Scaling the 4-20 mA analog output (Aout)
Figure 6-6:
NOTICE
Note that when power is removed from the meter, the analog output will drop below 1 mA.
Take this effect into consideration when designing any system using the 4-20 mA output.
6.5
Gate function (GATE)
Use the gate function for displaying slow pulse rates. When using the programmable gate,
the meter displays pulse rates as slow as 1 pulse every 9,999 seconds (0.0001 Hz). The
gate function can also be used to obtain a steady display reading with a fluctuating input
signal.