background image

Symptom

Symptom

Symptom

Symptom

Symptom

P

P

P

P

Possib

ossib

ossib

ossib

ossible Cause

le Cause

le Cause

le Cause

le Cause

Corrective Action

Corrective Action

Corrective Action

Corrective Action

Corrective Action

Heat, Cool or Fan Runs Constantly.

Heat, Cool or Fan Runs Constantly.

Heat, Cool or Fan Runs Constantly.

Heat, Cool or Fan Runs Constantly.

Heat, Cool or Fan Runs Constantly.

1. FAN Switch set to Fan ON.

Check each wire connection to verify they are

2. Possible short in wiring.

not shorted or touching together. No bare wire

3. Possible short in thermostat.

should stick out from under terminal screws.

4. Possible short in Heat/Cool/Fan system.

Try resetting the thermostat. If the condition
persists the manufacturer of your system
or service person can instruct you on how
to test the Heat/Cool system for correct
operation. If the system operates correctly,
replace the thermostat.

Furnace Cycles Too Fast or Too Slow

Furnace Cycles Too Fast or Too Slow

Furnace Cycles Too Fast or Too Slow

Furnace Cycles Too Fast or Too Slow

Furnace Cycles Too Fast or Too Slow

1. The location of the thermostat and/or the size

Item 2 in the Configuration Menu is the adjustment

(narrow or wide temperature swing)

(narrow or wide temperature swing)

(narrow or wide temperature swing)

(narrow or wide temperature swing)

(narrow or wide temperature swing)

of the Heating System may be influencing the

that controls the cycle rate. If an acceptable cycle

cycle rate.

rate is not achieved using the FA (Fast) or SL
(Slow) adjustment contact a local service person for
additional suggestions.

Cooling Cycles Too Fast or Too Slow

Cooling Cycles Too Fast or Too Slow

Cooling Cycles Too Fast or Too Slow

Cooling Cycles Too Fast or Too Slow

Cooling Cycles Too Fast or Too Slow

1. The location of the thermostat and/or the size

The cycle rate for cooling is fixed and can not be

(narrow or wide temperature swing)

(narrow or wide temperature swing)

(narrow or wide temperature swing)

(narrow or wide temperature swing)

(narrow or wide temperature swing)

of the Cooling System may be influencing the

adjusted. Contact a local service person for

 cycle rate.

suggestions.

Thermostat Setting and Thermometer

Thermostat Setting and Thermometer

Thermostat Setting and Thermometer

Thermostat Setting and Thermometer

Thermostat Setting and Thermometer

1. Thermostat thermometer setting requires

The thermometer can be ad/- 4 degrees as

Disagree

Disagree

Disagree

Disagree

Disagree

 adjustment.

listed in item 7 of the Configuration Menu. No other
adjustment is possible.

Clock Loses or Gains Time

Clock Loses or Gains Time

Clock Loses or Gains Time

Clock Loses or Gains Time

Clock Loses or Gains Time

1. Loss of power to thermostat and low batteries.

The thermostat will maintain its program in memory
even with no power/no batteries but the clock time
will be incorrect when power is restored. See No
Heat/No Cool/No Fan (common problems) above
for items to check in the system.

Heat or Cool Starts Early

Heat or Cool Starts Early

Heat or Cool Starts Early

Heat or Cool Starts Early

Heat or Cool Starts Early

1. EMR activated

See Configuration Menu (Item 4).

Thermostat Does Not Follow Program

Thermostat Does Not Follow Program

Thermostat Does Not Follow Program

Thermostat Does Not Follow Program

Thermostat Does Not Follow Program

1. AM or PM set incorrectly in program.

Check current clock and program settings including

2. AM or PM set incorrectly on the clock.

the AM or PM designations for each time period.

3. Voltage spike or static discharge.

If a voltage spike or static discharge occurs use the
Reset Operation listed above.

Blank Display and/or Keypad Not

Blank Display and/or Keypad Not

Blank Display and/or Keypad Not

Blank Display and/or Keypad Not

Blank Display and/or Keypad Not

1. Loss of power and dead batteries.

Replace batteries and check heat/cool system for

Responding

Responding

Responding

Responding

Responding

2. Voltage Spike or Static Discharge.

proper operation. If a voltage spike or static discharge
occurs use the Reset Operation listed above.

TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

TROUBLESHOOTING

www.white-rodgers.com

St. Louis, Missouri

Markham, Ontario

The Emerson logo is a
trademark and service mark 
of Emerson Electric Co.

HOMEOWNER HELP LINE:  1-800-284-2925

Summary of Contents for 1F80-361

Page 1: ...e on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Higher voltage will damage control and could cause Higher voltage will damage control and could cause Higher voltage will damage control and could cause H...

Page 2: ... THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL 1 Remove the packing material from the thermostat Gently pull the cover straight off the base Forcing or prying on the thermostat will cause damage to the unit If necessary move the electric heat switch see ELECTRIC HEAT SYSTEMS ELECTRIC HEAT SYSTEMS ...

Page 3: ...g Valve RC O B C JUMPER WIRE Compressor Contactor JUMPER WIRE Reversing valve is energized when the system switch is in the HEAT position Fan Relay The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a year with fresh premium brand alkaline batteries Heating System Heating System Heating System Heating System Heating System 1 Move SYSTE...

Page 4: ...Press RUN to make sure the thermostat is in the run program mode then press PRGM and RUN at the same time to enter the configuration menu The display will show the first item in the configuration menu The configuration menu table summarizes the configuration options An explanation of each option follows OPERATION OPERATION OPERATION OPERATION OPERATION Press HOLD to change to the next menu item or...

Page 5: ...emperature to match your previous thermostat 8 8 8 8 8 Select F or C Readout Select F or C Readout Select F or C Readout Select F or C Readout Select F or C Readout Changes the display readout to Centigrade or Fahrenheit as required OPERATING FEATURES OPERATING FEATURES OPERATING FEATURES OPERATING FEATURES OPERATING FEATURES Now that you are familiar with the thermostat buttons and display read t...

Page 6: ...mmed times and tempera tures follow these steps Determine the time periods and temperatures for your weekday and weekend programs You must program four periods for both the weekday and weekend program However you may use the same heating and cooling temperatures for consecutive time periods You can choose start times heating tempera tures and cooling temperatures independently for both week day an...

Page 7: ...rmo stat by pressing and TIME at the same time This also resets the factory defaults to the configuration menu and Symptom Symptom Symptom Symptom Symptom P P P P Possib ossib ossib ossib ossible Cause le Cause le Cause le Cause le Cause Corrective Action Corrective Action Corrective Action Corrective Action Corrective Action No Heat No Cool No Fan No Heat No Cool No Fan No Heat No Cool No Fan No ...

Page 8: ...einfluencingthe adjusted Contactalocalservicepersonfor cyclerate suggestions Thermostat Setting and Thermometer Thermostat Setting and Thermometer Thermostat Setting and Thermometer Thermostat Setting and Thermometer Thermostat Setting and Thermometer 1 Thermostatthermometersettingrequires Thethermometercanbeadjusted 4degreesas Disagree Disagree Disagree Disagree Disagree adjustment listedinitem7o...

Page 9: ... o por un electricista autorizado No exceda los valores nominales especificados Todas las conexiones eléctricas deben cumplir con los códigos y reglamentaciones locales y nacionales Este control es un instrumento de precisión y debe manipularse con cuidado Lamanipulacióndescuidadaoladistorsióndeloscomponentes podrían hacer que el control no funcionara correctamente PRECAUCIÓN Para evitar descargas...

Page 10: ...a unidad Si es necesario mueva el interruptor de calor eléctrico vea la sección SISTEMAS DE CALOR ELÉCTRICOS más arriba 2 Conecte los cables que se encuentran debajo de los tornillos terminales a la base consultando el esquema de conexiones apropiado vea las figuras 2 a 7 3 Coloquelabasesobreelorificiodelaparedymarquelasubicaciones de los orificios de montaje usando la base como plantilla 4 Mueva ...

Page 11: ...r CABLE DE PUENTE La válvula inversora se energiza cuando el interruptor del sistema está en la posición COOL Relé del ventilador SISTEMA TERMOSTATO Vivo Neutro RH Y 24 VCA 120 VCA Vivo Neutro G W Figura 7 Diagrama de conexiones típico para una bomba de calor con válvula inversora energizada en HEAT TRANSFORMADOR Válvula inversora RC O B C CABLE DE PUENTE Contactor del compresor CABLE DE PUENTE La...

Page 12: ...en el menú de configuración La pantalla mostrará la primera opción del menú de configuración En la tabla del menú de configuración se resumen las diferentes opciones de configuración disponibles seguidas por una explicación de cada una OPERACIÓN Presione HOLD para pasar a la siguiente opción del menú o presione TIME para volver a la opción anterior Para salir del menú y volver a la operación del p...

Page 13: ...s centígrados o Fahrenheit según su preferencia FUNCIONES DEL TERMOSTATO Ahoraqueestáfamiliarizadoconlosbotonesdeltermostatoylapantalla lea la siguiente información para conocer las diferentes funciones del termostato ALMACENAMIENTO SIMULTÁNEO DE PROGRAMAS DE CALEFACCIÓN REFRIGERACIÓN Cuando programe el termostato puede ingresar sus programas de calefacción y refrigeración al mismo tiempo No es ne...

Page 14: ...mine las horas y temperaturas para sus programas semanales y de fines de semana Debe programar cuatro períodos para el programa semanal y cuatro para el programa de fin de semana No obstante puede usar las mismas temperaturas de calefacción y refrigeración durante períodos consecutivos Puede elegir las horas de inicio las temperaturas de calefacción y las temperaturas de refrigeración de maneraind...

Page 15: ...enda cambiar las pilas una vez al año por pilas alcalinas nuevas AA Síntoma Causa posible Acción correctiva El sistema no calienta El sistema no enfría No funciona el ventilador problemas comunes 1 Se quemó el fusible o se disparó el disyuntor 2 El interruptor de alimentación de la caldera está en OFF 3 La puerta o el panel del compartimiento del soplador de la caldera están sueltos o no están bie...

Page 16: ...los de refrigeración son demasiado cortos o demasiado largos oscilación reducida o amplia de la temperatura 1 La ubicación del termostato y el tamaño del sistema de refrigeración pueden influir en la duración del ciclo La duración del ciclo de refrigeración es fija y no se puede ajustar Póngase en contacto con personal de servicio local para que le sugiera otras soluciones El ajuste del termostato...

Reviews: