background image

 

1592009550 XW264K GB r1.0 04.08.2015 

                     XW264K 

1/4 

                          XW264K   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4/ 

W

ING

 

XW264K 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be used 
as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the 
same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see 
address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 
inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Models 

XW264K

,  is microprocessor based controller suitable for applications on medium or low temperature 

refrigerating units. They must be connected by means of a two-wire cable (

 1mm) at a distance of up to 30 

meters  to  the  keyboards 

T620

,  185x38mm  format,  or 

V620 

64x164mm  format

It  is  provided  with  six  relay 

outputs to control compressor, two defrosts - which can be either electrical or hot gas  - the evaporator fans, the 
lights and an ON/OFF output. It is also provided with three NTC probe inputs, one for temperature control, two 
to control the defrost end temperature of two evaporators. There are two digital inputs (free contact) for the door 
switch and configurable by parameter. 
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a 

ModBUS-

RTU 

compatible monitoring system and to programme the parameter list with the 

“Hot Key”.

 

An output for remote display 

XW-REP, 

4÷20 mA 

output

 

to control evaporator or condenser fans and the direct 

serial output 

RS485

 are available as options. 

3.

 

CONTROLLING LOADS 

3.1

 

THE COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the  thermostat  probe  with  a  positive 
differential from the set point: if the temperature increases and reaches set point plus differential the compressor 
is started and then turned off when the temperature reaches the set point value again. 
In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through  parameters 

COn

” and “

COF

”. 

3.2

 

FAST FREEZING 

When  defrost  is  not  in  progress,  it  can  be  activated  the  keypad  by  holding  the 

o

  key  pressed  for  about  3 

seconds. The compressor operates in continuous mode for the time set through the “

CCt

” parameter. The cycle 

can be terminated before the end of the set time using the same activation key, 

o

 for about 3 seconds. 

3.3

 

DEFROST 

Three  defrost  modes  are  available  through  the  “

tdF

”  parameter:  defrost  with  electrical  heater,  hot  gas  or 

thermostatic defrost. The defrost interval is control by means of parameter “

EdF

”: (EdF=in) the defrost is made 

every  “

IdF

”  time,  (EdF=Sd)  the  interval  “IdF”  is  calculate  through  Smart  Defrost  algorithm  (only  when  the 

compressor is ON and the evaporator temperature is bigger than “SdF” parameter). 
At the end of defrost the drip time is controlled through the “

Fdt

” parameter. 

This instrument can menage a defrost on two different  evaporators. It waits the defrost end on both evaporators 
before starting normal regulation 

3.4

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter: 

C-n

   fans will switch ON and OFF with the compressor and

 not run

 during defrost; 

C-y

   fans will switch ON and OFF with the compressor, also during defrost  

After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. 

O-n

   fans will run continuously and

 not run

 during defrost; 

O-y

   fans will run continuously also during defrost 

 

An  additional  parameter  “FSt”  provides  the  setting  of  temperature,  detected  by  the  evaporator  probe,  above 
which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower 
than set in “FSt”. 

3.5

 

ON/OFF RELAY  

The ON/OFF relay is switched ON when the instrument is ON and it is OFF when the instrument is switched 
OFF.  This  relay  cuts  the  common  of  the  defrost  relays,  so  that,  when  the  instrument  is  switched  OFF  by 
keyboard button none of the loads have power supply. 

 

4.

 

KEYBOARD 

 

      

 

 

 

To display and modify target set point; in programming mode it selects a parameter or confirm an 
operation.  
By holding it pressed for 3s when max or min temperature is displayed it will be erased. 
 

 

To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the  parameter  codes  or 
increases the displayed value. By holding it pressed for 3s the fast freezing  cycle is started. 

 

To  see  the  min  stored  temperature;  in  programming  mode  it  browses  the  parameter  codes  or 
decreases the displayed value. 
 

 

 
By holding it pressed for 3s the defrost is started. 
 

 

 
Switch ON and OFF the cold room light. 

 

 
Switch ON and OFF the instrument. 

 

KEY COMBINATIONS 

 

 

 

 

To lock and unlock the keyboard.

 

 

 

 

To enter the programming mode. 

 

 

 

 

To exit the programming mode.

 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor is running 

 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

 

ON 

The fan is running 

 

FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

  

ON 

- ALARM signal 
- In “Pr2” indicates that the parameter is also present in “Pr1” 

 
Function of the LEDs placed on the left top side of buttons: 
 

BUTTON 

MODE 

FUNCTION 

SET 

FLASHING 

The Set point is displayed and it can be modified  

SET 

SLOW FLASHING  The Energy Saving is enabled  

DEFROST 

ON 

The Manual Defrost is activated 

LIGHT 

ON 

The Light is ON 

ON/OFF 

ON 

The instrument is OFF 

 

4.2

 

HOW TO SEE THE MIN TEMPERATURE 

 

1.  

Press and release the 

n

 key. 

2.  

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

By pressing the 

n

 key or waiting for 5s the normal display will be restored. 

4.3

 

HOW TO SEE THE MAX TEMPERATURE 

 

1.  

Press and release the 

o

 key. 

2.  

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

By pressing the 

o

 key or waiting for 5s the normal display will be restored. 

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 
1.

 

Press SET key until “rST” label starts blinking. 

 

N.B. After the installation RESET the temperature stored .

 

4.5

 

HOW TO SEE AND MODIFY THE SET POINT 

 

1. 

Push and immediately release the 

SET 

key: the display will show the Set point value; 

2. 

The SET LED start blinking; 

3. 

To change the Set value push the 

or 

n

 arrows within 10s. 

4. 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

Summary of Contents for Dixell WING XW264K

Page 1: ...EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ON and the evaporator temperature is bigger than SdF parameter At the end of defrost the drip time is controlled through the Fdt parameter This instrument can menage a defrost on two different evaporators It waits the defrost end on both evaporators before starting normal regulation 3 4 CONTROL OF EVAP...

Page 2: ... mode dtE Defrost termination temperature 1st evaporator 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the first evaporator probe which causes the end of defrost dtS Defrost termination temperature 2nd evaporator 50 0 110 0 C 58 230 F Enabled only when the 2nd evaporator probe is present sets the temperature measured by the 2nd evaporator ...

Page 3: ...unction is enabled until the digital input is activated 6 7 CONFIGURABLE INPUT REMOTE ON OFF ONF This function allows to switch ON and OFF the instrument 6 8 DIGITAL INPUTS POLARITY The digital inputs polarity depends on I1P and I2P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 7 INSTALLATION AND MOUNTING Keyboard T620 ...

Page 4: ... digits red LED 14 2 mm high Inputs 3 NTC probes Digital inputs 2 free voltage Relay outputs Total current on loads MAX 20A compressor relay SPST 8 3 A 250Vac light relay SPST 16 3 A 250Vac or optional relay SPST 16 3 A special for fluorescent lights fans relay SPST 8 3 A 250Vac 1st defrost relay SPDT 8 3 A 250Vac 2nd defrost relay SPDT 8 3 A 250Vac ON OFF SPST relay 16 3 A 250Vac Other output Ala...

Reviews: