Product Manual, Issue 6
CMS200
www.nexo.com
Page 60
6.3.35 Defrost heater (dHr)
Display
Description
Enables the use of an auxiliary relay to switch a defrost heater or solenoid valve. The
defrost heater is a heating element located below the evaporator.
Considerations
None
Range
0: Do not use a defrost heater.
1: Switch on the defrost heater during the defrost cycle and run the evaporator fan.
2: Switch on the defrost heater during the defrost cycle and do not run the evaporator
fan.
3: Switch on the defrost heater during the defrost cycle and do not run the evaporator
fan. The evaporator fan then remains off for one minute after the end of the defrost
cycle.
4: Switch on the defrost heater during the defrost cycle and do not run the evaporator
fan. The evaporator fan then remains off for two minutes after the end of the defrost
cycle.
5: Switch on the defrost heater during the defrost cycle and do not run the evaporator
fan. The evaporator fan then remains off for three minutes after the end of the defrost
cycle.
6: Hot gas defrost. That is, the relay switches a solenoid valve.
Global default
0
6.3.36 Shelf data enable (ShF)
Display
Description
Option to allow the Nexo controller to log stock sensing data to be sent to the cloud.
Considerations
Input will still be operational when viewed via the test routine (tSt).
Stock sensing hardware currently unavailable.
Range
0 (disabled) to 1 (enabled)
Global default
0 (disabled)