BVE__65155__R06.docx
Replacement for R05
General information:
The BVE/BVS series of Bi-directional Ball valves
are designed for general use in isolating suction,
discharge and liquid line pipe-work during
maintenance shutdown periods.
•
For further information, see technical data sheet
BVE_35066.
Safety instructions:
•
Read installation instructions thoroughly.
Failure to comply can result in device failure,
system damage or personal injury.
•
It is intended for use by persons having the
appropriate knowledge and skill. Before
attempting to install the valve, make sure
pressure in system is brought to and remains at
atmospheric pressure.
•
Do not release any refrigerant into the
atmosphere.
•
Do not use any other fluid media without prior
approval of Emerson. Use of fluid not listed
could result in change of hazard category of
product and consequently change of conformity
assessment
requirement
for
product
in
accordance with European pressure equipment
directive 97/23/EC
•
The attached strap (Fig. 3) contains important
valve data. Do not remove because of warranty
and traceability reasons.
•
Do not connect on BVS Schrader connection
any safety pressure switches or other control
devices
Mounting location:
•
•
Installation:
•
•
•
•
•
•
•
•
Technical Data
Type:
BVE- / BVS-…
≤
≤
≤
≤
28 mm
Connection, DN
1/4” (6mm) … 1-1/8” (28mm)
Max. working pressure PS
Medium temperature TS
–40°C … +120°C (short term +150° C)
Fluid group acc. PED
Refrigerant:
HCFC, HFC
Material
Hazard category: PED 97/23/EC
not applicable
Marking
UL 207
,
!
Date: 18.04.2011
Ball Valves Series BVE / BVS
Operating Instructions
Mounting location:
•
The BVE/BVS valve may be installed in any
position which allows access to remove the stem
cap. The valves are bi-directional.
•
Locate the BVE/BVS as close as possible to the
section of pipe-work to be isolated. This will reduce
the amount of refrigerant to be recovered during
future maintenance of the system.
Installation:
•
Do not remove seal caps until ready for
installation. The seal caps should be removed with
care to avoid damaging the connections.
•
For BVS version do not mount schraeder valve
and cap before brazing.
•
Ensure valve is in the fully open position before
brazing (see Fig. 2a). Failure to do so could cause
damage to internal components.
•
To avoid oxidization, it is advised to purge the
system with an inert gas such as nitrogen while
brazing.
•
When brazing, direct the flame away from the
main body of the valve to avoid possible internal
damage. Use wet rags or other suitable heat
protection (see Fig. 1). On larger body sizes it may
be necessary to re-humidify wet rags with
additional water during brazing process!
To avoid overheating the valve body, it is advised to
make the joint at one end and cool the valve
completely before repeating the procedure on the
other end connection.
For BVS version install schraeder valve and
schraeder valve cap after cooling down of the ball
valve.
For panel mounting see dimension of holes in Fig. 4.
Leakage test:
•
After completion of installation, a test pressure
must be carried out as follows:
- According to EN378 for systems which must
comply with European pressure equipment
directive
- To maximum working pressure of system for
other applications
Warning
:
refrigerant.
Operation:
•
The Valve has a built
opening/closing of the valve is clearly indicated as
shown in Fig. 3. Open Va
and closed valve in Fig. 2b.
•
Never leave the ball position as shown in Fig. 2c
otherwise seat leakage can occur
•
To avoid operation by unauthorized person’s valve
can be equipped with a seal
available as
•
The plastic cap is equipped with an O
not use any tool to mount the cap. Cap must be
closed
hand tight
Warning:
discharge line, the valve has hot surface temperature
during operation of syst
•
The Design pressure marked on this component shall not
be less than the installed system working pressure or less
than the values outlined in ANSI/ASHARE 15 for the
charges refrigerant. After charging mark the installed
equipment with the refrigerant type and Oil used.
•
For use with HFC and HCFC refrigerant listed in
CAN/CSA
B52,
ANSI/ASHARE
34
and
ANSI/ASHARE 15 SEC. 9.2. Where the saturation
pressure at 125°F (High side) and 80°F (Low side) is less
than the maximum design Worki
charging mark Unit with refrigerant type and oil type.
28 mm
BVE- / BVS-…> 32 mm
1/8” (28mm)
1-3/8” (35mm) … 2-5/8” (67mm)
45 bar / 650 psig
(short term +150° C) / –40°F … +250°F (short term +300° F)
II
HCFC, HFC, CO
2
(ASHRAE Standard 34: A1, A2)
CW617N
not applicable
I
, UL 207,
PCN 864 091
GB
US
Leakage test:
After completion of installation, a test pressure
must be carried out as follows:
According to EN378 for systems which must
comply with European pressure equipment
directive 97/23/EC.
maximum working pressure of system for
other applications
:
Failure to do so could result in loss of
refrigerant.
Operation:
The Valve has a built-in stop for the stem and
opening/closing of the valve is clearly indicated as
shown in Fig. 3. Open Valve is shown in Fig. 2a
and closed valve in Fig. 2b.
Never leave the ball position as shown in Fig. 2c
otherwise seat leakage can occur.
To avoid operation by unauthorized person’s valve
can be equipped with a sealable cap which is
available as accessory (see fig. 5).
The plastic cap is equipped with an O-Ring. Do
not use any tool to mount the cap. Cap must be
hand tight
only
.
If the valve is installed in hot gas
discharge line, the valve has hot surface temperature
during operation of system or short after off-cycle.
The Design pressure marked on this component shall not
be less than the installed system working pressure or less
than the values outlined in ANSI/ASHARE 15 for the
charges refrigerant. After charging mark the installed
nt with the refrigerant type and Oil used.
For use with HFC and HCFC refrigerant listed in
CAN/CSA
B52,
ANSI/ASHARE
34
and
ANSI/ASHARE 15 SEC. 9.2. Where the saturation
pressure at 125°F (High side) and 80°F (Low side) is less
than the maximum design Working Pressure. After
charging mark Unit with refrigerant type and oil type.