8
No. Name
Function
DPT
Flags
11
Temp. threshold value 1:
Switching output
Output
1.001
C R T
12
Temp. threshold value 1:
Switching output block
Input 1.006
C
W
13
Temp. threshold value 2: Absolute value
Input / Output
9.001
C R W T U
14
Temp. threshold value 2: (1:+ | 0:-)
Input
1.006
C W
15
Temp. threshold value 2:
Switching output
Output
1.001
C R T
16
Temp. threshold value 2:
Switching output block
Input 1.006
C
W
17
Temp. threshold value 3: Absolute value
Input / Output
9.001
C R W T U
18
Temp. threshold value 3: (1:+ | 0:-)
Input
1.006
C W
19
Temp. threshold value 3:
Switching output
Output
1.001
C R T
20
Temp. threshold value 3:
Switching output block
Input 1.006
C
W
21
Temp. threshold value 4: Absolute value
Input / Output
9.001
C R W T U
22
Temp. threshold value 4: (1:+ | 0:-)
Input
1.006
C W
23
Temp. threshold value 4:
Switching output
Output
1.001
C R T
24
Temp. threshold value 4:
Switching output block
Input 1.006
C
W
25
Temp. control: Switching object
(0:heating | 1:cooling)
Input 1.002
C
W
26
Temp. control: Target value current
Output
9.001
C R T
27
Temp. control: Blocking object
Input
1.006
C R W
28
Temp. control: Target value, day heating Input / Output
9.001
C R W T U
29
Temp. control: Target value, day heating
(1:+ | 0:-)
Input 1.002
C
W
30
Temp. control: Target value, day cooling
Input / Output
9.001
C R W T U
31
Temp. control: Target value, day cooling
(1:+ | 0:-)
Input 1.002
C
W
32
Temp. control: Act. variable heating
1. stage
Output
5.001
C R T
33
Temp. control: Act. variable heating
2. stage
Output
5.001
C R T
34
Temp. control: Act. variable heating
2. stage
Output
1.001