Alarm Monitors 

Alarm  monitors  are  software  modules  used  by  the  system

 

controller  to 

measure  system 

internal and external input signals or logical states

When  an  alarm  monitor  is  enabled,  it 

compares  the  measured  parameter  with  the 

preprogramed  values  or  limits

,  and  raises  an  alarm  in  the  event  of  the  measured 

parameter reaching one of the limits. 

When this event occurs

, the alarm monitor stores the event in the Event Log, initiates an 

internal action and activates an output group. 

Internal  preprogrammed  actions  may  be  battery  current  limiting,  boost  inhibiting  or 
similar.  The  generated  alarm 

activates  a  preprogrammed  group  of  relay  outputs

  (an 

alarm output group, AOG). 

 

 
 

The  alarm  monitors’  most  commonly  used  configuration  parameters  are: 
(Refer to the “

Alarm Monitor dialog boxes

” topic in 

PowerSuite Online Help

 

Type of input

 

The measured Input Signal can be 

analogue

 (e.g. a voltage),  

logical

 (e.g. an open or closed contact) and 

numeric

 (e.g. number of rectifiers, % remaining capacity, etc.) 

 

Alarm Monitor activation

 

You have to 

Enable

 the alarm monitor so that it functions 

 

Type of alarm reset

 

You can select whether the alarm generated by monitor can be 

reset manually

or automatically (when the event that caused the alarm is no longer true) 

 

Hysteresis and Time delay 

 

When the input signal has reached a certain limit or criteria for a 

certain period 

of time

, the alarm monitor raises an alarm. This period of time is called 

Time 

Summary of Contents for Smartpack2

Page 1: ...350020 013 Monitoring and Control Units Powerpack Flatpack2 Minipack DC Power Supply Systems User s Guide Smartpack2 Master Controller...

Page 2: ...regular basis Indoor installations in dusty or humid areas require appropriate air filtering of the room or filtering of the air entering the DC power system Follow the instructions given in Generic...

Page 3: ...Introduction User s Guide Smartpack2 Master Controller 350020 013 Issue 2 0 2014 Jan 3 Part number for Smartpack2 Master Controller 242100 500 350020 013 Issue 2 0 2014 Jan Published 2014 03 06 mafen...

Page 4: ...ware Upgrade Controller 13 Firmware Upgrade from the SD Card 13 Firmware Upgrade from a Computer 14 Overview LAN Devices and Firmware Files PC S19 Format 14 3 About Power System Configuration 15 Logic...

Page 5: ...m and consists of the Smartpack2 Master SP2M controller the Smartpack2 Basic SP2B controller and the I O Monitor2 CAN node The Smartpack2 Master serves as the local user interface between you and the...

Page 6: ...are implemented in the Smartpack2 Master controller as mentioned below Graphical TFT high contrast high resolution color display for easy navigation LEDs for local visual alarming Major Minor Power O...

Page 7: ...the handle s knob slightly outwards use your fingers or a pen and 2 then slide the handle to the left the controller s right side opens 3 To close it slide the handle to the right the controller s ri...

Page 8: ...ends and plug it in one of the CAN ports on the last connected CAN node CAN Bus Cabling In addition to the two dedicated wires for communication the CAN bus multi wire cable must integrate wires for t...

Page 9: ...ugh the graphical menu structure via the following 6 front keys Press on the key to change from Status Mode to Menu Mode and to select options enter values Press the key to navigate to previous level...

Page 10: ...imated icons keys to press alarms system time etc Multi Info field Display area M Status Battery Bank Displayed in or in Ah Display area B Menu Mode Main Menu Options Level 1 Menu Icons Menu Names Men...

Page 11: ...Using the ENU program 1 Select the controller 2 Click in the Configuration button 3 Change from default 192 168 10 20 0 0 0 0 to e g IP address 169 254 52 133 255 255 0 0 Ping 169 254 52 133 first to...

Page 12: ...er Controller 12 User s Guide Smartpack2 Master Controller 350020 013 Issue 2 0 2014 Jan o o Technical Specifications o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o...

Page 13: ...grade and configuration files stored in the SC card must have specific file names Open the controller using your fingers or a pen see steps 1 2 above or chapter Opening and Closing Smartpack2 Master C...

Page 14: ...rogram ENU will transfer the specific firmware file s19 format from a LAN connected computer to the device or hardware platform LAN Device File Name examples File Type Smartpack S Smartpack S_ part _...

Page 15: ...user interface built in the controllers The PowerSuite program A PC application run on computers using MS Windows operating systems Logical Groups or Menu Options All the mentioned functions characte...

Page 16: ...llowed at this level using a Pin Code NOTICE The default Service Access Level password or Pin Code is 0003 which may be changed for security reasons The parameters are organized in system oriented gro...

Page 17: ...commands such as resetting manual alarms deleting the event log starting battery tests etc Issuing commands is allowed at this level using a Pin Code NOTICE The default Service Access Level password...

Page 18: ...rtpack2 Master Controller s submenu Logs Report Active Alarms Description Value Limit Alarm Group Output Note BatteryTemp 1 1 42 30 SymmVolt 1 1 12 91 1 50 Alarm Group 15 RectifierError 1 1 Minor Alar...

Page 19: ...Inventory Report The Inventory Report presents information that describes the power system the site s name serial number installation and service dates software name etc Example of Inventory Report ta...

Page 20: ...the Service Access Level NOTICE Using the CWUI Controller Web based User Interface or PowerSuite you can also up download to other storage media e g computer hard discs The Up and Download options ar...

Page 21: ...storing the files on the SD card you must rename them so that they conform to the specific file names described below For example if you receive the file SmartPack2_Basic_405007 009_V1 1 mhx to upgrad...

Page 22: ...ontrol units if several units of the same type are connected to the CAN bus the Smartpack S controller will request you to specify the CAN bus ID number of the unit to upgrade FTP Client The files sto...

Page 23: ...nhibiting or similar The generated alarm activates a preprogrammed group of relay outputs an alarm output group AOG The alarm monitors most commonly used configuration parameters are Refer to the Alar...

Page 24: ...ctions events are usually defined from factory Logical alarm monitors only compare the measured input signal with a logical state normally open or closed The user can define the alarm group that the m...

Page 25: ...rs LVD monitor the battery voltage and controls the LVD contactors Analogue and numerical alarm monitors compare the measured input with one to four user defined values or limits two above normal valu...

Page 26: ...tivate Parameters for Numerical Alarm Monitors N1 Example to monitor numeric values such as the number of rectifiers errors etc Description Value Unit Label Note Monitor Enable Disable Enable Activate...

Page 27: ...e options b MajorHigh AlarmLevel 280 Volt AC Major High upper limit MajorHigh AlarmGroup Mains Alarm Selects the alarm group to activate MinorHigh AlarmLevel 260 Volt AC Minor High upper limit MinorHi...

Page 28: ...OT reconnect the LVD contactor until Mains is ON again d Temperature Dependent Used with LVD contactors that disconnect the battery bank LVBD Check this option if you want that the LVD alarm monitor w...

Page 29: ...ng contactors Usually the first seven alarm output groups have alarm relay outputs already assigned to them from factory Factory Default Settings Typically alarm output groups 8 through 18 are listed...

Page 30: ...w Battery Alarm AOG 7 Rectifier Alarm AOG 8 Gen Set AOG 9 Alarm Group 9 10 Alarm Group 10 17 Alarm Group 17 18 OutpBlocked AOG 19 LVBD AOG 20 LVLD AOG 1 In the example above Alarm relay output 1 is us...

Page 31: ...ent for a certain period of time entered in the Output Test Timeout sec in PowerSuite Issuing commands is allowed using a Pin Code NOTICE The default Service Access Level password or Pin Code is 0003...

Page 32: ......

Reviews: