Page 15
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1.6.3 Function outputs and alarms
Two function outputs per channel with separate configuration for functions and alarm limits.
Function and switching characteristics are configured separately.
Limit settings
During configuration freely selectable depending on the relevant function. With functions
rotational direction and standstill no alarm limits.
Adjustment range
0 ... 100 % of the configured measuring range
Resolution
≤
0,1 % of full scale.,
1 rpm in speed range 0...12000 rpm
Hysteresis
freely selectable
Reaction time
Delay time between calculation of characteristical value and reaction of the limit output (only
valid for output function limit).
average reaction time
2 ms
Alarm blocking
Blocking
if (supply or watchdog not ok) ODER
(Ex. locking = lock)
ODER
(channel status = not ok*)
No blocking
if condition above are not met
* During configuration it can be defined whether or not blocking of the alarm outputs shall be
controlled by the channel supervision.
Alarm visualization
By means of two yellow LEDs for channel 1 and channel 2.
No limit exceeded or alarms blocked LED off
Limit eceeded or function „true”
LED switched on (steady light)