Section 5: Customizing Actuator Settings
Customizing Actuator Settings
5.5.9 Network Setup (CAM and Controlinc ACM Required)
NOTE:
Only displayed/applicable if the Communication Adapter Module (CAM) and
the ControIinc ACM are installed, and the network control is enabled.
See
Section 5.5.2, Valve Control Setup.
1.
At the “
NETWORK SETUP?
” prompt, answer “
YES.
”
2.
Use the selector knob (
NEXT/BACK
) to review the settings for
network control.
3.
Use the control knob (
NO
) to increment the node address, response delay,
and analog I/O scale, and to select the parity, and analog scale.
4.
Answer “
YES
” after each selection.
See
Figure 5-14
.
Protocol is set at the factory by the selected CAM based on purchase order
information. Protocol may not be changed by the user in the field. Only factory
technicians may change the CAM or protocol in the field.
Baud rate is automatically defined by the Controlinc ACM and no setup is required.
To calibrate analog inputs, the user must connect a calibrated precision 4-20mA
current source to Terminals 25(+) and 26(-) for AIN#1 or Terminals 27(+) and 28 (-)
for AIN#2. To calibrate analog output, the user must connect a calibrated precision
4-20mA current meter to Terminals 29(+) and 30(-) for AO#1.