Installation and Operating Instructions

1.   Before putting into operation carefully check all electrical connections and the supply voltage (24 VDC ±10 %). 

Overload can destroy the electronics. Recommended pre-fuse T2.0 A.

2.   The electrical connection is made with a round connector M12x1. The connector must meet the requirements of 

DIN 60079-15.

WARNING: 
Do not disconnect the connector while under voltage! 

When disconnected from power, use supplied protection cover to ensure IP protection.

3.   Use shielded cables for the electrical connection of the valve. The shield, connector and control cabinet must 

be EMC compliant. The valve body must be electrically connected to ground (PE, machine ground). Do not run 
control cables parallel to high-voltage lines, servo-motor control cables etc.

4.   Min. wire cross-section of supply voltage cable: 0.25 mm2. 

For longer cabling distances use larger cross-section cables as required.

5.    Make sure that the valve is under pressure when a setpoint signal is applied to the valve (applying a setpoint signal 

with no pressure on the valve will cause it to overheat).

6.  The valve is factory adjusted.

7.  The product must be returned to the factory for repair.

WARNING NOTES 

These products are intended for use in industrial compressed air systems only. Do not use these products where 
pressures and temperatures can exceed those listed under SPECIFICATIONS. Please also see the corresponding 
product specification sheets.

Before using these products with fluids other than those specified, for non-industrial applications, life-support 
systems, or other applications not within published specifications, consult ASCO Numatics.

Through misuse, age, or malfunction, components used in fluid power systems can fail in various modes.

The system designer is warned to consider the failure modes of all component parts used in fluid power 
systems and to provide adequate safeguards to prevent personal injury or damage to equipment in the event 
of such failure.

System designers must provide a warning to end users in the operating manual if protection against a failure mode 
cannot be adequately ensured.

System designers and end users are cautioned to review specific warnings found in instruction sheets packed and 
shipped with these products.

5. Accessories

Description

Catalog Number

Supply cable 5 m; 8x0.50 mm

2

 ; straight connector

TC0805MQX0000000

Supply cable 10 m; 8x0.50 mm

2

 ; straight connector

TC0810MQX0000000

Supply cable 10 m; 8x0.50 mm

2

 ; right-angle connector

TD0810MQX0000000

Programming cable 5 m; M12 Straight 4 Pin Male D-Coded to Male RJ45

QA0405MK0VA04000

Summary of Contents for Aventics SENTRONIC HD 616 Series

Page 1: ...GB IM14277 GB R01 Series616 Installation Manual SentronicHD Digital Electronic Pressure Regulator ...

Page 2: ...89 392 EEC Annex II B is available on request Please provide ordering code and serial numbers of products concerned DECLARATION OF INCORPORATION according to Machinery Directive 89 392 EEC Annex II B We herewith declare that the version of the product described in this installation manual is intended to be incorporated into or assembled with other machinery and that it must not be put into service...

Page 3: ...time The control parameters can be changed with the DaS software This flexibility allows the valve to be adapted to the most various applications and its response time overshoot and precision to be optimised After having set the optimum parameters you can save them in a project file for your personal use or send them to our Product Support for future serial production 1 1 How to Order SentronicHD ...

Page 4: ...st 8 Ground connection M4 thread 1 3 Operating Modes Shut off If the setpoint falls below 0 5 the pilot valves are switched off and the valve is fully exhausted Overtemperature If the temperature of the internal control electronics exceeds 100 C the operating mode is switched to AUTOSAFE Autosafe If the coil current exceeds a certain value dependent on the mechanics for more than 20 seconds the ou...

Page 5: ... varistor must be used 4 A shielded cable must be used for protection against interference and EMC 5 The valve body must be grounded with the earthing terminal PE dia M4 Ethernet IP Programming Interface M12 Cable Plug 4 pole D coded M12 male connector 8 pin A coded View on male connector the device is equipped with a female connector The use of a shielded cable is recommended View on valve Pin De...

Page 6: ...ed to the PMR In order to avoid damaging the sensor the supply pressure must always be less than the maximum inlet pressure MAP see Technical Characteristics Setpoint span The pressure span of the setpoint can be changed via the DaS HD software Switch Module 1 to Rescale in the Parameter Setpoint section The span is between 10 and 150 Offset Adjustment SHUT OFF Max outlet pressure PMR 50 PMR 50 mV...

Page 7: ...d or not Class 5 to ISO 8573 1 Ports G1 4 Max Inlet Pressure 174 psi 12 bar Pressure Range see Section 1 1 Temperature Fluid 32 122 F 0 50 C Temperature Ambient 32 122 F 0 50 C Hysteresis 0 25 of span Linearity 0 25 of span Reliability 0 25 of span 4 2 Specification Nominal Diameter DN Stabilized Voltage Max Power W Max Cur rent mA Insulation Class Degree of Protec tion Flow Electrical Connection ...

Page 8: ...ct must be returned to the factory for repair WARNING NOTES These products are intended for use in industrial compressed air systems only Do not use these products where pressures and temperatures can exceed those listed under SPECIFICATIONS Please also see the corresponding product specification sheets Before using these products with fluids other than those specified for non industrial applicati...

Page 9: ... or care required 7 Dimensions mm Weight kg Weight 1 6 kg 20 7 143 0 3 42 95 122 3 16 55 59 5 0 2 G1 4 x 10 18 0 2 50 0 2 G1 4 x 10 29 75 0 2 43 0 2 78 26 89 6 12 29 75 0 2 35 0 2 G1 4 x 10 51 0 2 14 0 2 46 0 2 19 0 2 14 0 2 46 0 2 14 0 2 46 0 2 68 75 29 75 PE M12 female connector M12 connector 8 pins 4 pin Ethernet M4 x 8 1 M4 x 10 M4 x 10 2 3 M4 x 10 M4 x 10 ...

Reviews: