Product Manual, Issue 6
CMS200
www.nexo.com
Page 48
6.3.6 Lights delay (Ld)
Display
Description
Defines the delay to switch off the cooler lights after the controller switches to the
Saving mode.
Considerations
Set in multiples of 30.
Should only take affect once Delay to saving (dS) has completed.
Range
0 to 120 minutes (in multiples of 30 minutes)
Global default
0 (no delay)
6.3.7 Saving restart period (Sr)
Display
Description
Cooler runs at the ready mode temperatures for the duration of this period to ensure
that the product is at the ready mode temperatures prior to retail outlet opening time.
Considerations
•
Set and verified by OEMs through the test protocol to ensure that product
temperatures are within specification when outlets open.
• Set in multiples of 30 minutes.
Range
0 to 240 minutes (in multiples of 30 minutes)
Global default
120 minutes
6.3.8 Refrigeration system failure (Ct)
Display
Description
Defines the maximum continuous runtime of the compressor without reaching the set
point (SP) temperature.
If the set point (SP) temperature is not reached within this time, the controller enters
the RSF Limp home mode.
Considerations
None
Range
0 to 100 hours
Global default
72 hours