background image

30

“Set-Point pH” (PWM)

This mode is valid for “Digital D1” output. Pulse-width modulation (PWM) of a signal or power source involves the 

modulation of its duty cycle, to either convey information over a communications channel or control the amount of power 

sent to a load.

This mode works over a settable (0 to 100 seconds) time to switch on or off selected output. 

During this time if reading value will move towards a set value (on or off) the PWM will operate the output on timered 

basis. Reaching the set value the PWM will permanently leave on or off the output.

Parameters to set for this mode are: 

Unit Value + %: 

(time activity towards set value. 0% means 0 seconds. 100% means 100 seconds.

)

pH range: 

two pH values within PWM operates.

For example: set first pH value at 8.00 = 100% and second pH value at 4.0 = 0%.

For reading values ≥ to 8.00 the output will be permanently ON.

For reading values ≤ 4.0 the output will be permanently OFF.

For reading value of 7.00 the output will be OFF for 25 seconds, ON for 75 seconds.

For reading value of 6.00 the output will be OFF for 50 seconds, ON for 50 seconds.

4.00

   5.00    6.00    7.00    

8.00

ON

OFF

0%

             50%    75%    

100%

Summary of Contents for MTOWER PLUS CD

Page 1: ...UCTIONS F O R MTOWER PLUS INSTRUMENT This manual contains safety information that if ignored can endanger life or result in serious injury They are indicated by this icon Keep the instrument protected...

Page 2: ...must be serviced and repaired by qualified and authorized personnel only Always discharge the liquid end before servicing the instrument Empty and rinse the liquid end before work on a pump which has...

Page 3: ...nstrument can be easily programmed MTOWER PLUS is housed in a IP65 plastic box Measures are L325 x H235 x D125 including wheel and connectors Main features of MTOWER PLUS are BLEED INHIBITOR with 5 wo...

Page 4: ...E N F1 fuse protected Inhibitor 3 E N F1 fuse protected D1 mV Biocide 1 4 E N F1 fuse protected Biocide 2 5 E N F1 fuse protected Pre biocide 1 6 E N F1 fuse protected Pre biocide 2 Bleed Valve Free V...

Page 5: ...vel 37 38 Inhibitor Level 54 55 pH Level FLOW sensor mod SEPR input 39 Brown 40 Black 41 Blue 41 shortcut with block n 37 MANIFOLD input 39 White 40 Black 41 shortcut with block n 37 Hall effect pulse...

Page 6: ...ds through the fill by gravity while in direct contact with air that passes over it The cooled water is then collected in a cold water basin below the fill from which it is pumped back through the pro...

Page 7: ...e fill and spray zones of the tower Blow out Water droplets blown out of the cooling tower by wind generally at the air inlet openings Water may also be lost in the absence of wind through splashing o...

Page 8: ...up water thereby allowing precise control of the chemical concentration in the make up liquid Further a bleed valve is provided which is responsive to the vacuum produced at the injector valve and bl...

Page 9: ...bleed activity time exceeded Check biocide 1 or 2 menu Alarm status Message Explanation Action Required ALARM ALARM Output 10 11 12 active see contact mode Check alarm by rotating wheel in main scree...

Page 10: ...Water Meter Bleed Bleed water input totalizer Water Meter Delta Plant water totalizer delta between WMI and WMB Status Level PreBiocide 1 or 2 Pre Biocide 1 or 2 tank level Biocide 1 or 2 Biocide 1 o...

Page 11: ...first time here then the PASSCODE is 0000 factory preset Press wheel 5 times to grant access Otherwise press the wheel 1 time and enter the PASSCODE Numbers can be selected by rotating the wheel To s...

Page 12: ...wheel To end procedure move cursor on EXIT and press wheel to proceed to Save request screen Move wheel on YES to save or NO to discard changes WARNING when programming instrument BIOCIDE check into S...

Page 13: ...t standard or IS international unit standard See table for differencies EUROPE IS Internationl Standard USA Date DD MM YY Date MM DD YY Time 24h Time AM PM C Celsius F Farhenheit Liters Gallons To cha...

Page 14: ...Scale Conductivity calibration procedure involves a zero calibration P1 and a 2nd calibration point P2 that requires a buffer solution with value near working range Furthermore TE Temperature and CA A...

Page 15: ...f other solutions simply measure conductivity at a range of temperatures and graORP the change in conductivity versus the change in temperature MTOWER PLUS has either fixed or adjustable automatic tem...

Page 16: ...connected Otherwise unattended results may occurr Calib 1st Point Once into pH Calibration menu move wheel on P1 then press wheel to enter into first point calibration submenu Prepare 7 00pH buffer s...

Page 17: ...ading value is stable and according to buffer solution value move wheel until it is the same on display Cal at field Default value is 4 00pH To end procedure rotate cursor on OK and move on TE submenu...

Page 18: ...ion referenced to a standard temperature of 25 C For manual temperature compensation move cursor on TE press wheel and adjust manual temperature compensation Move cursor on OK and press wheel again Mo...

Page 19: ...t buffer solution should be near working value From Probe menu choose Calibration mV In the following example instrument will calibrate ORP using default buffer solutions values Note this procedure as...

Page 20: ...alue read by the pumps group and the quantity of residual chlorine expressed in mg litre and are linked to the pH value To end procedure move cursor on OK and press wheel to proceed to Save request sc...

Page 21: ...edure assumes that instrument is correctly installed and configured connected to a working probe Calibrate using plant s temperature otherwise unattended results might occur Using an external thermome...

Page 22: ...rating time for feeding procedure will be active for a time T every C water meter pulses Before setting this mode first configure Flow meter menu from Menu Setup E g T 00h 30m and C 0050 Inhibitor act...

Page 23: ...will activate 6 E N output Lockout LCK This option lock keep closed bleed valve for set time at the end of biocide activity Week WK This option set events repetitivity on daily basis for set amount of...

Page 24: ...etup choose Bleed and configure the following parameters Setpoint target value for conductivity Dead Band MTOWER PLUS opens bleed valve when reaching setpoint and it leaves valve opens until conductiv...

Page 25: ...to change it Set Point ORP on off mode Digital D1 This mode is valid for Digital D1 output On Off mode set the instrument to operate using two set values that enable or disable the ORP pump To use thi...

Page 26: ...f reading value will move towards a set value on or off the PWM will operate the output on timered basis Reaching the set value the PWM will permanently leave on or off the output Parameters to set ar...

Page 27: ...ect it PROPORTIONAL MODE between 700 0 P m and 680 180 P m P m pulses per minute This mode operates ORP pump for a value lower that 680mV with maximum dosing capacity 180strokes and it will stop ORP p...

Page 28: ...ode set the instrument to operate using two set values that enable or disable the pH pump To use this mode move cursor on Working Mode Press the wheel and select it ON OFF mode while dosing ALKALI Set...

Page 29: ...se especially for soluble bases This broad use of the term is likely to have come about because alkalis were the first bases known to obey the Arrhenius definition of a base and are still among the mo...

Page 30: ...ut on timered basis Reaching the set value the PWM will permanently leave on or off the output Parameters to set for this mode are Unit Value time activity towards set value 0 means 0 seconds 100 mean...

Page 31: ...Press the wheel and select it PROPORTIONAL mode between 7pH 0 P m and 8pH 180 P m p m is pulses per minute In this mode the pH pump will be ON for values greater than 8pH with maximum set pulses per...

Page 32: ...er for water meter bleed working mode and counters reset To end procedure move cursor on EXIT and press wheel to proceed to Save request screen Move wheel on YES to save or NO to discard changes WMI M...

Page 33: ...set to 1000 Alarm will switch on at 3000 HIC HIGH CONDUCTIVITY alarm HPH HIGH pH alarm HMV HIGH ORP alarm OFF alarm disabled ABS absolute alarm on set value TRK track alarm on bleed setpoint minus tra...

Page 34: ...nfiguration Set to 4 20 mAfor 4 setpoint low and 20 setpoint high mode Set to 0 20 mAfor 0 setpoint low and 20 setpoint high mode Cd mA High and Cd mA Low are related to maximum and minimum conductivi...

Page 35: ...NHIB This option manually operate inhibitor output on 2 E N blocks OUT PRE BIO 1 This option manually operate pre biocide 1 output on 5 E N blocks OUT PRE BIO 2 This option manually operate pre biocid...

Page 36: ...board temperature input MDIND 8 WIRES CABLE 4 PROBE WIRES 4 PT100 WIRES Connect 4 probe wires to MDIND module as follows Block n 1 blue Block n 2 black Block n 3 grey Block n 4 red Connect 4 PT100 wi...

Page 37: ...enclosure NEMA4x MTOWER control instruments are ma nufactured in ABS housing to ensure protection against aggressive chemi cals and tough environment ENCLOSURE 10 C 50 C 14 F 122 F 0 95 non condensing...

Page 38: ...ing wrong occurrs SMS number must be set using local number format For example 3391349134 will send an SMS message to mobile phone Log level and SMS frequency alert may be set using options in ACTIVE...

Page 39: ...address is simi lar to using a pay phone Unless there is a reason to receive a call the user does not care what number he or she is calling from There are times however when users who connect to the I...

Page 40: ...C Email menu If Ethernet module or GPRS module is installed sold as option the instrument can be configured to send email alarm messages up to two recipients Click on Email 1 or Email 2 and enter emai...

Page 41: ...t instrument s activities To obtain reliable results with this feature please set instrument ID and NAME from RS485 Setup menu and activate log recording from LOG SETUP menu HOW TO RECORD INSTRUMENT S...

Page 42: ...Simple and robust it has since become a de facto standard communication protocol and it is now a commonly available means of connecting industrial electronic devices From main menu select SETUP then...

Page 43: ...43 Appendix C Motorized valve connection...

Page 44: ...he alarm will be notified into main screen and water meter status see page 6 FM Input can be set to operate Water Meter as 0 20mA or 4 20mA input P L pulses per liter or L P liters per pulse Tot WMI w...

Page 45: ...ppears move wheel on it then click Enter WEP WPA WPA2 password if required and wait until connection has been estabilished and WiFi signal strength appears To obtain a reliable connection be sure to i...

Page 46: ...46...

Page 47: ...ion Temp menu page 21 Inhibitor menu page 22 Biocide 1 and Biocide 2 menu page 23 Bleed menu page 24 Set Point mV menu modes page 25 Set Point mV on off mode D1 page 25 Set Point mV PWM mode D1 page 2...

Page 48: ...ial types and send them according to local recycling disposal requirements We appreciate your efforts in supporting your local Recycle Environmental Program Working together we ll form an active union...

Reviews: