February 2018
Installation and Operation Manual
E2K-405-0218 Rev. 2
26
Section 3: Installation
Installation
3.8.1 24 Vdc Power Source
If the RDM is to receive power from the actuator, connect cable type Belden 8723
or equivalent as detailed in
Table 3-3
. The cable distance is limited to 1,200 feet
(366 meters).
NOTE:
By using two cables, Belden 8719, or equivalent for power and Belden 9841 or
equivalent for RS-485 communication, the distance limitation is increased to
4,000 feet (1,200 meters).
Figure 3-21 RDM Interface Module (Support Both 24V DC and AC)
P2
SW1 1-6
All manuals and user guides at all-guides.com