background image

Mounting of WS1 Color

1

Mounting of WS1 Color

 • Version: 30.06.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

Brief Instruction

Mounting of WS1 Color

Item numbers 60135-60142, 60145-46 (WS1 Color)

Warning, mains voltage! National legal regulations are to be 
observed. Installation, inspection, commissioning and 
troubleshooting of the device must only be carried out by a

competent electrician.

Notes on wireless equipment

When planning facilities with devices that communicate via radio, adequate radio
reception must be guaranteed.  The range will be limited by legal regulation and
structural circumstances. Avoid sources of interference and obstacles between re-
ceiver and transmitter, that could disturb the wireless communication. Those
would be for example:

Walls and ceilings (especially concrete and solar protection glazing).

Metal surfaces next to the wireless participants (e. g. aluminium 
construction of a conservatory).

Other wireless devices and powerful local transmitters (e.g. wireless 
headphones), which transmit on the same frequency. Please maintain a 
minimum distance of 30 cm between wireless transmitters for that reason.

Preparing the installation location

The device must only be installed and used in dry, interior 
spaces. Avoid condensation.

The device is to be installed flush to the wall surface. When selecting an installation
location, please ensure that the measurement results of the integrated temperatu-
re/humidity sensor are affected as little as possible by external influences. Possible
sources of interference include:

Direct sunlight

Drafts from windows and doors

Draft from ducts which lead from other rooms to the concealed box

Warming or cooling of the building structure on which the device is 
mounted, e.g. due to sunlight, heating or cold water pipes

Connection lines which lead from warmer or colder areas to the device

An external antenna can be connected in order to improve wireless communicati-
ons. During installation, a 

conduit 50 cm in length

 should be placed beneath the

recessed housing, in which the external antenna can be mounted (antenna dimen-
sions approx. 565 x 8 x 5, L × W × H in mm):

Preparing for installation

Wall-fitting

Cavity wall fitting

Assembling the control unit with concealed box

During electrical installation, please introduce all connection cables into the con-
cealed box through the lower or upper side wall. In the process, keep the individual
connection wires short to prevent long reserve loops.

After wiring, connect the ribbon cable to the screen board. Make sure that the
transport lock (foam) is removed and also remove the foil protecting the screen
(red flap). Screw the lower part of the housing onto the flush mounting box. Set
the frame on the lower part of the housing. To this end, the frame is first suspended
below and then clapped shut above and snapped in place.

Structure of the connector board WS1 Color

The manual with additional information about commissioning,
functions and use of the controls 

WS1 Color

 can be down-

loaded from www.elsner-elektronik.de in the menu area "Ser-
vice/Downloads".

External dimensions
of concealed box
in mm: 

(depth approx. 62 mm)

Conduit angled diagonally dow-
nwards (for cable access from 
above or below)

Conduit angled vertically downwards 
(only for cable access from above!)

concealed

concealed

45°

cable

cable

box

box

M16 conduit, 50 cm in length

M16 conduit, 
50 cm in length

Loosen the frame on the upper corners by
pulling it forward. You can press your
thumbs on the screen while doing this.

Take the frame off at the top first, then at
the bottom.

The lower portion of the housing is moun-
ted on the flush mounting box with 2
screws: loosen the screws.

Take off the housing component with the
screen board. The screen is connected via
a ribbon cable (1) with the board in the
flush mounting box. Loosen the plug in
order to be able to remove the upper part.

Remove the transport lock (2).

Remove the circuit board from the con-
cealed box to be installed a keep it in a
place where it is protected from dirt. 

It

may never be exposed to dust or mo-
isture!

For fitting, screw the cover (board) on to
the concealed box with the enclosed
screws.

Clamp the concealed box to the wall with
the four enclosed screws.

Upon delivery, the pouch containing the
assembly screws can be found in the con-
trol unit’s flush-mounted casing.

or

1 Drive group 1
2 Drive group 2
3 Drive group 3
4 Drive group 4
5 Mains connection L/N/PE 230 V/50 

Hz

6 Outer conductor L1
7 Multifunctional output 1 

(potential-free)

8 MF output 2 (potential-free)
9 Wall button 1 

(terminal 1: +12 V | 2: Up | 3: Down)

10 Wall button 2 

(4: +12 V | 5: Up | 6: Down)

11 Wall button 3 

(7: +12 V | 8: Up | 9: Down)

12 Wall button 4 

(10:+12V|11:Up|12:Down)

13 Weather station (terminals 1-2)

Wire assignment: red = 1, black = 2,
yellow and white = not connected

14*Multifunctional input 1 

(terminal 3: +12 V | 4: GND | 5: IN)

15*MF input 2 

(6: +12 V | 7: GND | 8: IN)

16 Connector for flat-ribbon cable to 

front board

17 Microfuse T6,3 A

* Supply voltage e. g. indoor sensor 

possible via MF inputs 
(No. 14, terminal 3(+), 4(-) and 
No. 15, terminal 6(+), 7(-)), 
max. 50 mA altogether.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

EN

Reviews: