background image

5

© 2014 Emerson Climate Technologies, Inc.
Printed in the U.S.A.

AE4-1317 R10

Application Engineering

B

U

L

L

E

T

I

N

If the system is designed where operation with in these 

guidelines cannot be guaranteed, then the discharge line 

thermostat is required in the compressor control circuit.

The thermostats have a cut out setting that will insure 

discharge line temperatures below the 260°F maximum 

limit. It should be installed approximately 7 inches from 

the discharge tube outlet. If a service valve is installed 

at the discharge tube, the thermostat should be located 

5 inches from the valve braze. 

Kits have been set up to include the thermostat, retainer, 

and installation instructions. These thermostats must 

be used with ½” O.D. discharge lines to ensure proper 

thermal transfer and temperature control. They work with 

either 120 or 240-volt control circuits and are available 

with or without an alarm circuit capability. See 

Table 4

 

for a list of discharge line thermostat kit numbers.

Pressure Controls

Both high and low-pressure controls are required on the 

following models, (1.3-2 HP) ZB10-14KCE. Only low-

pressure controls are required on the following models, 

(2-7.5 HP) ZB15-57KC/E. See 

Table 5

 for set points.

Application Note: There are exceptions to the pressure 

settings listed in 

Table 5

. Certain OEMs are approved 

for LPC settings below our standard recommendations.

Pump Down Recommendations
Table 6

 identi

fi

 es the “ZB” models that incorporate 

the low-leak check valve suitable for pump-down 

applications. The standard disc is not intended for use 

with a pump down.

NOTICE

Typically, the compressors that use the low-leak 

discharge check valve are suitable for pump down 

applications. This valve prevents system pressures 

from equalizing and pump down can be achieved. 

However, during laboratory testing, we have observed 

a potential short cycling condition on the ZB15 through 

ZB29 models. This phenomenon can be attributed to 

several factors:

1.  Location of low-pressure control sensor. If it is 

located right at the suction inlet of the compressor, 

it will be more sensitive to pressure spikes. 

2.  Actual low-pressure setting. Refer to our 

recommended setting in 

Table 5.

 If the differential 

pressure setting is too close, this will increase the 

possibility of short cycling.

3.  Type of Low-pressure control can have an effect 

on cycling. The encapsulated non-adjustable type 

is more susceptible to causing excessive cycling 

due to tolerances.

4.  If short cycling cannot be avoided, using a 3-minute 

time delay will limit the cycling of the compressor 

to an acceptable level.

NOTICE

The ZB10 through ZB14 models will require the following 

recommendations for pump down applications:

1.  Install an external check-valve in the discharge 

line to prevent back-

fl

 ow from the high side to low 

side. Install check-valve as close to the compressor 

discharge 

fi

 tting as possible to minimize discharge 

gas volume. 

2.  Set low pressure to recommended settings in 

Table 5

.

3.  Since these models are single-phase only, add 

a time delay relay to prevent reverse rotation. 

Refer to “Brief Power Interruptions” section of this 

bulletin for additional information. 

IPR Valve 

Refrigeration scroll compressors (2-7.5 HP) ZB15-

57KC/E have internal pressure relief valves, which 

open at a discharge to suction differential pressure of 

375 to 450 psi. This action will trip the motor protector 

and remove the motor from the line. The ZB10-14KCE 

models DO require a high pressure control in addition 

to a low pressure control, since these models do not 

have an IPR valve. 

Internal Temperature Protection 

Refrigeration Scroll compressors (1.3-7.5 HP) 

ZB10-57KC/E incorporate a  thermo disc which is a 

temperature-sensitive snap disc device located at the 

scroll discharge port. It is designed to open and route 

hot discharge gas back to the motor protector thus 

removing the compressor from the line.

Motor Protection

Conventional inherent internal line break motor protection 

is provided.  

Oil Types

Polyol ester lubricants must be provided if the scroll 

compressor is to be used with HFC refrigerants. ZBKC 

compressors are intended for use with R22 and are 

supplied with mineral oil. See 

Form 93-11

 for a complete 

list of all Emerson approved lubricants.

Summary of Contents for Copeland Scroll ZBKC

Page 1: ...plications 6 Compressor Tubing and Mounting 6 Mounting for Rack Systems 6 Condensing Unit Mounting 6 Starting Characteristics 6 Fusite 7 Shell Temperature 7 Connection Fittings 7 Three Phase Rotation Direction 7 Brief Power Interruptions 7 Deep Vacuum Operation 7 Unbrazing System Components 7 High Potential Hipot Testing 7 Copeland Scroll Functional Check 8 TABLE OF CONTENTS Section Page Section P...

Page 2: ...hout the lifetime of the compressor You are strongly advised to follow these safety instructions Safety Icon Explanation DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION used with the safety alert symbol indicates a hazardous situation which...

Page 3: ...n oils Personal safety equipment must be used Failure to follow these warnings could result in serious personal injury BURN HAZARD Do not touch the compressor until it has cooled down Ensure that materials and wiring do not touch high temperature areas of the compressor Use caution when brazing system components Personal safety equipment must be used Failure to follow these warnings could result i...

Page 4: ...imum of 20 F 11 C superheat measured on the suction line 6 inches 152mm from the suction valve to prevent liquid refrigerant floodback Another method to determine if liquid refrigerant is returning to the compressor is to accurately measure the temperature difference between the compressor oil crankcase and the suction line During continuous operation we recommend that this difference be a minimum...

Page 5: ...is locatedrightatthesuctioninletofthecompressor it will be more sensitive to pressure spikes 2 Actual low pressure setting Refer to our recommended setting in Table 5 If the differential pressure setting is too close this will increase the possibility of short cycling 3 Type of Low pressure control can have an effect oncycling Theencapsulatednon adjustabletype is more susceptible to causing excess...

Page 6: ...tion and tubing reliability Some tubing geometry or shock loops may be required to reduce vibration transferred from the compressor to external tubing Mounting for Rack Systems For 1 3 7 5 HP compressors specially designed rubber grommets are available for refrigeration scroll compressor applications These grommets are formulated from a durometer material specifically designed for refrigeration ap...

Page 7: ...shell and suction line tubing pressurized If a brazing torch is then applied to the low side the pressurized refrigerant oil mixture could ignite as it escapes and contacts the of start assist devices in most applications However if low voltage conditions exist at start up protector trips can result Therefore start assist devices start capacitorsandrelays areavailabletomaximizestarting characteris...

Page 8: ...ltage 2 Normal motor winding continuity and short to ground checks will determine if the inherent overload motor protector has opened or if an internal short to ground has developed If the protector has opened the compressor must cool sufficiently to reset 3 With service gauges connected to suction and discharge pressure fittings turn on the compressor Ifsuctionpressurefallsbelownormal levels the ...

Page 9: ...ompletely around the joint Slowly move torch inArea 3 to draw braze material into the joint Do not overheat joint 1 2 3 Scroll Tube Brazing Figure 1A ZB KCE Application Envelope for R 404A R 507 1 3 7 5 HP p 10 50 10 120 10 140 45 140 45 80 15 50 10 50 10 120 10 140 15 140 10 100 10 120 40 60 80 100 120 140 160 20 10 0 10 20 30 40 50 60 Condensing Temperature F Evaporating Temperature F 65 F Retur...

Page 10: ...chnologies Inc Printed in the U S A AE4 1317 R10 Application Engineering B U L L E T I N Figure 2A 1 3 7 5 HP Refrigeration Scroll Rack Mounting Figure 2B 1 3 7 5 HP Refrigeration Scroll Condensing Unit Mounting Kit 527 0157 00 ...

Page 11: ...ediate clamps may be necessary 4 Do not hang weights on tubing e g filter drier on suction tubing except after clamps or close to the header 5 Tube runs of less than 8 are not recommended 6 This dimension should be made as short as possible e g 2 or less but still insuring a proper braze joint 7 The above tubing recommendations are based on no elbow joints The use of continuous tubing is preferred...

Page 12: ...ne Thermostat Compressor Contactor Coil Other Protective Devices if used System Operating Thermostat Fuse Optional Condenser Fan Contactor Coil if used Time Delay Relay Specifications Timer Opens 1 Electrical Cycle 016 Seconds with 60 HZ Operation After Power is Removed Timer Closes 2 Minutes 20 Later Whether Power is Restored or Not CSR Current Sensing Relay Contact 230 240 VAC C2 C1 ...

Page 13: ...2 5 R 22 R 404A R 507 R 134a MO POE ZB21KCE 3 0 R 22 R 404A R 507 R 134a R 407A R 407C R 407F MO POE ZB26KCE 3 5 R 22 R 404A R 507 R 134a R 407A R 407C R 407F MO POE ZB29KCE 4 0 R22 R404A R507 R134a R407A R407C R407F POE ZB30KCE 4 0 R 22 R 404A R 507 R 134a R 407A R 407C R 407F MO POE ZB38KCE 5 0 R 22 R 404A R 507 R 134a R 407A R 407C R 407F MO POE ZB42KCE 5 5 R 22 R 404A R 507 R 134a MO POE ZB45K...

Page 14: ... 48 Table 3 Crankcase Heater Model Number Kit Number ZB10 ZB14 N A ZB15 ZB29 998 7026 00 ZB30 ZB57 998 7024 00 Table 3A Conduit Ready Heater Terminal Box Kits Table 4 Discharge Thermostat Line Kits Kit Number Conduit Lead Connector Alarm Contact Discharge Line Diameter 998 0540 00 No No 1 2 998 0548 00 No Yes 1 2 998 7022 02 Yes No 1 2 998 7022 04 Yes No 5 8 998 7022 07 ZB48 ZF25 only Yes No 3 4 T...

Page 15: ... Emerson product remains solely with the purchaser or end user Table 7 Recommended Oil Charges by Model Family Note Theoillevelofrefrigerationscrollcompressors shouldbeadjustedtothemid pointofthesightglass during normal operation Model Family Initial Recharge ZB10KCE 25 22 ZB11 13 14KCE 25 21 ZB15KC E 44 40 ZB19 21 26 29KC E 49 45 ZB30KC E 64 60 ZB38KC E 64 60 ZB45KC E 64 60 ZB48KCE 60 56 ZB57KCE ...

Reviews: