Configuration Menu
Operation • 11
3.2.2. Configuration Menu — Modbus Device Baud Rate
The second configuration menu (see
) allows users to change the Modbus
device baud rate. “
br
” is shown on the right side of the display to indicate which
parameter is being changed (
br
stands for Baud Rate). To change the value, press
either the up or down arrow, and then press the check icon to go to the next
parameter. Press
CA
to cancel and exit the configuration menu without saving any
changes.
0
9600 bps
1
19200 bps (default)
3.2.3. Configuration Menu — Thermostat System Configuration
The third configuration menu (see
) allows users to set the thermostat
system configuration.
SC
is shown on the right side of the display to indicate which
parameter is being changed (
SC
stands for System Configuration). The current
revision of the Emerson Programmable Touchscreen Thermostat supports
Conventional HVAC Systems such as RTU and Heat-pump Systems using a
reversing valve. There are 4x possible configurations: IDLE, RTU, HP_O and
finally HP_B. The first system configuration is IDLE. In this configuration, all the
outputs of the thermostats are open and the thermostat controls are inactive. This is
to prevent any issue in current configuration compared to the equipment connected
Figure 3-4
- Modbus Baud Rate Configuration Menu
Menu Option Number
Corresponding Baud Rate
Table 3-2
- Modbus Baud Rate