POLARIS 10●15●20●30●40●60●80●100●120●160
TRIPHASE-TRIPHASE
Rev. 04 – 06 December 2016
4
◆
Charging Current is configurable
Via setting tool, the user may set the capacity of the batteries as well as reasonable charging current as
well as maximum charging current. Constant voltage mode, constant current mode or floating mode can
be switched automatically and smoothly.
◆
◆
◆
◆
Intelligent Charging Method
The series UPS adopts advanced three-stage charging method:
1
st
stage: high current constant current charging to guarantee to charge back to 90%;
2
nd
-stage: Constant Voltage in order to vitalize battery and make sure batteries are fully charged
3
rd
stage: floating mode.
With this 3-stage charging method, it extends the life of the batteries and guarantees fast charging.
◆
◆
◆
◆
LCD Display
With LCD plus LED displays, the user may easily get UPS status and its operational parameters, such as
input/output voltage, frequency & load%, battery % and ambient temperature, etc...
◆
◆
◆
◆
Intelligent Monitoring Function
Via optional SNMP Card, you may remotely control and monitor the UPS.
◆
◆
◆
◆
EPO Function
The series UPS may be completely shut off when the EPO is pressed. REPO function (Remote EPO) is
also available in this series UPS.
3. INSTALLATION
3.1 Unpack checking
1.
Don’t lean the UPS when moving it out from the packaging
2.
Check the appearance to see if the UPS is damaged or not during the transportation, do not switch
on the UPS if any damage found. Please contact the dealer right away.
3.
Check the accessories according to the list at Appendix 8 and contact the dealer in case of missing
parts.
3.2 Cabinet Outlook
Front View
Side View