25
Bit 6 = current threshold value exceeded
Bit 7 = system defect
= value 64
= value 128
A combination of error messages is possible. If e.g. value 34 is transferred, then Bit 1 =
Overload and Bit 5 = Overtemperature are set.
The value set in the menu “current threshold value” (see next chapter) is used as
current threshold value
. The additional settings for hysteresis etc. are
not
taken into
account for the status collection. Bit 6 “current threshold status exceeded” is set, if the
threshold value has been exceeded for 1 minute. The bit is immediately deleted again, if
the threshold value is underrun.
Error log:
……………………………
Use error log
No • Yes
If the error log is used:
Object “message part 1” sends signal:
Error no. (1 = latest error)
Object “message part 2” sends signal:
Error type
Object “message part 3” sends signal:
Date of error start
Object “message part 4” sends signal:
Time of error start