameters “COn” and “COF” 

“P2” 

1

st

 Evaporator probe failure 

Alarm output ON; Other outputs unchanged 

“P3” 

2

nd

 Evaporator probe failure 

Alarm output ON; Other outputs unchanged 

“HA” 

Max. temperature alarm 

Alarm output ON; Other outputs unchanged 

“LA” 

Min. temperature alarm 

Alarm output ON; Other outputs unchanged 

“EE”  

Data or memory failure 

Alarm output ON; Other outputs unchanged 

“dA” 

Defrost timeout alarm 

Alarm output ON; Other outputs unchanged 

“dAL” 

Door switch alarm 

Alarm output ON; Other outputs unchanged 

“EAL” 

External alarm 

Alarm output ON; Other outputs unchanged 

“BAL” 

Serious external alarm 

Alarm output ON; Other outputs OFF 

“PAL” 

Pressure switch alarm 

Alarm output ON; Other outputs OFF

 

The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. 
To reset the “EE” alarm and restart the normal functioning press any key, the “

rSt

” message is displayed for 

about 3s. 

11.1

 

SILENCING BUZZER  

Once the alarm signal is detected the buzzer can be silenced by pressing any key.  

11.2

 

“EE” ALARM 

The  Dixell  instruments  are  provided  with  an  internal  check  for  the  data  integrity.  Alarm  “EE”  flashes  when  a 
failure in the memory data occurs. In such cases the alarm output is enabled. 

11.3

 

ALARM RECOVERY 

Probe alarms : “

P1

” (probe1 faulty), “

P2

” and “

P3

”; they automatically stop 10s after the probe restarts normal 

operation. Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to normal 

values or when the defrost starts. 
Door switch alarm “

dA

”  stop as soon as the door is closed. 

External alarms “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled “

PAL

” alarm is recovered by 

switching OFF the instrument. 

 

12.

 

TECHNICAL DATA 

T820 keyboard 
Housing: 

self extinguishing ABS.

 

Case: T620 

facia 38x185 mm; depth 23mm; 

V620 

facia 64x164 mm; depth 23mm 

Mounting :

 

T620 

panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

 

Distance between the holes 165mm 

V620:

 panel mounting in a 56x72 mm panel cut-out with two screws. 

 3x2mm. Distance between the 

holes 40mm 

Protection: 

IP20; 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm  

Power supply: 

from

 XW230K 

power module

 

Display

: 3 digits, red LED, 14,2 mm high; 

Optional output: 

buzzer

 

 
Power module XW264K 
Housing: 

self extinguishing ABS; 

Case: 

facia 38x185 mm; depth 76mm 

Mounting:

 panel mounting in a 150x31 mm panel cut-out with two screws. 

 3 x 2mm. 

Distance between the holes 165mm 

Protection: 

IP20.

 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw  terminal  block 

  2,5  mm

2

  heat-resistant  wiring  and  6,3mm  Faston; 

Optional

 

disconnectable terminal blocks (

max.12A

Power supply: 

230Vac or. 110Vac 

 10%; 

Power absorption: 

7VA max.

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: 3 NTC probes 

Digital inputs

: 2 free voltage 

Relay outputs: 

Total current on loads MAX. 20A

 

compressor:

 relay SPST 8(3) A, 250Vac  

light: 

relay SPST 16(3) A, 250Vac (or 

optional

 relay SPST 16(3) A, special for fluorescent lights) 

fans:

 relay SPST 8(3) A, 250Vac

 

1

st

 defrost:

 relay SPDT 8(3) A, 250Vac  

2

nd 

defrost : 

relay SPDT 8(3) A, 250Vac 

ON/OFF:

 SPST relay 16(3) A, 250Vac 

Other output:

 

Alarm buzzer

 (Standard) 

 

Direct

 RS485 

(optional)

 

Serial output :

 TTL standard; 

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

normal; 

Software class: 

A.

 

Operating temperature: 

0÷60 °C; 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

  

13.

 

CONNECTIONS 

13.1

 

XW264K 

L

1918

1514

20

2221

C

om

p

N

16(6)A

Light

1 2 3 4

6

8

7

9 10

K

brd

Def

.1

Roo

m

Def

.2

5

13

16

17

D

ef 1

Fan

1211

23

24

8(3)

A

8(3)A

8(3)A

250V

~

8(3)A

D

ef 2

16(6)A

 

Supply: 230Vac 

or

 120Vac 

or

 24Vac 

according to the model 

 

14.

 

DEFAULT SETTING VALUES 

Label  Name 

  Range 

Default 

Level

 

 

REGULATION 

 

°C/°F 

 

Set 

Set point 

LS÷US 

-5/23 

Pr1 

Hy 

Differential 

0,1÷25,5 °C;  1÷45°F 

2/4 

Pr1 

LS 

Minimum set point 

 -50,0°C÷SET; -58°F÷SET 

-30/-22 

Pr2 

US 

Maximum set point 

SET ÷ 110°C, SET ÷ 230°F 

20/68 

Pr2 

OdS 

Outputs activation delay at start up 

0÷255 min. 

Pr2 

AC 

Anti-short cycle delay 

0÷30 min. 

Pr1 

CCt 

Compressor ON time during fast freezing 

0 ÷ 23h 50 min. 

Pr2 

COn 

Compressor ON time with faulty probe 

0÷255 min. 

15 

Pr2 

COF 

Compressor OFF time with faulty probe 

0÷255 min. 

30 

Pr2 

 

DISPLAY 

 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C/°F 

Pr2 

rES 

Resolution (integer/decimal point) 

in ÷ de 

de 

Pr1 

Lod 

Local display  

P1 ÷ 1r2 

P1 

Pr2 

Red 

Remote display  

P1 ÷ 1r2 

p1 

Pr2 

 

DEFROST 

 

 

 

tdF 

Defrost type 

rE,  rT,  in  

rE 

Pr1 

EdF 

Defrost mode 

In, Sd 

In 

Pr2 

SdF 

Set point for SMART DEFROST 

-30 ÷ +30°C; -22÷+86°F 

Pr2 

dtE 

Defrost termination temperature (1°Evaporator) 

-50,0÷110°C; -58÷230°F 

8/46 

Pr1 

dtS 

Defrost termination temperature (2°Evaporator) 

-50,0÷110°C; -58÷230°F 

8/46 

Pr1 

IdF 

Interval between defrost cycles 

1÷120h 

Pr1 

MdF 

(Maximum) length for 1° defrost 

0÷255 min. 

30 

Pr1 

MdS 

(Maximum) length for 2° defrost 

0÷255 min. 

30 

Pr1 

dFd 

Displaying during defrost 

rt, it, SEt, dEF, dEG 

it 

Pr2 

dAd 

MAX display delay after defrost 

0÷255 min. 

30 

Pr2 

dSd 

Defrost delay  

0÷99min 

Pr2 

Fdt 

Draining time 

0÷60 min. 

Pr2 

dPO 

First defrost after start up 

n ÷ y 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h 50 min. 

Pr2 

 

FANS 

 

 

 

FnC 

Fans operating mode 

C-n, C-y, O-n, O-y  

O-n 

Pr2 

Fnd 

Fans delay after defrost 

0÷255 min. 

10 

Pr2 

FSt 

Fans stop temperature 

-50,0÷110°C;  -58÷230°F 

2/35 

Pr2 

 

ALARMS 

 

 

 

ALC 

Temperature alarms configuration 

rE÷Ab 

rE 

Pr2 

ALU 

MAXIMUM temperature alarm 

-50,0÷110°C; -58÷230°F 

10/20 

Pr1 

ALL 

minimum temperature alarm 

-50,0÷110°C;  -58÷230°F 

10/20 

Pr1 

AFH 

Temperature alarm and fan differential 

0,1÷25,5 °C;  1÷45°F 

2/4 

 

ALd 

Temperature alarm delay 

0÷255 min. 

15 

Pr2 

dAO 

Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 

Pr2 

EdA 

Alarm delay at the end of defrost  

0÷255 min. 

30 

Pr2 

dot 

Delay of temperature alarm after closing the door  

0÷255 min. 

15 

Pr2 

dOA 

Open door alarm delay  

0÷254 min.,nu 

15 

Pr2 

nPS 

Pressure switch activation number 

0÷15 

Pr2 

 

ANALOGUE INPUTS 

 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C;  -21÷21°F 

Pr1 

OE 

1

st

 evaporator probe calibration 

-12,0÷12,0°C; -21÷21°F 

Pr2 

O3 

2

nd

 evaporator probe calibration 

-12,0÷12,0°C; -21÷21°F 

Pr2 

P2P 

1

st

 evaporator probe presence 

n ÷ y 

Pr2 

P3P 

2

nd

 evaporator probe presence 

n ÷ y 

Pr2 

HES 

Temperature increase during the En. Saving cycle  

-30÷30°C; -22÷86°F 

Pr2 

 

DIGITAL INPUTS 

 

 

 

Odc 

Open door control  

no, Fan, CPr, F_C 

Fan 

Pr2 

I1P 

Door switch polarity 

CL÷OP 

CL 

Pr2 

I2P 

Configurable digital input polarity 

CL÷OP 

CL 

Pr2 

i2F 

Digital input configuration 

EAL, bAL, PAL, 

dFr, AUS, ES, OnF 

EAL 

Pr2 

dId 

Digital input alarm delay 

0÷255 min. 

Pr2 

 

OTHER 

 

 

 

Adr 

Serial address 

0÷247 

Pr1 

rEL 

Software release 

- - - 

1.0 

Pr2 

Ptb 

Map code 

- - - 

- - - 

Pr2 

Prd 

Probes display 

Pb1÷Pb3 

- - - 

Pr2 

Pr2  

Access parameter list 

- - - 

- - - 

Pr2 

 
 

 

Summary of Contents for Dixell WING XW264K

Page 1: ...EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temperature is bigger than SdF parameter At the end of defrost the drip time is controlled through the Fdt parameter This instrument can menage a defrost on two different evaporators It waits the defrost end on both evaporators before starting normal regulation 3 4 CONTROL OF EVAP...

Page 2: ... mode dtE Defrost termination temperature 1st evaporator 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the first evaporator probe which causes the end of defrost dtS Defrost termination temperature 2nd evaporator 50 0 110 0 C 58 230 F Enabled only when the 2nd evaporator probe is present sets the temperature measured by the 2nd evaporator ...

Page 3: ...unction is enabled until the digital input is activated 6 7 CONFIGURABLE INPUT REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 6 8 DIGITAL INPUTS POLARITY The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING Keyboard T620 ...

Page 4: ... digits red LED 14 2 mm high Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A compressor relay SPST 8 3 A 250Vac light relay SPST 16 3 A 250Vac or optional relay SPST 16 3 A special for fluorescent lights fans relay SPST 8 3 A 250Vac 1st defrost relay SPDT 8 3 A 250Vac 2nd defrost relay SPDT 8 3 A 250Vac ON OFF SPST relay 16 3 A 250Vac Other output Ala...