15.2.2 Signals section
tag_job
defines the tag job. This is not used for this protocol and should be set to ”’1”.
tag_job_todo
defines the job subjob. This field should contain the exact representation of the
OBIS code as it is configured in the meter. E.g. if the parameter of interest is represented as
”1.8.0*24(0147238.4*kWh)”, the value of the configuration field should be ”1.8.0*24” (excluding
quotation marks).
Table 24: IEC 6205621 tag configuration
Parameter
Description
Type
Default
value
Example
tag_job
Tag job
string
n/a
1
tag_job_todo
Tag sub job
string
n/a
1.8.0, 11.8.0
For
tag_job_todo
configuration it is best to first manually read the meter via
PC or HHU (handheld unit) to determine the exact OBIS representation format
of the parameter as they can differ between meter manufacturers and utility
companies.
106