3 About Power System Configuration
User's Guide
Smartpack2 Master Controller
350020.013, Issue 2.0, 2014 Jan
31
Output Test Commands
This logical subgroup lets you issue or activate
specific commands to test the activation
of the alarm output relay contacts
. For example, following commands might be available
in
Smartpack S
controller’s submenu:
Commands > Output Test
#
Description
Action
Unit/Label
Note
Output Relay # 1
No
Tests alarm relay number 1
Output Relay # 2
No
Output Relay # 3
No
Output Relay # 4
Output Relay # 5
Output Relay # 6
The Output Test functionality enables to test and verify the circuits connecting external
equipment to the power system’s alarm relay outputs.
The Output Test command will toggle the alarm relay contacts -- regardless of the position
they are at the moment -- for a certain period of time (entered in the “Output Test Timeout
(sec)” in PowerSuite).
Issuing
commands is allowed
using a Pin-Code.
NOTICE:
The default Service Access Level password or Pin-Code is
<0003>, which may be changed for security reasons.
Alarm Outputs Isolation (Output Blocked)
When the user activates the “OutpBlocked” command, system alarms will NOT trigger any
alarm output group (similar to relay isolation), except for the “OutpBlocked, AOG” group,
which is always Alarm Output Group 18.
If an external warning is necessary, you can assign output relays to the “OutpBlocked,
AOG” group, e.g. to activate a lamp or alarm bell when the alarm output relays are
blocked.
The “OutpBlocked” command will reset all alarm output groups to normal status, and
possible new alarms will NOT trigger any alarm output groups (output relays activation is
blocked), except for AOG 18. Also, this command will always activate Alarm Output
Group 18 to facilitate external warning of this function being active.