Addressing
IP interface and KNX power supply unit are addressed separately at the bus.
Addressing the IP interface
The IP interface is supplied with the bus address 15.15.0. You can program another
address in the ETS (product file of IP interface) by overwriting the 15.15.0 address or by
teaching via the programming key at the unit.
Addressing the KNX power supply unit
The power supply unit is supplied with the bus address 15.15.250. You can program
another address in the ETS (product file of power supply unit) by overwriting the
15.15.250 address or by using the “Prog. Mode” of the unit (see chapter
Addressing the
power supply unit (programming mode)
).
Settings in der ETS
Different product files are used for setting of the IP interface and the KNX functions of
the power supply unit.
Parametrise the IP interface
Use the product file of PS640-IP power supply unit, item number 70142.
For description of parameters please see manual, chapter
Setting the IP interface in the
ETS
.
Parametrise the KNX power supply unit
Use the product file of PS640+(USB) power supply unit, item numbers 70141, 70144.
For description of parameters please see manual, chapter
Setting the bus functions of
the power supply unit in the ETS
.
Settings at the device
Starting position
The following may be read off and set on the display of the Power Supply System KNX
PS640+IP:
Reset of a line
Recall of the data memory with operating hours, overcharge, external electrical
surge, internal electrical surge, short circuit and excess temperature
Recall of the operating data bus voltage, bus current and temperature
elsner elektronik
KNX PS640+IP
Normal Operation
Diagnostics >