POLARIS 10●15●20●30●40●60●80●100●120●160
TRIPHASE-TRIPHASE
Rev. 04 – 06 December 2016
6
3.3 Display control panel
1) LED (from top to bottom: alarm / bypass / battery / inverter”)
2) TFT color display
3) Scroll button
4) Off button
5) On button (battery cold start switch)
3.4 Installation notes
Note: Consider for the convenience of operation and maintenance, the space in front and back of the
cabinet should be left at least 100cm and 80cm respectively when installing the cabinet.
◆
Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity, flammable gas
and liquid, corrosive. To avoid from high room temperature, a system of room extractor fans is
recommended to be installed. Optional air filters are available if the UPS operates in a dusty
environment.
◆
The environment temperature around UPS should keep in a range of 0°C
~
40°C. If the environment
temperature exceeds 40°C, the rated load capacity s hould be reduced by 12% per 5°C. The max
temperature can't be higher than 50°C.
◆
If the UPS is dismantled under low temperature, it might be in a condensing condition. The UPS can't be
installed unless the internal and external of the equipment is fully dry. Otherwise, there will be in danger
of electric shock.
◆
Batteries should be mounted in an environment where the temperature is within the required specs.
Temperature is a major factor in determining battery life and capacity. In a normal installation, the battery
temperature is maintained between 15°C and 25°C. Ke ep batteries away from heat sources or main air
ventilation area, etc.
WARNING!
Typical battery performance data are quoted for an operating temperature between 20°C and
25°C. Operating it above this range will reduce the battery life while operation below this range
will reduce the battery capacity.
◆
Should the equipment not be installed immediately it must be stored in a room so as to protect it against
excessive humidity and or heat sources.
CAUTION!
An unused battery must be recharged every 6months Temporarily connecting the UPS to a
suitable AC supply mains and activating it for the time required for recharging the batteries.
◆
The highest altitude that UPS may work normally with full load is 1500 meters. The load capacity should
be reduced when this UPS is installed in place whose altitude is higher than 1500 meters, shown as the
following table:
(Load coefficient equals max load in high altitude place divided by nominal power of the UPS)
Altitude
(Mt)
1500
2000
2500
3000
3500
4000
4500
5000
Load
coefficient
100%
95%
90%
85%
80%
75%
70%
65%
◆
The UPS cooling is depending on fan, so it should be kept in good air ventilation area. There are many
ventilation holes on the front and rear, so they should not be blocked by any obstacles.