Emerson Copeland Scroll ZP K3 Series Bulletin Download Page 11

11

© 2015 Emerson Climate Technologies, Inc.

AE4-1365 R4

with compressors of unequal capacity, check with 

application engineering or on-line product information 

for availability. Tandem ready compressors are 

designated with a -4XX bill of material number at the 

end of the model number (e.g. ZP61KCE-TFD-420). 

See 

Figure 5

 for a picture of an assembled tandem 

showing the hardware and parts required for assembly. 

Drawings of tandem tubing assemblies are available 

from Emerson Climate Technologies by contacting 

your Application Engineer.

Tandem Applications

Tandem compressors follow the same application 

guidelines as single compressors outlined in this 

bulletin. The refrigerant charge limit for tandem 

compressors is shown in 

Table 3

. Crankcase heaters 

must

 be installed on each compressor in the tandem 

set when the system charge amount exceeds the 

tandem charge limit. 

The compressors in a tandem set can be started/

stopped in any desired sequence. To help reduce 

the probability of light dimming and to reduce inrush 

current, starting the compressors individually is 

recommended. Should a compressor fail in the tandem 

set the complete tandem should be removed from the 

unit and replaced with a new tandem set. Replacing 

individual compressors is discouraged because of 

the care that must be used when installing the oil 

equalization tube and the availability of manifolds to 

the aftermarket.

APPLICATION TESTS
Application Test Summary

There are a number of tests the system designer 

will want to run to ensure the system operates as 

designed. These tests should be performed during 

system development and are dependent on the 

system type and amount of refrigerant charge. These 

application tests are to help identify gross errors in 

system design that may produce conditions that could 

lead to compressor failure. The Continuous Floodback 

Test and Field Application Test, both outlined below, are 

two tests to run to help verify the design. When to run 

these tests can be summarized as follows:

Continuous Floodback:

Required on all heatpumps.

Field Application Test:

Required for any unit where both the design system 

charge is higher than the compressor refrigerant 

charge limit listed in 

Table 3

; and a capillary tube, 

fixed orifice, or bleed-type TXV is used on either 

the indoor or the outdoor coil of the unit.

Continuous Floodback Test

It is expected that the design would not flood during 

standard air conditioning operation. Running a partially 

blocked indoor air filter or loss of evaporator air flow test 

and comparing the sump temperature results to 

Figure 

is recommended. The use of a TXV in heating does 

not guarantee operation without flood back in the lower 

end of the unit/TXV operating range.

To test for excessive continuous liquid refrigerant flood 

back, it is necessary to operate the system in a test 

room at conditions where steady state flood back may 

occur (low ambient heating operation). Thermocouples 

should be attached with glue or solder to the center of 

the bottom shell and to the suction and discharge lines 

approximately 6 inches (15 cm) from the shell. These 

thermocouples should be insulated from the ambient air 

with Permagum® or other thermal insulation to be able 

to record true shell and line temperatures. If the system 

is designed to be field charged, it should be overcharged 

by 15% in this test to simulate overcharging often found 

in field installations.

The system should be operated at an indoor temperature 

of 70°F (21°C) and outdoor temperature extremes of 

10°F (-12°C) or lower in heating to produce flood back 

conditions. The compressor suction and discharge 

pressures and temperatures as well as the sump 

temperature should be recorded. The system should 

be allowed to frost up for several hours (disabling the 

defrost control and spraying water on the outdoor coil 

may be necessary) to cause the saturated suction 

temperature to fall below 0°F (-18°C). The compressor 

sump temperature must remain above the sump 

temperature shown in 

Figure 2

 or design changes 

must be made to reduce the amount of flood back. If an 

accumulator is used, this test can be used to test the 

effectiveness of the accumulator. Increasing indoor coil 

volume, increasing outdoor air flow, reducing refrigerant 

charge,  decreasing  capillary  or  orifice  diameter,  and 

adding a charge compensator can also be used to reduce 

excessive continuous liquid refrigerant flood back.

Summary of Contents for Copeland Scroll ZP K3 Series

Page 1: ...ction Line Noise Vibration 8 Mounting Parts 9 Electrical Connections 9 Deep Vacuum Operation 9 Shell Temperature 9 Suction Discharge Fittings 9 System Tubing Stress 9 Three Phase Scroll Electrical Phasing 9 Brief Power Interruptions 10 Manifolding Tandem Compressors 10 Tandem Applications 10 Application Tests Application Summary 10 Continuous Floodback Test 11 Field Application Test 11 Assembly Li...

Page 2: ...ssor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which if not avoided could result in...

Page 3: ...ety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system commponents Personal safety equipment must be used Failure to follow these warnings could result in serious personal...

Page 4: ...fer to the on line product information at EmersonClimate com for details APPLICATION CONSIDERATIONS The following application guidelines should be considered in the design of a system using ZP K3 ZP KC and ZP KW scroll compressors Some of the guidelines are recommended in this bulletin for good practice or best in class other guidelines must be followed to ensure a safe and reliable application Th...

Page 5: ...in oil pump out and eventual bearing failure A cut out setting no lower than 20 psig 1 4 bar is recommended Discharge Line Thermostat Some systems such as air to air heat pumps may not work with the above low pressure control arrangement A discharge line thermostat set to shut the compressor off before the discharge temperature exceeds 260 F 125 C may have to be used to achieve the same protection...

Page 6: ...ring heating may not require an accumulator if testing assures the system designer that there will be no flood back throughout the operating range To test for flood back conditions and determine if the accumulator or TXV design is adequate please see the Application Tests section The accumulator oil return orifice should be from 040 to 055 inches 1 1 4mm in diameter depending on compressor size an...

Page 7: ...h the minimum run time obtain a sample compressor equipped with a sight tube available from Emerson and install it in a system with the longest connecting lines that are approved for the system The minimum on time becomes the time required for oil lost during compressor startup to return to the compressor sump and restore a minimal oil level that will assure oil pick up through the crankshaft Cycl...

Page 8: ...ing processes that leave solid or liquid contaminants in the evaporator coil condenser coil and interconnecting tubing plus any contaminants introduced during the field installation process Molecular sieve and activated alumina are two filter drier materials designed to remove moisture and mitigate acid formation A 100 molecular sieve filter can be used for maximum moisture capacity A more conserv...

Page 9: ...internal suspension and can be easily avoided by using standard suction line isolation techniques as described in Table 2 The sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends Mounting Parts Table 4 lists the mounting parts to be used with these compressors Many OEM customers b...

Page 10: ...reverse will sometimes make an abnormal sound There is no negative impact on durability caused by operating three phase Copeland Scroll compressors in the reversed direction for a short period of time under one hour After several minutes of reverse operation the compressor s internal overload protector will trip shutting off the compressor If allowed to repeatedly restart and run in reverse withou...

Page 11: ... for any unit where both the design system charge is higher than the compressor refrigerant charge limit listed in Table 3 and a capillary tube fixed orifice or bleed type TXV is used on either the indoor or the outdoor coil of the unit Continuous Floodback Test It is expected that the design would not flood during standard air conditioning operation Running a partially blocked indoor air filter o...

Page 12: ...lined above for the appropriate application tests ASSEMBLY LINE PROCEDURES Installing the Compressor WARNING Use care and the appropriate material handling equipment when lifting and moving compressors Personal safety equipment must be used Copeland Scroll compressors leave the factory dehydrated withadryairholdingcharge Ifcompressors are stored in a cold ambient i e outside during the winter the ...

Page 13: ...onal charge is needed it should be added as liquid to the low side of the system with the compressor operating Pre charging on the high side and adding liquid on the low side of the system are both meant to protect the compressor from operating with abnormally low suction pressures during charging NOTICE Do not operate the compressor without enough system charge to maintain at least 55 psig 3 8 ba...

Page 14: ...ng one side only it is very possible that either the high or low side of the system remains pressurized If a brazing torch is then used to disconnect tubing the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame Instructions should be provided in appropriate product literature and assembly line repair areas If compressor removal is required the comp...

Page 15: ...ecommendations NOTICE It is highly recommended that the suction accumulator be replaced if the system contains one This is because the accumulator oil return orifice or screen may be plugged with debris or may become plugged shortly after a compressor failure This will result in starvation of oil to the replacement compressor and a second failure The system contactor should be inspected for pitted...

Page 16: ... ng Temperature C Condensing Temperature C Condensing Temperature F Evapora ng Temperature F 29 19 9 1 11 21 31 4 14 24 34 44 54 64 40 50 60 70 80 90 100 110 120 130 140 150 160 20 10 0 10 20 30 40 50 60 70 80 90 Evaporating Temperature C Condensing Temperature C Condensing Temperature F Evaporating Temperature F ZP KW Pool Envelope ZP K3 ZP KC Envelope Figure 1a Operating Envelope Figure 1b Opera...

Page 17: ...mpressor Sump Temperature F Evaporating Temperature F 200 F 93 3 C Max Oil Temp Acceptable Unacceptable Too Much Refrigerant Dilu on See Note 1 Note 1 Operation in this refrigerant dilution area is safe in air to air heat pump heating mode For other applications such as AC only review expansion device to raise superheat A cold sump may result in high refrigerant migration after shut down Figure 2 ...

Page 18: ... Label Figure 4 Crankcase Heater Connect the heater so that the connection point straddles the compressor seam weld ZP50 57K3 ZP61 143KC ZP70 83KW Seam Weld WARNING Verify the correct crankcase heater voltage for the application and ensure heater is properly grounded ...

Page 19: ...e Discharge Manifold Assembly Suction Manifold Assembly Mounting Rail 2 Required Compressor to Rail Mounting Kit Tandem to Unit Mounting Kit Figure 5 Typical ZP KC Tandem 12 Min Tilt the Compressor a Minimum of 12 for Installation of the Oil Equalization Line Oil Equalization Line Figure 6 Tilted Tandem ...

Page 20: ...evenly Add braze material to the joint while moving torch around joint to flow braze material around circumference After braze material flows around joint move torch to heat Area 3 This will draw the braze material down into the joint The time spent heating Area 3 should be minimal As with any brazed joint overheating may be detrimental to the final result Field Service WARNING Remove refrigerant ...

Page 21: ...21 2015 Emerson Climate Technologies Inc AE4 1365 R4 Figure 8 ...

Page 22: ...fler Not required Alternate Configuration Component Description Tubing Configuration Shock loop Service Valve Straight through valve not fastened to unit Mass Suction muffler May be required Acts as dampening mass Table 2 Design Configurations Table 3 Compressor Refrigerant Charge Limits Model Frame Size Charge Limit 120 x Limit Tandem Charge Limit Pounds kg Pounds kg Pounds kg ZP50 57K3 ZP70 83KW...

Page 23: ...case Heater 277V 70W 018 0095 09 21 Leads Crankcase Heater Junction Box 998 7024 00 All Models Terminal Cover 005 1213 00 ZP50 57K3 ZP61 91KC ZP70 83KW Terminal Cover Gasket 020 0964 00 Terminal Cover 005 1494 00 ZP104 143KC Terminal Cover Gasket 020 1390 00 Terminal Block 021 0227 03 ZP104 143KC All Voltages Terminal Block 021 0234 00 ZP50 57K3 ZP61 91KC ZP70 83KW 230 Volt Only Terminal Block 021...

Page 24: ...1 1 Phase Only Comfort Alert Module 543 0038 02 All Models 3 Phase Only Discharge Line Thermostat 998 7022 02 ZP50 57K3 ZP61 83KC Fits 1 2 Tube Discharge Line Thermostat not available ZP91KC Fits 3 4 Tube Discharge Line Thermostat 998 0071 02 ZP104 143KC Fits 7 8 Tube Discharge Rotalock Pipe Plug 036 0008 16 ZP104 143KC 1 8 27 NPTF Discharge Rotalock O Ring Seal 028 0028 00 ZP50 57K3 ZP61 83KC Dis...

Page 25: ...required per tandem Includes bolts washers and steel spacers Tandem Mounting Kit Rails To Unit 527 0150 00 ZPT100 114K3 ZPT122 182KC Includes sleeves washers and grommets 35 45 durometer Tandem Mounting Kit Rails To Unit 527 0177 00 ZPT208 286KC Includes sleeves washers and grommets 65 75 durometer Tandem Rail 074 1235 00 ZPT100 114K3 ZPT122 182KC 2 rails required per tandem Tandem Rail 574 0053 0...

Reviews: