6.3
Open collector outputs (OUTPUT)
The meter is equipped with two NPN open collector outputs that may be set up for pulse
outputs, alarms, timed pulses, or turned off.
Pulse outputs are based on K-factor, total or grand total counts, or one-for-one retransmit
for input pulses. Both outputs may be used to generate a quadrature output based on any
pulse menu output type. An output test mode may be selected to generate pulses at a
constant programmable frequency.
Alarms are available based on the rate, total, or grand total. The alarm status appears on
the display even if the output is not wired. The outputs may also be forced on or off. A
timed pulse output generates constant pulses at a specified frequency and on time. The
output may be disabled by selecting Off.
Open collector outputs
Figure 6-2:
6.3.1
Output 1 and 2 Setup (OUT 1, OUT 2)
The function of open collector output 1 and 2 is configured using the Off, Pulse, Alarm,
and the Timer menus detailed below.
Product advanced features
User manual
59
Summary of Contents for Daniel 1200 Series
Page 8: ......
Page 12: ...Contents iv LTM Internal Display ...
Page 14: ...Plan 2 LTM Internal Display ...
Page 33: ...Open collector output connections Figure 3 13 Product connections User manual 21 ...
Page 34: ...Product connections 22 LTM Internal Display ...
Page 35: ...Part II Install Install User manual 23 ...
Page 36: ...Install 24 LTM Internal Display ...
Page 38: ...Installation requirements and limitations 26 LTM Internal Display ...
Page 40: ...Operate 28 LTM Internal Display ...
Page 64: ...Setting the toggle time TIME Figure 5 20 Setup and programming 52 LTM Internal Display ...
Page 98: ...Product advanced features 86 LTM Internal Display ...
Page 106: ...Startup procedure 94 LTM Internal Display ...
Page 107: ...Part IV Maintain Maintain User manual 95 ...
Page 108: ...Maintain 96 LTM Internal Display ...
Page 113: ...Maintenance User manual 101 ...