Motor control unit IMSG-UC-2H • Status 02/08/2011 • Subject to technical changes. Errors excepted. 

4

Individual movement position 

The IMSG-UC-2H can store one movement position for each connected drive. This allows 

fast and uncomplicated movement to a position that is needed often (e.g. a shutter 

position or the partial opening of a window). 

Storing a movement position 

Storing a position is carried out as follows: 

 

Move the drive to the starting/zero position, i.e. close the window, retract the 

awning or raise the blinds 

 

Press the 

 and   buttons for three seconds at the same time 

 

As feedback the drive moves briefly up and down. You are in now Programming 

mode 

 

Move to the desired position 

 

Store the position by pressing the 

 and   buttons for 1 second long at the same 

time 

 

As feedback the drive moves briefly up and down 

 

With blind slats, now open the slats to the desired angle. With awnings, tighten the 

canvas with 

. For windows, you can skip this point. 

 

Store by again pressing the 

 and   buttons for 1 second long at the same time 

 

As feedback the drive moves briefly up and down. The storage is complete and the 

IMSG-UC-2H is again in normal mode 

 

Note: As soon as a central command arrives (e.g. because of a wind or rain alarm), the 

Programming mode will be interrupted! In this case, please carry out the position 

storage again when the central command is no longer present.

 

Calling up a movement position 

The stored position can be called up by pressing the   button of the appropriate channel 

for 3-6 seconds.  

The drive will move to the movement position directly if it is in a secure position and the 

runtimes of previous commands have expired. If the drive is in an intermediate position, 

it will move initially to the secure position and then to the stored position after expiry of 

the runtime. 

 

Technical data 

Housing:  

Plastic

Colour:  

White

Installation:  

Series installation on mounting rails

Protection rating:  

IP 20

Dimensions:  

approx. 53 x 88 x 60 (W x H x D, mm), 3 modules 

Weight: 

 

approx. 190 g

Summary of Contents for IMSG-UC-2H

Page 1: ...MSG UC 2H Technical data Elsner Elektronik GmbH Steuerungs und Automatisierungstechnik Herdweg 7 D 75391 Gechingen Germany Phone 49 0 70 56 93 97 0 Fax 49 0 70 56 93 97 20 info elsner elektronik de www elsner elektronik de ...

Page 2: ...rection 1 second motor runtime 240 seconds Connect through clamps Potential free relays Central operation The central input of the IMSG UC 2H allows for example an automatic control unit a timeswitch or a normal unlocked double button Up Down to be connected The central command continuous voltage always has priority over a movement command from the extension inputs LED signals during central contr...

Page 3: ...ond the drive will move in a step by step fashion This allows for example slats to be positioned precisely If a button is held for longer than 1 second the drive moves to its final position switching off after 240 seconds of maximum runtime This is how you set the Standard mode Press the button on the channel to be set for 5 seconds and then additionally the button for longer than 1 second To conf...

Page 4: ...ghten the canvas with For windows you can skip this point Store by again pressing the and buttons for 1 second long at the same time As feedback the drive moves briefly up and down The storage is complete and the IMSG UC 2H is again in normal mode Note As soon as a central command arrives e g because of a wind or rain alarm the Programming mode will be interrupted In this case please carry out the...

Page 5: ...usively for appropriate use Any improper alteration or non observance of the operating instructions will void any warranty or guarantee claim After unpacking the unit shall be checked immediately for any possible mechanical damage The supplier shall be immediately notified in the event of any transport damage The motor control unit must not be used if damaged If it is assumed that danger free oper...

Page 6: ...please note Mixing different control voltages for central and on the spot operation is not permitted for IMSG UC If two motor control units are switched in series behind one another central commands Up and Down are looped through the N connections must be bridged for equipotential bonding Cable length for inputs max 200 m Control with 12V ...

Page 7: ...Motor control unit IMSG UC 2H Status 02 08 2011 Subject to technical changes Errors excepted 7 Control with 230V ...

Page 8: ...Motor control unit IMSG UC 2H Status 02 08 2011 Subject to technical changes Errors excepted 8 Connection example with several groups For IMSG UC 2H and or 4H ...

Reviews: