![Eltek Smartpack2 User Manual Download Page 21](http://html1.mh-extra.com/html/eltek/smartpack2/smartpack2_user-manual_2397251021.webp)
3 About Power System Configuration
User's Guide
Smartpack2 Master Controller
350020.013, Issue 2.0, 2014 Jan
21
automatic configuration of specific functions
The “nn” in the file name specifies the unit’s CAN bus address.
Software Upgrade
which offers you to upgrade the firmware in connected controllers and
control units, by uploading files stored in the controller’s data storage device.
Read chapter “SD Card Storage - Overview Firmware Files (Binary
Format)”, page 21
Example of some of the available options in controller’s submenu:
Up/Download > Software Upgrade
#
Description
SW Info
Note
Compack 11
405006.009
0A.M
Smartpack1
402073.009
3.05E
I/O Unit 1
402088.009
3.01
SD Card Storage - Overview Firmware Files (Binary Format)
You can store binary files in the
Smartpack2 Master
controller’s SD card (data storage
device) and use them for firmware upgrading of controllers and control units, as well as for
exporting and importing configuration files.
NOTICE:
All firmware upgrade and configuration files stored in the SC card
must have specific file names.
The SD card uses the 8.3 file name format. Before storing the files on the SD card, you
must rename them, so that they conform to the specific file names described below.
For example, if you receive the file “SmartPack2_Basic_405007.009_V1.1.mhx” to
upgrade your
Smartpack2
Basic
controller firmware to version 1.1, you must first rename
the file to exactly “SP2BAS.MHX”, then copy the file to the SD card and finally insert the
SD card in the
Smartpack2 Master
controller to start the firmware upgrade process.
#
CAN Node
File Name
File Type
CAN Node Type
Smartpack2 Master
SP2MAST.BIN
Firmware upgrade
Controller
Smartpack2 Basic
SP2BAS.MHX
Firmware upgrade
Controller
Smartpack2 Basic Industrial
SP2BASIN.S19
Firmware upgrade
Controller
Smartpack
SP.MHX
Firmware upgrade
Controller
Smartnode
SMARTNOD.MHX
Firmware upgrade
Control Unit
Battery Monitor
BATTMON.HEX
Firmware upgrade
Control Unit
Load Monitor
LOADMON.HEX
Firmware upgrade
Control Unit
AC Mains Monitor
MAINSMON.HEX
Firmware upgrade
Control Unit
I/O Monitor
IO_UNIT.HEX
Firmware upgrade
Control Units:
I/O Monitor, Monitor2 & Monitor3
Flexi-Monitor
FLEXIMON.S19
Firmware upgrade
Control Unit
Any node
UNIT_aa.HEX
Configuration File (Save/Load)
All types
The “aa” refers to the CAN bus address or ID number.
E.g. “UNIT_82.HEX” could be the configuration file for I/O Monitor with CAN bus address 82.