17
Setting of parameters
Brightness sensor KNX L
• Status: 20.12.2019 • Technical changes reserved. Errors reserved.
If the threshold value is set per Communication object:
Switching output
See „Brightness threshold value 1 / 2 / 3“
Blocking
„Blocking“ only appears if using „Switching output sends on change“
See „Brightness threshold value 1 / 2 / 3“
6.2.3. Logic
AND Logic
OR Logic
Threshold value setpoint per
Communication object
The value communicated last shall be
maintained
• not
• after restoration of voltage
(der geänderte Grenzwert kann
mindestens 100.000 Mal gesichert
werden)
• after restoration of voltage and
programming (Attention: Do not use for
first commissioning)
Start threshold value in lux
valid until 1. communication
(only if the value communicated last is
„not“ maintained or „after restoration of
voltage“)
0 … 1000; 200
Type of threshold change
• Absolute value with a 16 bit
communication object
• Increment / decrement with one
communication object
• Increment / decrement with two
communication objects
Step size
(only if sending „Increment/decrement“)
1 lux • 2 lux • 3 lux • 4 lux • 5 lux • 10 lux •
20
lux • 30 lux • 40 lux • 50 lux • 100 lux
Hysteresis of threshold value in %
0 … 50; 20
Communication objects logic inputs
do not release • release
Logic 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8
not active • active
Transmission delay of the switching
outputs after power up and programming
5 sec … 2 h
Logic 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8
not active • active
Transmission delay of the switching
outputs after power up and programming
5 sec … 2 h
Summary of Contents for 70119
Page 1: ...Item number 70119 EN KNX L Brightness Sensor Installation and Adjustment...
Page 2: ......
Page 23: ......