Specifications
43
Using the configuration program, the user may specify the number of external battery cabinets
attached to the UPS. The factory default is programmed for internal batteries only.
Table 14
shows the estimated run times at different loads.
Table 14
Battery run time, minutes
Number of
Batteries
Load
Run Time, Minutes
GXT3-6000RTL630 GXT3-5000RT208 GXT3-6000RT208 GXT3-8000RT208 GXT3-10000RT208
Internal
Battery
30%
40
30
23
34
26
40%
27
22
17
25
18
50%
21
16
12
18
13.5
60%
16
12
10
14
11
70%
13
10
7
12
8
80%
11
8
5.5
9
7
90%
9
6
4.5
8
6
100%
8
5
4
7
4.5
Internal
B 1
External
Battery
Cabinet
30%
70
72
53
75
60
40%
48
47
38
57
39
50%
36
42
29
42
32
60%
29
30
24
33
25
70%
24
25
20
27
21
80%
19
21
16
23
18
90%
16
18
14
21
16
100%
14
16
12
17
13
Internal
B 2
External
Battery
Cabinet
30%
110
106
86
120
92
40%
78
78
72
86
70
50%
60
63
48
70
52
60%
48
49
41
56
41
70%
40
42
35
47
34
80%
34
36
28
39
29
90%
30
30
24
33
26
100%
25
25
21
29
23
Internal
B 3
External
Battery
Cabinet
30%
150
140
124
180
125
40%
110
105
86
120
90
50%
82
82
72
90
72
60%
76
71
54
72
60
70%
59
58
47
64
47
80%
46
48
38
57
39
90%
41
42
34
48
35
100%
36
37
30
43
32
Internal
B 4
External
Battery
Cabinet
30%
200
200
158
230
180
40%
160
150
110
150
120
50%
110
103
88
120
90
60%
96
86
72
95
72
70%
78
72
63
82
65
80%
65
64
49
70
54
90%
57
54
45
63
47
100%
46
48
41
56
39