Controls and Indicators
24
7.3
Load Level Indicators (4 Green, 1 Amber)
The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative
load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in
Figure 19
.
The load level indicators display the approximate electrical load placed upon the UPS at all times.
Figure 19 Load level indicators
7.4
Battery Level Indicators (5 Green)
The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate
the battery capacity level. The Liebert GXT3 battery capacity level is shown in 20% increments (±5%).
The battery level indicators will illuminate as shown in
Figure 20
The battery level indicators display approximate battery capacity at all times.
The Liebert GXT3 is equipped with automatic and remote battery test features. The default setting is
for the automatic test to occur every 14 days (this option is user-configurable) if utility power has not
been interrupted. Should the battery fail this test, the red Fault indicator LED along with the A and
C diagnostic LEDs will illuminate and an alarm will sound (refer to
11.0 - Troubleshooting
). The
remote test feature functions with Liebert MultiLink and can remotely initiate the battery test.
Figure 20 Battery level indicators
0 - 25%
Overload
76 - 100%
51 - 75%
26 - 50%
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
The Liebert GXT3 has
load level indicators for
Line 1 and for Line 2. One
set of indicators shown
for clarity.
0 - 20%
Fully
Charged
81 - 100%
61 - 80%
41 - 60%
21 - 40%
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
Discharging
Flash OFF
OFF
OFF
OFF
OFF
ON
ON
ON
Flash
ON
ON
Flash OFF
OFF
ON
Flash OFF
OFF
OFF
Flash
ON
ON
ON
ON
ON
ON
ON
ON
ON
Charging