<octet-string>timestamp of the event</octet-string>
<octet-string>OBIS code of the event object</octet-string>
<unsigned>event code</unsigned>
Optionally, it may also contain another item:
<visible-string>custom event message</visible-string>
OBIS codes used:
Timestamp: 0.0.1.0.0.255
Event object: 0.0.96.11.0.255 (Standard), 0.0.96.11.1.255 (Fraud)
Custom event message: 0.128.96.11.0.255 (Standard), 0.128.96.11.1.255 (Fraud)
7.6.2 Event triggered push of data
7.6.2.1 Push On-Installation Event
This event is triggered when the meter list of a gateway is changed. The event triggers a push
with the event code On-Installation, which can be used by the HES to trigger a poll operation to
update the meter list (read meter list from the gateway).
The gateway will only trigger a single push, even if more than one meter is added/removed
during an operation. The hysteresis for grouping the event is three (3) minutes.
The payload of the Data Notification APDU has the following structure:
<octet-string>COSEM logical device name of the gateway</octet-string>
<octet-string>COSEM logical name of the push setup – on installation
object</octet-string>
<double-long-unsigned>ip adress of the gateway</double-long-unsigned>
<octet-string> System title of the gateway as defined in [4] 6.1.1</octet-
string>
The OBIS code for the push setup – on installation object is fixed to 0-7:25.9.0*255 (see [4],
section 7.2.1).