–   The gas meter marked with 

 must be in-

cluded in the equipotential bond when being 
installed in a potentially explosive atmosphere, 
e.g. by connecting it to a grounded pipeline. 
Installation must be carried out in accordance 
with EN 60079-14.

–   The gas meter marked with 

 must be pro-

tected from falling parts.

 

  If the calibration seal has been damaged or re-

moved, the gas meter is no longer approved for 
measurements which are subject to statutory 
testing. 

 

If the gas meter is stored or installed outdoors, 
protect the site against rain. Condensing humid-
ity is permitted.

    

Remove protective caps.

 

Installation in the horizontal position: connectors 
must be pointing upwards.

 

Note direction of flow (arrow).

 

The gas meter must not be in contact with ma-

sonry or other parts.

 

Ensure that there is sufficient installation space.

 

Ensure unobstructed view of the index.

 

The seal faces on the screw unions must be 

clean and damage-free.

 

For the compression of seals and the resulting 
tightening torques for the screw unions, the seal 
manufacturers’ specifications must be observed.

 

 Tightening torques for the recommended flat 

seals in conjunction with screw connectors 
pursuant to DIN  3376-1 and  3376-2, see 
www.docuthek.com 

 Elster-Instromet 

 Prod-

ucts 

 Gas measuring devices 

 Diaphragm 

meters 

 Ergänzung für Betriebsanleitung BK, 

Verschraubungen und Anzugsmomente für BK-
G1,6 bis BK-G25 (Supplement to BK operating
 

instructions, Screw unions and tightening tor-
ques for BK-G1.6 to BK-G25) (D).

    

Install the gas meter free of mechanical stress.

 

If a pulse transmitter IN-Z6x is used for pulse 
tapping on the gas meter marked with 

 – see 

Data sheet for pulse transmitter IN-Z6x (D, GB) 

 

www.docuthek.com 

 Elster-Instromet 

 Prod-

ucts 

 Gas measuring devices 

 Diaphragm 

meters 

 Pulse transmitter IN-Z61 and the 

standard EN 60079-14 (Explosive atmospheres).

Temperature test point

 

Temperature sensors can be inserted into the 

thermowells for measuring the gas temperature 
in the meter housing.

1

2

  

 Secure each of the temperature sensors using 

the capstan screw provided.

Connecting the pressure measuring 
line

 WARNING

In order to ensure that the gas meter is tight:

–   The pressure test nipple must not be twisted, 

bent, or otherwise manipulated.

–   When installing, always secure the pressure test 

nipple using a suitable spanner.

 

Functional safety and reliability are ensured only if 
the material combination of the screw connector 
and the pressure line are inter-matched.

 

Only use the olive and the attached union nut 
supplied. The olive is secured to the sealing 
sleeve.

 

When re-ordering, use original Parker EO pro-
gressive ring fittings PSR/DPR.

1

6

7

2

3

4

5

 

Use corrosion-resistant, seamless precision steel 
tube pursuant to DIN EN 10305-4 (external di-
ameter 6 mm, material E235 = 1.0308). For other 
materials, use a suitable adapter and note the 
Parker/EO recommendations.

 

Install pipes free of mechanical stress.

1

6

7

2

3

4

5

Summary of Contents for BK-G Series

Page 1: ...transported in the upright position On receipt of the product check that the delivery is complete see Part desig nations Report any transport damage immediately Storage Diaphragm gas meters are always to be stored in the upright position and in a dry place Ambient tempera ture see Technical data Changes to edition 05 13 The following chapters have been changed Checking the usage Commissioning Main...

Page 2: ...hekker mechanical index Absolute ENCODER index Electronic index Indication of volume at base conditions T Te TB Temperature conversion mechanical electronic mechanical electronic temperature conversion and pressure correction Part designations 2 1 3 4 6 5 1 Diaphragm gas meter BK 2 Index with index plate 3 Connectors 4 Protective caps 5 2 x thermowells optional 6 Pressure test point with sealing s...

Page 3: ...ermany TÜV 12 ATEX 098560 X II 2 G IIA T4 Use as follows Category internal none external Category 2 Zone 1 Type of atmosphere gases hazes and vapours Installation WARNING Please observe the following to ensure that neither persons nor the gas meter are damaged during installation and operation Note the max allowable operating pres sure pmax and measuring range Qmax see page 2 Type label Index plat...

Page 4: ...Anzugsmomente für BK G1 6 bis BK G25 Supplement to BK operating instructions Screw unions and tightening tor ques for BK G1 6 to BK G25 D 2 Install the gas meter free of mechanical stress If a pulse transmitter IN Z6x is used for pulse tapping on the gas meter marked with see Data sheet for pulse transmitter IN Z6x D GB www docuthek com Elster Instromet Prod ucts Gas measuring devices Diaphragm me...

Page 5: ...g the pulse transmitter IN Z6x can be connected see Data sheet for pulse transmitter IN Z6x D GB www docuthek com Elster Instromet Products Gas measuring devices Diaphragm meters Pulse transmitter IN Z61 BK G A with Absolute ENCODER index AE1 Z6 Interface description for gas meters with ENCODER index see Specification GB www docuthek com Elster Instromet Products Archive Gas measuring devices BK G...

Page 6: ...eleases the gas supply If consumers of the customer are open pressure equalization cannot occur and the valve remains in the Released position and continues to release only the minimum gas flow rate of the bypass Closed The valve and the bypass are closed in the event of remote shut down All valve positions are kept de energized Maintenance Removal Gas meters BK G1 6 to 25 from Elster are mainte n...

Page 7: ...i 30 mA Pi 33 mW Ci 140 µF Li 0 µH Diaphragm gas meters BK with integrated valve Vp Opening time 4 s Closing time 0 5 s Max operating pressure 100 mbar Leakage flow closed max 5 l h The specified leakage flow rate is also complied with at pressures 100 mbar e g in the event of a fault Diaphragm gas meters BK with integrated Smart Valve Vs Not suitable for highly contaminated gases e g town gas Ope...

Page 8: ...ische Bundesan stalt German National Metrological Institute Notified Body 0102 Markings M 0102 DE 11 MI002 PTB001 After the M the year of construction is given EMC EC Directive 2004 108 EC EMC Standards OIML D11 2004 Sec 12 EN 55022 2006 A1 2007 ETSI EN 301 489 17 V2 1 1 ETSI EN 301 489 1 V1 8 1 Tests and inspections EMC Test NRW GmbH Test Report No P10 Z 00086 002 P13 Z 00096 001 TRaC Global Ltd ...

Page 9: ...en EMC EC Directive 2004 108 EC EMC Standards EN 55022 2006 A1 2007 Class B EN 61000 4 2 2009 EN 61000 4 3 2006 A1 2008 A2 2010 EN 61000 4 4 2004 A1 2010 EN 61000 4 5 2006 EN 61000 4 6 2009 EN 61000 4 12 2006 EN 61000 4 8 2010 IEC 61000 6 3 2006 Class B Tests EMV Testhaus GmbH Test Report No 120393 AU01 E01 NMi Certin B V Test Report NMi 12200781 03 R TTE EC Directive 1999 5 EC R TTE Standards EN ...

Page 10: ...eaconside Stafford ST16 3EF T 44 1785 275200 F 44 1785 275305 jeavons info gb elster com www elstermetering co uk Ireland Active Energy Control Ltd Unit 4 Clare Marts Quin Road Ennis Co Clare T 353 65 6840600 F 353 65 6840610 info aec ie www aec ie Germany Elster GmbH Strotheweg 1 49504 Lotte T 49 541 1214 0 F 49 541 1214 370 info elster instromet com www elster instromet com Contact ...

Reviews: