background image

   6

SW12.T

Controllable actuators

Ref.

Description

EIM1 - EA20 - EA20/SE

Linear operator 12 V 2 m 

EA25 - EA25/SE

Linear operator 12 V 2,5 m

EA50 - EA50/SE

Linear operator 12 V 3,5 m

EI20 - EI20/SE - EI20/21

Underground operator 12 V 2 m

ZI26

Underground operator 12 V 2 m

ZI27

Underground operator 12 V 3 m

Trimmer function

Trimmer Description
TCA

Automatic re-closing time (adjustable from 2 to 120 seconds, turn the trimmer clockwise to increase the time)

FM1

Power of motor M1 (adjusts the torque of motor M1, turn the trimmer clockwise to increase the force)

FM2

Power of motor M2 (adjusts the torque of motor M2, turn the trimmer clockwise to increase the force)

VS

Slow speed (adjusts the slow speed of both motors, turn the trimmer clockwise to increase the speed)

V

Standard speed (adjusts the standard speed of both motors, turn the trimmer clockwise to increase the speed)

Button functions

Button

Description

PROG

Button for programming the travel

MRX

Button for programming or deleting remote controls

51

Step-by-step command button

DIP-switch functions

Dip

Function

Status Description

DIP 1

Automatic 

closing

OFF

Automatic closing off

ON

Automatic closing on

DIP 2

Apartment 

block

OFF

Apartment block on (while the gate is opening, you cannot stop the movement with a radio command or with inputs 

51 (step-by-step) and 52 (pedestrian). With automatic closing on (DIP 1 = ON) and the gate open, an additional 

step-by-step command (terminal 51 or radio command) renews the pause time, and if input 51 remains engaged, 

the control panel suspends the pause count until the input is disengaged (for connecting any coils or a timer)

ON

Apartment block off

DIP 3

Pre-flash

OFF

Pre-flashing off

ON

Pre-flashing on, before the gate moves the flashing light comes on for 3 seconds

DIP 4

Input 63 type

OFF

Input 63 is for internal photocell

ON

Input 63 is for safety edge (see DIP 7 for the safety edge type)

DIP 5

Photo test

OFF

Photo-test function off

ON

Photo-test on: the negative accessory power supply terminal (0) turns off for a few fractions of a second before the 

start of movement, so any accessories that require a permanent power supply (e.g. photocell receivers) must get 

the negative power supply from an input common (terminal 99).

DIP 6

Output 12

OFF

Output 12 for Courtesy Light (LCO): each time the gate moves, the output remains on for 100 s. 

The remote control buttons saved on the second radio channel give a pedestrian command

ON

Output 12 for Auxiliary Radio output: the remote control buttons saved on the second radio channel turn the output on for 1 s

DIP 7

Safety edge 

type

OFF

Sensitive edge with normally closed contact

ON

Resistive sensitive edge, normally open contact with balancing resistance of 8.2 K Ohm in parallel

DIP 8

Rapid closing

OFF

Fast closing off

ON

Fast closing function on: if the closing photocell (terminal 62) is engaged, the automatic closing time is set to 5 

seconds when it is released

DIP 9

Hammering

OFF

Hammering function for electric lock off

ON

Hammering function for electric lock on (facilitates the unlocking and resetting the electric lock)

DIP 10

Motor with/

without encoder

OFF

The motors connected are equipped with encoders

ON

The motors connected are not equipped with encoders

LED functions

LED

Status

Description

PWR

OFF

Mains power supply not present

ON

Mains power supply present

PRG 

(or flashing light)

2 blinks

Photocell test failed (incorrect wiring or photocells busy)

3 blinks

Problem detected in the circuit that activates motor M1

4 blinks

Problem detected in the circuit that activates motor M2

5 blinks

Problem on encoder M1 (encoder M1 damaged or wired incorrectly)

6 blinks

Problem on encoder M2 (encoder M2 damaged or wired incorrectly)

7 blinks

Serious EEPROM error (EEPROM missing or damaged)

EN

Summary of Contents for Vimar SW12.T

Page 1: ...12 Vdc control panel for swing gates Centrale de commande 12 Vcc pour portails battants Central de mando 12 Vcc para cancelas batientes Steuerger t 12 Vdc f r Drehtorantriebe 12 Vdc C BAT U2 N8 F1 AT...

Page 2: ...ivo lampeggiante Morsetto Descrizione Dati nominali E Positivo alimentazione encoder 12 Vdc E Negativo alimentazione encoder 41 Segnale encoder motore 1 45 Segnale encoder motore 2 99 Comune ingressi...

Page 3: ...esso 63 come fotocellula interna ON Ingresso 63 come bordo sensibile per tipo bordo sensibile vedere DIP 7 DIP 5 Foto test OFF Funzione foto test non attiva ON Funzione foto test attiva il morsetto al...

Page 4: ...velocit rallentata fino al fermo meccanico in apertura 5 Apertura anta M2 M2 apre a velocit rallentata fino al fermo meccanico in apertura 6 Chiusura anta M2 M2 chiude a velocit normale al 70 della c...

Page 5: ...anta M1 M1 chiude a velocit normale fino al fermo meccanico in chiusura 8 Ciclo completo Il cancello esegue un ciclo completo di apertura e di chiusura con gli spazi di rallentamento e con gli sfasam...

Page 6: ...ando memorizzato nuovo radiocomando 3 lampeggi Memoria piena Programmazione del secondo canale radio N Pressione pulsante Segnalazione LED PRG Descrizione 1 MRX Spento Premere e mantenere premuto il p...

Page 7: ...ng light positive Terminal Description Rated data E Encoder power supply positive 12 Vdc E Encoder power supply negative 41 Motor 1 encoder signal 45 Motor 2 encoder signal 99 Common inputs 51 Step by...

Page 8: ...type OFF Input 63 is for internal photocell ON Input 63 is for safety edge see DIP 7 for the safety edge type DIP 5 Photo test OFF Photo test function off ON Photo test on the negative accessory powe...

Page 9: ...en leaf M2 M2 closes at slow speed until it reaches the open mechanical stop 6 Close leaf M2 M2 closes at normal speed slows down at 70 of its travel and continues until it reaches the closed mechanic...

Page 10: ...e The PRG LED turns off End of procedure Note With this type of programming the mechanical stops are necessary both when opening and closing during programming and in normal operation The steps with a...

Page 11: ...ush button and hold it down until the green PRG LED starts flashing fast 2 Remote control push button Fast blink Press the remote control push button that you want to save 3 Fixed 1 s Button of the sa...

Page 12: ...clignotant Borne Description Donn es nominales E Positif alimentation codeur 12 Vcc E N gatif alimentation codeur 41 Signal codeur moteur 1 45 Signal codeur moteur 2 99 Commun entr es 51 Pas pas NO 5...

Page 13: ...e cellule photo lectrique interne ON Entr e 63 comme bord sensible pour le type bord sensible voir DIP 7 DIP 5 Phototest OFF Fonction phototest non active ON Fonction phototest active la borne d alime...

Page 14: ...usqu l arr t m ca nique de fermeture 7 Fermeture vantail M1 M1 se ferme la vitesse normale ralentit 70 de la course puis continue jusqu l arr t m ca nique de fermeture 8 Cycle complet Le portail ex cu...

Page 15: ...ue ce type de programmation n cessite des arr toirs m caniques en phase d ouverture et de fermeture durant la programmation et les man uvres normales Les phases sur fond gris correspondent une install...

Page 16: ...on LED PRG Description 1 MRX teinte Appuyer sur le bouton MRX et garder le doigt dessus jusqu ce que la led PRG verte com mence clignoter rapidement 2 Bouton radiocommande Clignotement rapide Appuyer...

Page 17: ...m x 11 Positivo luz rotativa Borne Descripci n Datos nominales E Positivo alimentaci n encoder 12 Vcc E Negativo alimentaci n encoder 41 Se al encoder motor 1 45 Se al del encoder del motor 2 99 Com...

Page 18: ...undos DIP 4 Tipo de en trada 63 OFF Entrada 63 como fotoc lula interna ON Entrada 63 como borde sensible para el tipo de borde sensible v ase DIP 7 DIP 5 Prueba de fotoc lulas OFF Funci n Prueba de fo...

Page 19: ...M2 cierra a velocidad normal al alcanzar el 70 de la carrera desacelera y sigue cerrando hasta el tope mec nico 7 Cierre de la hoja M1 M1 cierra a velocidad normal al alcanzar el 70 de la carrera desa...

Page 20: ...ocedimiento El LED PRG se apaga Procedimiento finalizado Nota con este tipo de programaci n los topes mec nicos de apertura y cierre son necesarios tanto durante la programaci n como en las maniobras...

Page 21: ...l de radio N Presi n pulsador Se alizaci n LED PRG Descripci n 1 MRX Apagado Pulse y mantenga pulsado el pulsador MRX hasta que el LED PRG empiece a parpadear r pidamente con luz verde 2 Bot n del man...

Page 22: ...uchte Klemme Beschreibung Nenndaten E Plusleiter Encoderversorgung 12 Vdc E Minusleiter Encoderversorgung 41 Encodersignal Motor 1 45 Encodersignal Motor 2 99 Bezugspotenzial Eing nge 51 Schrittmotor...

Page 23: ...ntaktleiste f r Typ der Kontaktleiste siehe DIP 7 DIP 5 Lichtschran kentest OFF Funktion Lichtschrankentest nicht aktiv ON Funktion Lichtschrankentest aktiv Die Phasenklemme Zubeh r Minus 0 geht f r e...

Page 24: ...Arretierung f r die Schlie endlage weiter 7 Schlie en Fl gel M1 M1 schlie t mit normaler Geschwindigkeit bremst bei 70 des Laufwegs ab und l uft bis zur mechani schen Arretierung f r die Schlie endlag...

Page 25: ...de des Vorgangs Die LED PRG erlischt Vorgang abgeschlossen Hinweis Mit dieser Programmierung sind die mechanischen Anschl ge sowohl beim ffnen als auch beim Schlie en und sowohl w hrend der Program mi...

Page 26: ...ulse Speicher voll Programmierung des zweiten Funkkanals Nr Tastendruck Anzeige LED PRG Beschreibung 1 MRX Aus Die Taste MRX dr cken und gedr ckt halten bis die LED PRG mit gr nem Licht beginnt schnel...

Page 27: ...N8 F1 ATO SEC DIP1 FM1 FM2 VS V PWR 51 F2 5X20 F3 15 A CNRX U1 41 51 52 61 62 63 45 SW12 T 15A T1 T2 TCA PROG MRX ON 1 2 3 4 5 6 7 8 9 10 PRG 21 22 26 25 12 19 18 14 1 0 10 11 E E 45 41 99 52 63 51 99...

Page 28: ...M1 trimmer FM2 M2 M2 trimmer VS trimmer V trimmer PROG MRX 51 Dip switch Dip DIP 1 OFF ON DIP 2 OFF 51 52 DIP 1 ON 51 51 ON DIP 3 OFF ON 3 DIP 4 63 OFF 63 ON 63 DIP 7 DIP 5 Foto test OFF foto test ON...

Page 29: ...52 61 OFF 61 ON 61 62 OFF 62 ON 62 63 OFF 63 ON 63 DIP 10 OFF 30 3 6 2 1 PROG PROG 3 LED PRG PROG 2 51 M2 51 M2 3 M1 M1 4 M1 M1 5 M2 M2 6 M2 M2 70 7 M1 M1 70 8 9 LED PRG DIP 10 OFF 2 1 PROG PROG LED...

Page 30: ...20 51 51 21 M1 22 LED PRG DIP 10 ON 30 3 6 2 1 PROG PROG 3 LED PRG PROG 2 51 M2 51 M2 3 M1 M1 4 M1 M1 5 M2 M2 6 M2 M2 7 M1 M1 8 9 LED PRG DIP 10 ON 2 1 PROG PROG LED PRG LED PRG PROG 2 51 M2 51 M2 3 M...

Page 31: ...12 T 15 M1 M1 16 M1 M1 17 51 51 18 M2 19 M2 M2 20 51 51 21 M1 22 LED PRG LED PRG 1 MRX MRX LED PRG 2 3 1 3 LED PRG 1 MRX MRX LED PRG 2 3 1 3 LED PRG 1 MRX MRX LED PRG 2 3 1 LED PRG 1 2 MRX MRX LED PRG...

Page 32: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 49401426A0 00 1909...

Reviews: