background image

Item number 70395

Sewi KNX L

Indoor brightness sensor

EN

Installation and Ad justment

Summary of Contents for Sewi KNX L

Page 1: ...Item number 70395 Sewi KNX L Indoor brightness sensor EN Installation and Adjustment...

Page 2: ......

Page 3: ...ted circuit boards connections 6 2 4 Assembly 6 2 5 Notes on mounting and commissioning 7 3 Addressing the equipment 8 4 Maintenance 8 5 Transfer protocol 9 5 1 List of all communication objects 9 6 P...

Page 4: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Page 5: ...ic gates The output of each gate can be configured optionally as 1 bit or 2 x 8 bit 8 multi function modules computers for changing the input data by calculations by querying a condition or by convert...

Page 6: ...The device is only to be used for its intended purpose Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the dev...

Page 7: ...Errors excepted The Sensor Sewi KNX L is installed surface mounted on walls or ceilings 2 3 Construction of the sensor 2 3 1 Housing from the outside 1 Fig 1 1 Brightness sensors A Recess to open the...

Page 8: ...s connections 2 4 Assembly Fig 2 1 a b Long holes for mounting hole distance 60 mm 2 Brightness sensor 3 Programming button 4 Programming LED 5 KNX terminal BUS 6 Cable bushing A Mark for aligning the...

Page 9: ...or covered After the bus voltage has been applied the device will enter an initialisation phase last ing a few seconds During this phase no information can be received or sent via the bus Fig 4 Lead t...

Page 10: ...dress 15 15 255 You can program a differ ent address in the ETS by overwriting the address 15 15 255 or by teaching the device via the programming button The programming button is on the inside of the...

Page 11: ...1 bit 131 Brightness sensor 2 threshold value 1 Delay from 0 to 1 Input WC 7 5 DPT_Time PeriodSec 2 bytes 132 Brightness sensor 2 threshold value 1 Delay from 1 to 0 Input WC 7 5 DPT_Time PeriodSec 2...

Page 12: ...hold value 4 1 0 Input WC 1 1 DPT_Switch 1 bit 152 Brightness sensor 2 threshold value 4 Delay from 0 to 1 Input WC 7 5 DPT_Time PeriodSec 2 bytes 153 Brightness sensor 2 threshold value 4 Delay from...

Page 13: ...ing on setting 4 bytes 1158 Computer 3 Input I2 Input RWCT Depending on setting 4 bytes 1159 Computer 3 Input I3 Input RWCT Depending on setting 4 bytes 1160 Computer 3 Output O1 Output R CT Depending...

Page 14: ...ding on setting 4 bytes 1183 Computer 6 Input I3 Input RWCT Depending on setting 4 bytes 1184 Computer 6 Output O1 Output R CT Depending on setting 4 bytes 1185 Computer 6 Output O2 Output R CT Depend...

Page 15: ...96 Logic input 6 Input WC 1 2 DPT_Bool 1 bit 1397 Logic input 7 Input WC 1 2 DPT_Bool 1 bit 1398 Logic input 8 Input WC 1 2 DPT_Bool 1 bit 1399 Logic input 9 Input WC 1 2 DPT_Bool 1 bit 1400 Logic inp...

Page 16: ...logic 5 Block Input WC 1 1 DPT_Switch 1 bit 1431 AND logic 6 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1432 AND logic 6 8 bit output A Output R CT 5 010 DPT_ Value_1_Ucount 1 byte 1433 AN...

Page 17: ...logic 4 Block Input WC 1 1 DPT_Switch 1 bit 1459 OR logic 5 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1460 OR logic 5 8 bit output A Output R CT 5 010 DPT_ Value_1_Ucount 1 byte 1461 OR lo...

Page 18: ...er increments Input RWCT 5 1 DPT_Scaling 1 byte 1586 Light controller Target actual difference Input Output RWCT 9 4 DPT_Val ue_Lux 2 bytes 1587 Light controller Reset time Input Output RWCT 7 5 DPT_T...

Page 19: ...ld also be sent With Sensor Sewi KNX L the regulation is always started or stopped by an object Set the object evaluation and the object value prior to the first communication At the end of the regula...

Page 20: ...top 0 start 1 stop Object value prior to first communication 0 1 Reaction to stop send nothing send off command send on command send value Value in 0 100 Send the dim command if the actual value devia...

Page 21: ...ght point of installation for the sensor Set in which cases the correction factor received via object is to be retained Please note that the setting After power supply restoration and programming shou...

Page 22: ...initial start up as the factory settings are always used until the first call setting via objects is ignored Select whether the threshold value is to be specified per parameter or via a communi cation...

Page 23: ...ld value for setting in 0 100 50 Hysteresis in Lux for absolute setting 0 150000 30000 When the following conditions apply the output is LV Threshold value GW above 1 GW Hyst below 0 GW above 0 GW Hys...

Page 24: ...ted Set the delay for the switching and in which cases the switch output sends and which value is output at night Switching output sends on change do not send message Status object s send s Switching...

Page 25: ...Please note that the setting After power restoration and programming should not be used for the initial start up as the factory settings are always used until the first call setting via objects is ign...

Page 26: ...on Output 1 E1 X Y Output 2 E2 X Y Transformation General Tolerance for comparison in the case of prerequisite E1 E2 0 4 294 967 295 Input type Selection options depending on the func tion 1 bit 1 byt...

Page 27: ...epending on the type of output Output sends on change on change and after reset on change and periodically when receiving an input object when receiving an input object and periodically Type of change...

Page 28: ...t the block entry means and what happens in the event of a block Output sends on change on change and after reset on change and periodically when receiving an input object when receiving an input obje...

Page 29: ...for AND and OR logic Each logic output may transmit one 1 bit or two 8 bit objects Determine what the out put should send if logic 1 and 0 Value before first call 0 1 Output pattern On block do not s...

Page 30: ...Output value if logic 1 1 0 Output value if logic 0 1 0 Output value If block is active 1 0 Output value if monitoring period is exceeded 1 0 Object type Value 0 255 Percent 0 100 Angle 0 360 Scene c...

Page 31: ...e of logic and periodically on change of logic to 1 and periodically on change of logic to 0 and periodically on change of logic object receipt on change of logic object receipt and periodically Send...

Page 32: ...put 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input 15 inverted Logic input 16 Logic input 16 inverted Switching output night Switc...

Page 33: ...ic 2 inverted Switching output AND logic 3 Switching output AND logic 3 inverted Switching output AND logic 4 Switching output AND logic 4 inverted Switching output AND logic 5 Switching output AND lo...

Page 34: ...bH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49...